Description
Core Product Summary (Brand / Model / Key Attributes)
The ABB PU515A (Order Code: 3BSE032401R1) is a specialized PCI-bus Real-Time Accelerator (RTA) board designed to connect personal computers and server workstations directly to ABB MasterNet (MB300) control networks. Functioning within the ABB System 800xA and Advant Master control architectures, the board offloads real-time MasterNet protocol processing and time-critical communication tasks from the host operating system’s main processor.
Featuring dual MasterNet (MB300) communication channels, the PU515A allows workstations to maintain high-speed, deterministic data exchange with AC 400 series controllers (such as AC 410, AC 450) and MasterPiece nodes. It provides dedicated processing power and onboard memory specifically tuned to manage high-throughput process data streams, system diagnostics, and alarm routing without impacting workstation application performance.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | ABB |
| Product Type | Real-Time Accelerator (RTA) Board |
| Model / Type Designation | PU515A |
| Order Code / Part Number | 3BSE032401R1 |
| Bus Interface | PCI expansion slot |
| Protocol Support | Dual-channel MasterNet (MB300) |
| Communication Speed | 10 Mbit/s (10,000 kbit/s) per channel |
| Channel Capacity | 2 Independent Channels (Dual Ch. MB300) |
| CPU Architecture | 1 Onboard Communication Microprocessor @ 25 MHz |
| Onboard Memory | 16 MB RAM |
| Physical Dimensions | 12.7 cm × 5.1 cm × 33 cm |
| Net Weight | 0.2 kg to 0.4 kg |
Detailed Product Overview
The ABB PU515A RTA board serves as an interface component for integrating PC-based engineering stations, operator workplaces, and connectivity servers into heritage and upgraded Advant Master control environments. In process automation plants using System 800xA for Advant Master, real-time deterministic communication is required to send control commands, monitor field tags, and collect trend logs. The PU515A satisfies this requirement by acting as an intelligent network coprocessor.
The board hosts its own 25 MHz microprocessor and 16 MB of dedicated onboard RAM. This hardware architecture isolates the execution of time-sensitive MB300 token-ring protocol tasks from host operating system latency. By handling low-level protocol execution, frame acknowledgment, and time synchronization locally on the PCI board, the host PC remains responsive to user interaction and higher-level database operations.
Dual MB300 channel support enables the implementation of redundant MasterNet communication paths. In critical process facilities, dual coaxial or AUI network cables connect to the channels, providing fault tolerance against physical cable breaks or transceiver failures without interrupting operator visibility or server data collection.

PU515A 3BSE032401R1
Engineering Selection Highlights
- PCI Slot Integration: Installs directly into standard 32-bit PCI expansion slots on compatible industrial PCs and servers.
- Offloaded Network Execution: Integrated 25 MHz processor handles MB300 protocol tasks locally, keeping host CPU resources free for applications.
- Dual-Channel Redundancy: Provides two independent MB300 channels operating at 10 Mbit/s for redundant network configurations.
- Advant Master Compatibility: Connects System 800xA connectivity servers directly to AC 450, AC 410, and MasterPiece controllers over MasterNet.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Control System Suite | System 800xA for Advant Master / Advant OCS | Requires 800xA MasterNet connectivity software drivers. |
| Host Workstation Hardware | PC / Server with an available 32-bit PCI expansion slot | Operates under supported 32-bit workstation operating system environments. |
| Network Interface | MasterNet (MB300) coaxial cable network | Connects via external transceiver / AUI cabling adapters. |
| Compatible Controllers | Advant Controller 450 (AC 450), AC 410, MasterPiece series | Interfaces via MB300 communication sub-modules (e.g., CS513). |
Dimensions, Mounting & Connection Notes
- Form Factor: Full-height, full-length PCI card layout.
- Dimensions: Approximately 12.7 cm Height × 5.1 cm Width × 33 cm Depth.
- Physical Weight: Net board weight is approximately 0.2 kg to 0.4 kg.
- Mounting Method: Plugs firmly into a PCI slot on the motherboard and secures via the standard rear enclosure retention screw.
- Cable Connections: Connects to MB300 transceivers using standard AUI/MB300 attachment cables.
- Handling Precautions: Standard anti-static ESD grounding protocols must be followed during insertion and removal to protect onboard CMOS components.
FAQ
What is the primary function of the ABB PU515A (3BSE032401R1)?
The PU515A is a PCI-based Real-Time Accelerator (RTA) board that provides dual-channel MasterNet (MB300) network communication for PCs and servers running ABB System 800xA for Advant Master.
Which network protocol does the PU515A support?
It supports the ABB MasterNet (MB300) industrial control network protocol operating at speeds up to 10 Mbit/s across two independent channels.
What slot type is required on the host PC for the PU515A?
The PU515A requires an available 32-bit PCI expansion slot on the motherboard of the host computer or server.
Does the PU515A support redundant network connections?
Yes. The board features dual MB300 communication channels, allowing connection to redundant MasterNet cable layouts for high-availability system designs.
Verification & Troubleshooting Notes
- Slot Alignment & Seating: Ensure the PC is powered off completely before insertion. Verify that the PCI edge connector is fully seated into the PCI slot and secured to the rear card frame.
- Driver & Device Recognition: After powering up the host PC, verify in the operating system Device Manager or 800xA hardware diagnostic tool that the RTA board driver initializes without resource conflicts.
- Transceiver & Cable Checks: Confirm that external AUI transceiver cables connected to the PU515A ports are locked in place and that transceiver power LEDs indicate active line status.
- Network Synchronization: Check the MasterNet diagnostic utilities in System 800xA to confirm that both MB300 channel 1 and channel 2 are active and communicating with network nodes without framing errors.

WhatsApp: +86 16626708626