Description
Core Product Summary (Brand / Model / Key Attributes)
The ABB DI810 (catalog order number 3BSE008508R1) is a 16-channel 24V DC digital input module belonging to the ABB S800 I/O product family. Engineered for use with System 800xA, AC 800M controllers, and Advant OCS control systems, this module monitors field contacts, pushbuttons, limit switches, and discrete proximity sensors across industrial automation process environments.
The module features 16 discrete input channels split into two individually isolated groups of 8 channels. Operating across a nominal voltage range of 18V DC to 30V DC with current-limiting input circuitry, the DI810 incorporates internal hardware filtering (~3 ms input delay) to eliminate contact bounce and field signal noise. Designed to mount onto standard S800 Module Termination Units (MTUs), the DI810 supports hot-swappable module replacement under power without disturbing field wiring or backplane bus communications.
Key Technical Specifications
| Parameter | Specification / Value |
| Product Type | Digital Input Module |
| ABB Catalog Part Number | 3BSE008508R1 |
| ABB Type Designation | DI810 |
| I/O System Family | ABB S800 I/O (System 800xA / AC 800M / Advant) |
| Number of Channels | 16 discrete digital inputs |
| Channel Group Isolation | 2 isolated groups of 8 channels each |
| Nominal Input Voltage | 24V DC (operating voltage range: 18V DC to 30V DC) |
| Input Current | 6 mA to 7 mA per channel at nominal 24V DC |
| Input Type | Current sinking (negative logic) |
| Hardware Input Filter Delay | Typ. 3 ms |
| Power Dissipation | Max. 2.1 W at nominal 24V DC |
| Module Hot Swap | Supported (Removal and Insertion Under Power via MTU) |
| Dimensions (W × H × D) | 45 mm × 119 mm × 102 mm |
| Net Product Weight | 0.2 kg |
Detailed Product Overview
The ABB DI810 (3BSE008508R1) is a fundamental signal acquisition card within ABB’s S800 I/O platform. In continuous process industries—such as chemical manufacturing, power generation, oil and gas, and water treatment—the module interfaces field-level binary switch contacts with central AC 800M controllers or Advant master stations.
The module organizes its 16 channels into two galvanically isolated 8-channel groups. This split-group isolation allows field engineers to isolate distinct power source zones or separate emergency shutdown loops without adding intermediate isolation relays. Each channel includes input current-limiting components and EMC filtering networks to protect internal logic circuits against high-voltage spikes, ground potential shifts, and inductive line noise.
Mounting onto an S800 Module Termination Unit (such as the TU810 or TU812), the active DI810 electronics card snaps onto the base while field wiring lands on the MTU terminal block. This separation enables Removal and Insertion Under Power (RIOP), allowing plant maintenance technicians to unlatch and replace a faulty module without disconnecting field terminal wiring or interrupting power to adjacent I/O modules on the ModuleBus.

DI810
Engineering Selection Highlights
- S800 I/O Architecture Compatibility: Directly compatible with System 800xA, AC 800M controllers, and Advant OCS platforms via ModuleBus communication.
- Dual Group Isolation (2 × 8 Channels): Provides galvanic isolation between two 8-channel groups to isolate separate field power feeds or independent signal zones.
- Built-in Current Limiting & Noise Filtering: Hardware-level ~3 ms filter time suppresses contact bounce and voltage transients caused by long field cable runs.
- Hot-Swappable MTU Mounting: Supports Removal and Insertion Under Power (RIOP), allowing module replacement without stopping controller execution or disconnecting field wiring.
- Individual Channel LED Indication: Front-panel green LEDs provide immediate visual verification of signal state for each of the 16 input channels.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| Control System Platforms | ABB System 800xA, AC 800M, Advant Controller 800, MasterPiece 200/90 | Communicates via S800 ModuleBus |
| Compatible Termination Units | TU810, TU812, TU814, TU818, TU830, TU833, TU838, TU850 | Select MTU based on terminal connection style (screw, spring, or crimp) |
| Field Power Feed | 24V DC process power supply (18–30V DC) | Requires external 24V DC loop power for field contact excitation |
| System Software | Control Builder M / Compact Control Builder | Module hardware parameters are configured via standard S800 I/O libraries |
Dimensions, Mounting & Connection Notes
- Form Factor: Compact S800 I/O module plug-in unit.
- Dimensions: Width: 45 mm, Height: 119 mm, Depth: 102 mm.
- Net Weight: 0.2 kg.
- Mounting Method: Snaps directly into an S800 Module Termination Unit (MTU), which mounts onto a standard 35 mm DIN rail.
- Field Wiring: Connects through the underlying MTU terminal block; no direct wire connections are made to the DI810 module housing itself.
- Grounding: Internal logic and bus shield grounding are established automatically via the MTU ground clip on the DIN rail.
FAQ
What is the primary function of the ABB DI810 module?
The ABB DI810 (3BSE008508R1) is a 16-channel 24V DC digital input module used in S800 I/O systems to monitor binary field signals such as switch contacts, sensors, and alarm contacts.
Which Module Termination Units (MTUs) are compatible with the DI810?
The DI810 module is compatible with several S800 MTUs, including the TU810, TU812, TU814, TU818, TU830, TU833, TU838, and TU850 baseplates.
Can the DI810 module be hot-swapped while the system is powered?
Yes. The DI810 supports Removal and Insertion Under Power (RIOP) when mounted on an S800 MTU, allowing live replacement without interrupting adjacent I/O modules.
How are the input channels on the DI810 isolated?
The 16 channels are divided into two isolated groups of 8 channels each, providing galvanic isolation between the two groups as well as between the field circuits and the internal ModuleBus.
Verification & Troubleshooting Notes
- Module Lock Verification: Ensure the MTU locking mechanism is fully engaged after inserting the DI810 module to maintain reliable backplane connector contact.
- Front-Panel LED Indicators:
- POS / FAULT (Red/Yellow): Indicates module power status or internal self-test fault conditions during boot.
- Channel LEDs (1–16 Green): Illuminate when the corresponding field contact closes and completes the 24V DC circuit.
- Field Power Check: If an entire group of 8 channels fails to respond, verify that the 24V DC field process voltage supply connected to that group’s MTU terminals is active.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626