Description
In chemical processing, power generation, and test facilities where field transmitters and sensors deliver both process values and diagnostic data over shared wiring without separate communication networks, the GE IC695ALG626-CA combines high-density analog acquisition with embedded HART protocol support for PACSystems RX3i controllers.
It serves industrial automation applications like distillation columns tracking levels/pressures via 4-20 mA while extracting HART device variables for predictive maintenance, or turbine auxiliaries polling vibration and temperature with status alerts—all through 16 single-ended or 8 differential channels in one slot.
Product Introduction & Positioning
The GE IC695ALG626-CA is a 16/8-channel non-isolated differential analog input module with HART 5.0 communications for GE Emerson PACSystems RX3i universal backplanes, configuring channels independently for voltage (±10/0-10/±5/0-5/1-5 V) or current (0-20/4-20/±20 mA). Four internal HART modems enable bidirectional multidrop polling, delivering 24-bit ADC data as 32-bit float/integer plus HART secondary/tertiary variables to %AI registers via Proficy Machine Edition.
In RX3i architectures, it mounts hot-swappable (firmware-dependent) with software auto-calibration, supporting up to 512 ms scans while prioritizing HART traffic. It pairs with outputs like IC695ALG728 for closed loops with diagnostics.
Integrators position it for HART-enabled brownfield upgrades, consolidating analog + digital data streams without I/O multipliers or multiplexers.
Key Technical Features & Functional Benefits
Sixteen single-ended (or eight differential) channels update via configurable filters (8-500 Hz) with 24-bit resolution converted to floating-point or 16-bit integer, enabling 0.05-0.3125% accuracy across ranges. Four HART modems poll devices asynchronously, extracting PV/SV/TV/QV/status without interrupting analog scans.pdfsupply+1
Rugged design draws 600 mA @3.3 V/450 mA @5 V (4.5 W max) for 0-60°C operation with 120 dB CMRR at 50/60 Hz, mounting via standard terminal blocks. Diagnostics include underrange/overrange, open-wire, and HART fail states piped to PLC bits.
Proficy configures HART schedules and scaling; non-isolated design suits clean signal environments. Thermal derating applies in current mode per datasheet curves.
Detailed Technical Specifications
| Parameter | Value |
|---|---|
| Model | IC695ALG626-CA |
| Brand | GE Emerson PACSystems RX3i |
| Product Type | 16/8-ch analog input w/HART |
| Input Types | Voltage (±10/0-10/±5/0-5/1-5 V); Current (0-20/4-20/±20 mA) |
| Channels | 16 single-ended / 8 differential |
| Resolution | 24-bit ADC (32-bit float/16-bit int) |
| Accuracy | 0.05-0.3125% span (typ); HART pass-through |
| HART Support | 4 modems, protocol 5.0, multidrop |
| Update Rate | Configurable; filter-dependent |
| Backplane Power | 3.3 V @600 mA; 5 V @450 mA (4.5 W max) |
| Isolation | Non-isolated (field-device grounded) |
| Operating Temperature | 0 to 60 °C (derating in current mode) |
| Filters/CMRR | 8-500 Hz; 120 dB @50/60 Hz (8 Hz filter) |
| Terminal Block | Standard RX3i removable |
| Certifications | UL, CE, ATEX Zone 2 |
- IC695ALG626-CA
Related Modules or Compatible Units
IC695ALG628 – 8-channel HART variant with higher packing density.
IC695ALG704 – Analog output for HART-enabled loops.
IC695PNS001 – PROFINET scanner integrating IC695ALG626-CA data.
IC695CPU310 – RX3i CPU processing IC695ALG626-CA signals.
Installation Notes & Maintenance Best Practices
Wire GE IC695ALG626-CA transmitters single-ended with shields grounded at module, configuring HART polling intervals in Proficy pre-scan. Verify no CM noise via filter sweeps; baseline secondary variables during commissioning.
Monthly HART status checks for device health; quarterly full-range calibration. Hot-swap supported on later revisions.




WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626