Parameter Value
Product type Communication interface module (INSUM Ethernet interface) for AC 800M
Type designation / article number CI857K01 / 3BSE018144R1
Controller family ABB AC 800M (System 800xA / Compact Product Suite)
Communication protocol ABB’s INSUM
Role Master
Transmission speed 10 Mbit/s (Ethernet)
Connector RJ-45, female, 8-pin
Power supply Supplied from the processor unit via the CEX bus; no external power source required
24 V consumption 150 mA, typical
Categories: , , , , SKU: CI857K01 3BSE018144R1 Brand:

Description

Core Product Summary

The ABB CI857K01, article number 3BSE018144R1, is the INSUM Ethernet communication interface for the AC 800M controller family within ABB System 800xA and the Compact Product Suite. It connects an AC 800M controller to ABB’s INSUM system (Integrated System for User-optimized Motor control), the motor and switchgear control and protection platform, allowing the controller to read motor data, send commands, and integrate INSUM functions directly into its control application.

The module operates as an INSUM master at 10 Mbit/s over standard Ethernet via an RJ-45 female connector, with a typical closed-loop response of 500 ms, assuming a 250 ms control cycle time. It is powered entirely from the processor unit through the CEX bus, consuming a typical 150 mA at 24 V, so no external power supply is needed. Each AC 800M supports up to six CI857 modules, each of which can serve up to 128 MCUs (motor control units) or other INSUM devices. The module supports hot swap, can be used with High Integrity controllers, and is configured through function blocks in the INSUM Communication Library in Control Builder.

 

Key Technical Specifications

Parameter Value
Product type Communication interface module (INSUM Ethernet interface) for AC 800M
Type designation / article number CI857K01 / 3BSE018144R1
Controller family ABB AC 800M (System 800xA / Compact Product Suite)
Communication protocol ABB’s INSUM
Role Master
Transmission speed 10 Mbit/s (Ethernet)
Connector RJ-45, female, 8-pin
Power supply Supplied from the processor unit via the CEX bus; no external power source required
24 V consumption 150 mA, typical
Max. units on CEX bus 6 CI857 modules per AC 800M
Max. INSUM devices per CI857 128 MCUs (motor control units) or other INSUM devices
Max. INSUM TCP/IP gateways per CI857 2 (up to 128 INSUM devices and 4 LonWorks subnets per gateway, max. 32 devices per subnet)
Line redundancy No
Module redundancy No
Hot swap Yes
Usable with High Integrity controllers Yes
Operating temperature 0 to +55 °C
Storage temperature ‘-40 to +70 °C
Corrosion protection G3 per ISA 71.04
Protection class IP20 per EN60529 / IEC 529
Compliance CE marking, RoHS (EU, UAE, CN), WEEE Directive 2012/19/EU
Dimensions 59 mm W × 185 mm H × 127.5 mm D
Weight 700 g, including base

 

Engineering Selection Highlights

  • Protocol-specific role. The CI857 is not a general-purpose Ethernet card: it implements ABB’s INSUM protocol as the master side of the link to INSUM motor management. It cannot substitute for the PROFIBUS (CI854), MODBUS (CI853/CI867), or PROFINET (CI869) interfaces of the same controller family.
  • CEX bus budget limits module count. A maximum of six CI857 modules can be mounted on one AC 800M, and the CEX bus supply (max. 24 V, 2.4 A on the CPU) is shared with all communication modules, so total CEX-bus load must be checked when planning multiple interfaces.
  • Gateway architecture, not direct bus. The controller reaches INSUM devices through up to two INSUM TCP/IP gateways per CI857, each supporting up to 128 INSUM devices and up to four LonWorks subnets with 32 devices each; the gateway is therefore a required companion component in the network design.
  • Separate physical networks required. INSUM communication and the AC 800M Control Network must run on separate physical networks, which affects switch and cabling planning in the cabinet.
  • Controller-dependent device capacity. The total number of MCUs per AC 800M depends on the processor: up to 256 with PM864 or PM866, up to 128 with PM861, so the CPU type bounds the INSUM integration scope.
  • Hot swap and HI compatibility. The module supports hot swap and can be used with High Integrity (HI) controllers, simplifying maintenance in safety-relevant installations; however, neither line redundancy nor module redundancy is supported, so redundancy must be planned at the network or application level.
  • Software dependency. Configuration is done in Control Builder with the INSUM Communication Library function blocks (CI857InsumHwLib); the application accesses motor data and commands through these blocks rather than raw network configuration.
CI857K01 3BSE018144R1

CI857K01 3BSE018144R1

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Controller AC 800M processor units (PM861, PM864, PM866 and other AC 800M CPUs) Max. MCUs per controller depends on CPU type: 256 with PM864/PM866, 128 with PM861
Mounting / bus CEX-bus expansion rail of the AC 800M; powered from the processor unit No external 24 V supply connection; up to 6 CI857 per controller
Companion device INSUM TCP/IP gateway Required between the CI857 and the INSUM/LonWorks device level; up to 2 gateways per CI857
Device level INSUM MCUs and other INSUM devices, connected via LonWorks subnets behind the gateway Up to 128 INSUM devices per gateway; 4 LonWorks subnets with max. 32 devices each
Engineering software Control Builder (Compact Control Builder / 800xA Control Builder) with the INSUM Communication Library Function blocks provide access to INSUM motor data and commands
Network separation INSUM and the Control Network must use separate physical networks Plan dedicated switches or cabling for each network
High Integrity systems Usable together with High Integrity controllers Confirm the HI project’s approved hardware list

 

Dimensions, Mounting & Connection Notes

  • Module dimensions: 59 mm wide × 185 mm high × 127.5 mm deep; weight 700 g including the base plate.
  • The module mounts on the CEX bus of the AC 800M controller and draws its power from the processor unit; typical 24 V consumption is 150 mA.
  • Network connection is made through an RJ-45 female (8-pin) connector for the 10 Mbit/s INSUM Ethernet link.
  • The module supports hot swap, allowing replacement while the controller remains powered, subject to the system’s hot-swap procedures.
  • Operating environment: 0 to +55 °C ambient, IP20 protection (mounting in a suitable cabinet is required), and G3 corrosion protection per ISA 71.04.

 

Detailed Product Overview

The CI857K01 exists because modern process control systems rarely control motors directly through hard-wired I/O anymore. In plants with hundreds of motors, each motor is managed by a motor control unit in the switchgear that handles protection, starting, and interlocking locally. ABB’s INSUM platform is one such system, and the CI857 is the specific hardware interface that lets an AC 800M controller participate in it: the module acts as the INSUM master on an Ethernet network, and the control application communicates with motor control units through function blocks in the INSUM Communication Library.

The module’s position in the architecture is well defined. On one side, it plugs into the CEX bus of the AC 800M, the expansion rail on which communication interfaces such as PROFIBUS, MODBUS, and Satt I/O modules are mounted. It takes its power from this bus, drawing a typical 150 mA at 24 V, which means installation is a matter of slotting the module and connecting the network cable, with no separate supply wiring. On the other side, it presents a single 10 Mbit/s Ethernet port (RJ-45) toward the INSUM network. Between the CI857 and the motor control units sit the INSUM TCP/IP gateways: up to two per CI857, each aggregating up to 128 INSUM devices over four LonWorks subnets with up to 32 devices each.

Engineers evaluating this module for an existing or planned system should pay attention to three design boundaries. First, the CEX bus limit: an AC 800M carries at most six CI857 modules, and since the CEX bus also supplies the other communication interfaces, total load and slot count must be verified. Second, the CPU-dependent device budget: an AC 800M with a PM861 processor addresses up to 128 INSUM devices overall, while PM864 and PM866 processors support up to 256. Third, the network separation rule: INSUM traffic and the controller’s Control Network must not share physical cabling, which is a planning constraint rather than a configuration option.

From a maintenance perspective, the module is designed for live replacement. Hot-swap support means a failed CI857 can be exchanged without powering down the controller, and because the module itself carries no stored configuration beyond what Control Builder downloads, restoring operation is a matter of hardware replacement and re-downloading the controller configuration. Two limitations are worth stating plainly: the CI857 supports neither line redundancy nor module redundancy. High-availability designs must therefore handle INSUM network failures through application-level responses, not through redundant interface modules.

For procurement teams, the key identification point is the article number pairing: CI857K01 identifies the INSUM Ethernet interface variant of the CI857 family, and 3BSE018144R1 is the ABB article number under which the module is ordered and cross-referenced in the 800xA hardware selector. Because the AC 800M communication modules share the same mechanical format, verifying the protocol (ABB’s INSUM) and article number against the controller configuration is the safest way to avoid ordering a visually similar but functionally different interface such as the CI855 or CI860.

 

Applications & System Role

Within a System 800xA or Compact Control Suite architecture, the CI857K01 is the bridge between process control and electrical switchgear. INSUM is ABB’s integrated system for motor control and protection: motor control units (MCUs) mounted in the switchgear measure, protect, and operate the motors, and the CI857 makes that data available to the AC 800M application program. This lets a single control application coordinate process logic with motor management, including commands, status indications, time-stamped events, and time distribution into the switchgear.

The documented use case is motor and switchgear integration in distributed plant control: the AC 800M reads indications from motors through the CI857, processes them in its control cycle, and issues operation commands back through the same link, with a typical closed-loop time of 500 ms for an indication-to-command chain at a 250 ms control cycle. For an engineer, this positions the CI857 as part of the electrical integration layer of a plant control system, complementing the process I/O (S800 I/O via Modulebus or PROFIBUS) with dedicated low-voltage motor management communication.

 

FAQ

What is the ABB CI857K01 3BSE018144R1?
It is the INSUM Ethernet communication interface for the ABB AC 800M controller family, article number 3BSE018144R1, used in System 800xA and Compact Product Suite installations.

What does it do?
It acts as an INSUM master, connecting the AC 800M controller to ABB’s INSUM motor and switchgear control and protection system over 10 Mbit/s Ethernet, so the control application can exchange commands, status data, and events with motor control units.

Which controller does it require?
It mounts on the CEX bus of an AC 800M controller (for example with PM861, PM864, or PM866 processors), and up to six CI857 modules can be installed on one controller.

Does it need its own power supply?
No. The module is powered from the processor unit via the CEX bus, with a typical 24 V consumption of 150 mA.

How many INSUM devices can it support?
Each CI857 supports up to 128 MCUs or other INSUM devices, reached through up to two INSUM TCP/IP gateways, each handling up to 128 INSUM devices across four LonWorks subnets of up to 32 devices. The total per controller also depends on the CPU: up to 256 devices with PM864 or PM866, or 128 with PM861.

Is redundancy supported?
No. The CI857 supports neither line redundancy nor module redundancy, although it can be used with High Integrity controllers and supports hot swap.

How is it configured?
It is configured in Control Builder using function blocks from the INSUM Communication Library, which provide the application with access to INSUM motor data and commands.

What are its physical and environmental limits?
The module measures 59 × 185 × 127.5 mm, weighs 700 g including the base, connects via an RJ-45 female connector, and operates from 0 to +55 °C with IP20 protection and G3 corrosion protection per ISA 71.04.