Sale!

ABB 1KHL178025R0102P COM02 Communication Interface Module

ABB 1KHL178025R0102P COM02 is a communication interface board for ABB DCS backplanes, handling serial protocols between controllers and field devices or HMIs. Mounts as daughter card or slot module in AC31/800xA racks.

Categories: , , , , Brand:

Description

Product Core Brief

  • Model: 1KHL178025R0102P (COM02)
  • Brand: ABB
  • Series: Distributed Control Systems
  • Core Function: Communication interface board
  • Product Type: Network communication PCA
  • Key Specs: Multi-protocol serial, backplane mount
  • Condition: New Surplus

Key Technical Specifications

  • Type: COM02 communication module
  • Interfaces: RS-232/422/485 serial ports
  • Protocols: Modbus RTU, ABB SNP, Profibus DP
  • Power: 5 VDC backplane, <2 W consumption
  • Temperature: 0°C to 60°C operation
  • Isolation: 1.5 kV channel-to-bus
  • Baud rates: 300 bps to 115.2 kbps
  • Connectors: 9-pin D-sub, terminal blocks
  • Dimensions: 100 x 150 mm PCB approx.
  • Weight: 0.15 kg

Product Introduction

ABB 1KHL178025R0102P COM02 is a communication interface board for ABB DCS backplanes, handling serial protocols between controllers and field devices or HMIs. Mounts as daughter card or slot module in AC31/800xA racks.

Supports Modbus master/slave plus ABB native for remote I/O drops. Field installs link PLCs to SCADA over RS-485 up to 1200 m. Powers from backplane—no external supply. Set baud/DIP before bus scan; verify termination for Profibus.

Troubleshooting Quick Reference

Symptom Possible Cause Relevance to this Part Quick Check Method Recommendation
No TX/RX LEDs on serial Backplane +5 V dropout or fuse ✅ High Measure 5 VDC at power pins; continuity to host Reseat connector; check host slot power <2 W total 
Modbus timeout from master Baud/parity mismatch or echo ✅ High HyperTerminal loopback pins 2-3; 9600 8N1 std Match slave settings; disable echo in config
Profibus FDL errors rack-wide Terminator missing or stub >3 m ✅ Medium 220 Ω across A/B lines at ends; segment scope Add active terminator; max 32 drops per segment
Data garble on RS422 Common mode >7 V or shield ground loop ✅ High Voltmeter A-B idle >0.2 V; ground differential Single-end shield; isolator if >500 m run
Host no module detect Address conflict DIP or EEPROM corrupt ❌ Low Readback ID register via bus tool Clear EEPROM via programmer; document DIP photo 

Capture protocol analyzer trace before reset. Comms boards fail from spikes 75%—add surge protection. Photo LEDs/DIP for support.

P4LR 1KHL015107R0001
1KHL178025R0102P COM02

Frequently Asked Questions (FAQ)

Protocols supported—Modbus RTU only?
No, Modbus RTU/ASCII plus ABB CS31, Profibus DP-V0 slave. Config via DIP or COM200 software. Max 247 addresses.

Max cable distance per port?
RS485: 1200 m at 9600 bps. Profibus: 100 m/12 Mbps segment. Use repeaters beyond; twist shielded pairs.

Hot-plug into live backplane?
No—arcs damage traces. Power down rack, insert, verify latch. ESD strap required.

Power draw from host slot?
<2 W typical at 5 VDC. Leaves headroom in 5-slot racks. No external PSU needed.

❗ Common config error?
❗ Echo enabled on half-duplex RS485—collides TX/RX. Disable via switch 3 OFF. Lost half-shift chasing ghosts.

Condition and test details?
New Surplus: OEM stock, full Modbus loop + Profibus scan test on bench rack. All ports verified; no bent pins. Reports available.

Warranty, stock status?