Description
Core Product Summary (Brand / Model / Key Attributes)
The ABB CI867K01 (catalog order code 3BSE043660R1) is a Modbus TCP communication interface kit engineered for ABB AC 800M controller hardware within the System 800xA automation platform. The complete kit assembly includes the CI867 active communication module alongside its dedicated TP867 baseplate (part number 3BSE043662R1). Attaching directly to the controller’s Communication Expansion Bus (CEX-Bus), this module establishes high-speed Ethernet connectivity to integrate third-party PLCs, sub-systems, motor control centers (MCCs), and field instrumentation over Modbus TCP.
Equipped with two independent RJ-45 Ethernet interfaces, the CI867K01 operates as both a Modbus TCP Master (Client) and Slave (Server) simultaneously. Channel 1 supports 10/100 Mbit/s communication speeds for fast process data transfers, while Channel 2 operates at 10 Mbit/s. The unit supports up to 12 modules per CEX-Bus line and features galvanic isolation across Ethernet channels to protect AC 800M processor electronics against electrical noise in industrial control cabinets.
Key Technical Specifications
| Parameter | Specification / Value |
| Product Type | Modbus TCP Interface Kit (Module + Baseplate) |
| ABB Ordering Catalog Number | 3BSE043660R1 |
| ABB Type Designation | CI867K01 |
| Kit Components Included | CI867 Communication Module + TP867 Baseplate (3BSE043662R1) |
| Supported Protocols | Modbus TCP (Client/Master & Server/Slave modes) |
| Ethernet Interfaces | 2 × RJ-45 female 8-pin connectors (Channel 1: 10/100 Mbit/s; Channel 2: 10 Mbit/s) |
| System Expansion Bus | CEX-Bus (AC 800M Communication Expansion Bus) |
| Maximum Modules per CEX-Bus | Up to 12 modules |
| Power Consumption (24 V DC) | Typical 160 mA |
| Hot Swap Capability | Supported (Removal and Insertion Under Power via TP867 baseplate) |
| Operating Temperature Limit | Up to +55°C |
| Net Product Weight | 0.6 kg |
Detailed Product Overview
The ABB CI867K01 (3BSE043660R1) provides standardized Ethernet protocol translation for ABB AC 800M controller systems. In complex plant automation layouts, control systems must exchange process variable data, system status, and interlock signals with third-party automation equipment. The CI867K01 provides a native Modbus TCP interface within the Control Builder M engineering environment, removing the requirement for external protocol converter boxes.
Supplied as a hardware kit, the assembly comprises the removable CI867 interface module and the TP867 backplane baseplate. The TP867 baseplate clips onto a standard 35 mm DIN rail, extending CEX-Bus power distribution and communications to adjacent cards. The CI867 processor unit plugs into the baseplate, allowing hot-swappable module extraction and insertion without disrupting CEX-Bus power continuity to surrounding expansion cards.
Featuring two RJ-45 ports, the module handles multi-client Modbus TCP connections across industrial Ethernet topologies. Its internal firmware supports configurable master/slave data tables, allowing engineers to map Modbus holding registers, input registers, coils, and discrete inputs directly to control application variables in System 800xA.

CI867K01 3BSE043660R1
Engineering Selection Highlights
- Integrated Modbus TCP Master/Slave Functionality: Dual protocol engine enables simultaneous client and server communication over standard industrial Ethernet networks.
- Complete Kit Architecture: Delivered with both the CI867 processing unit and the TP867 baseplate for complete DIN-rail installation.
- Independent Dual Ethernet Ports: Provides two RJ-45 connections (10/100 Mbit/s and 10 Mbit/s) for flexible network routing and device connectivity.
- On-Line Hot Replacement: Supports Removal and Insertion Under Power (RIOP), allowing active module replacement on an energized TP867 baseplate without stopping the controller.
- Direct Control Builder M Configuration: Seamlessly configured within ABB engineering toolsets, eliminating external configuration software or third-party gateways.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| Control System Platform | ABB AC 800M Controller Series (PM860, PM861, PM864, PM865, PM866, PM867) | Connects via the controller CEX-Bus expansion line |
| Baseplate Unit | ABB TP867 Baseplate (3BSE043662R1) | Included in kit assembly; routes 24 V DC power and CEX-Bus signals |
| System Software | System 800xA / Control Builder M (Version 5.0 and higher) | Native hardware control libraries handle Modbus register mapping |
| Cabling Requirements | Standard Category 5e/6 STP (Shielded Twisted Pair) Ethernet cables | Use shielded RJ-45 connectors to preserve EMI protection ratings |
Dimensions, Mounting & Connection Notes
- Form Factor: Modular DIN-rail card assembly (59 mm width).
- Net Weight: 0.6 kg.
- Mounting Method: TP867 baseplate snaps onto standard 35 mm DIN rail (EN 50022).
- Power Supply Distribution: Receives 24 V DC logic power directly through the CEX-Bus backplane via the TP867 baseplate connection.
- Network Connectors: 2 × female 8-pin RJ-45 Ethernet ports on the front panel.
- Grounding Requirements: Baseplate features metallic grounding spring clips that contact the DIN rail; ensure the rail is connected to a low-impedance protective earth (PE).
FAQ
What is included in the ABB CI867K01 kit?
The CI867K01 kit (3BSE043660R1) includes the active CI867 Modbus TCP communication interface module and the passive TP867 CEX-Bus baseplate assembly.
What protocols does the CI867K01 support?
The module supports Modbus TCP protocol operating in both Master (Client) and Slave (Server) roles over industrial Ethernet links.
How many CI867K01 modules can be attached to one AC 800M controller?
A single AC 800M controller setup can support up to 12 modules on its CEX-Bus expansion line, depending on overall system power budget and application memory limits.
Can the CI867 module be replaced while the controller is running?
Yes. The assembly supports Removal and Insertion Under Power (RIOP). The active CI867 module can be unlatched and replaced on an energized TP867 baseplate without interrupting power to neighboring CEX-Bus cards.
Verification & Troubleshooting Notes
- Baseplate Engagement: Ensure side-locking levers on the TP867 baseplate are locked with adjacent CEX-Bus modules before mounting the CI867 processing card.
- Front-Panel Diagnostic LEDs:
- RUN (Green): Indicates normal operating state and initialized protocol execution.
- FAULT (Red): Flags hardware errors, self-test failures, or unconfigured network states.
- Channel LNK/ACT (Green/Yellow): Indicates active Ethernet link detection and packet traffic on the RJ-45 ports.
- Network IP Configuration: Verify that IP address assignments, subnet masks, and Modbus device slave IDs match settings in Control Builder M to prevent communication timeout errors.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626