Description
Core Product Summary (Brand / Model / Key Attributes)
The ABB IMHSS03 (Hydraulic Servo Slave Module) is a specialized closed-loop positioning card developed for the ABB Bailey INFI 90 and Symphony Strategic Process Management System architectures. Engineered for demanding turbomachinery and heavy utility positioning loops, this module provides high-speed interface control between central system processing units and electro-hydraulic servo valves or hydraulic actuators used in steam turbine governing systems.
The IMHSS03 operates as a slave module within standard INFI 90 module mounting units, handling real-time position control, LVDT (Linear Variable Differential Transformer) excitation/feedback processing, and servo valve driver output generation. By processing high-speed position feedback locally at the sub-rack level, the module offloads microsecond-level servo loop calculations from the main controller, ensuring deterministic valve response and tight position regulation under rapid turbine load changes.
Key Technical Specifications
| Parameter | Specification / Value |
| Product Type | Hydraulic Servo Slave Module |
| Model Designation | IMHSS03 |
| System Architecture | ABB Bailey INFI 90 / Symphony Strategic Process Management System |
| Control Loop Type | High-speed closed-loop hydraulic positioning and servo valve control |
| Position Transducer Support | LVDT (Linear Variable Differential Transformer) / RVDT inputs |
| LVDT Excitation Frequency | Onboard high-frequency AC excitation voltage source |
| Analog Servo Output | Proportional current/voltage driver outputs for electro-hydraulic servo valves |
| Module Interfacing | INFI 90 Backplane Slave Bus (communicates with Multi-Function Controllers) |
| Form Factor / Mounting | Standard INFI 90 Module Mounting Unit (MMU) slot |
| Enclosure Rating | IP20 (when installed in standard cabinet enclosure) |
Detailed Product Overview
The ABB IMHSS03 Hydraulic Servo Slave Module acts as the dedicated positioning interface within ABB Bailey INFI 90 distributed control systems. In power generation plants and heavy process installations, regulating steam turbine throttle valves, governor valves, and fuel control actuators requires precise, high-speed closed-loop control. Standard process I/O modules lack the high excitation frequencies and microsecond-level update rates needed to drive hydraulic servo valves without position hunting or phase lag.
The IMHSS03 addresses these requirements by integrating an onboard LVDT signal conditioner and a bipolar servo driver stage. The module energizes field-mounted LVDTs with a regulated AC excitation signal, demodulates the position feedback signal, and compares it against setpoints received over the INFI 90 slave bus from a host controller (such as an IMMFP12 or BRC module). The internal control hardware calculates proportional-integral position corrections and drives the electro-hydraulic servo valve coils directly, maintaining accurate valve positioning under heavy hydraulic flow forces.

IMHSS03
Engineering Selection Highlights
- INFI 90 / Symphony Native Integration: Mounts directly into standard INFI 90 sub-racks and communicates seamlessly over the internal slave bus with host controllers.
- Dedicated LVDT Conditioning: Provides integrated AC excitation supply and precision demodulation circuitry for dual or single LVDT position feedback sensors.
- Deterministic Servo Loop Processing: Offloads high-frequency position loop calculations from main system processors to maintain sub-millisecond servo loop execution.
- Bipolar Servo Driver Output: Generates direct coil drive currents to operate standard industrial electro-hydraulic servo valves (such as Moog or Abex valves).
- Fault Monitoring & Interlocking: Continuously monitors LVDT signal integrity, feedback wire breaks, and power supply rails to initiate safe trips if feedback continuity is lost.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| Control System Architecture | ABB Bailey INFI 90, Network 90, Symphony System | Plugs into standard Module Mounting Unit (MMU) slots |
| Host Controller Dependency | Requires an active Master Controller (e.g., IMMFP12, BRC100/200/300) | Communicates via the internal rack slave bus |
| Terminal Units | Compatible with INFI 90 NTDI or NTMP Termination Units | Connects to field LVDT cabling and servo valve leads via field termination cables |
| Field Devices | Standard 3-wire / 4-wire LVDTs and electro-hydraulic servo valves | Verify coil resistance and LVDT voltage/frequency specifications prior to wiring |
Dimensions, Mounting & Connection Notes
- Form Factor: Standard double-width or single-width INFI 90 plug-in circuit card module.
- Mounting Method: Slides into designated card guide slots within an INFI 90 Module Mounting Unit (MMU) rack assembly.
- Backplane Interfacing: Connects to the INFI 90 backplane via rear multi-pin edge connectors for slave bus communication and logic power.
- Field Wiring Routing: Field signals route through a rear cable ribbon from the backplane to an external field termination unit (NT series).
- ESD Safe Handling: Card components are sensitive to static electricity; technicians must use grounded wrist straps when handling or installing the module.
FAQ
What is the primary function of the ABB IMHSS03 module?
The ABB IMHSS03 is a Hydraulic Servo Slave Module used in INFI 90 and Symphony control systems to provide closed-loop position control for electro-hydraulic servo valves and hydraulic actuators.
Which control system platforms support the IMHSS03?
The IMHSS03 is designed for the ABB Bailey INFI 90, Network 90, and Symphony Strategic Process Management System platforms.
What position feedback devices connect to the IMHSS03 module?
The module directly supports Linear Variable Differential Transformers (LVDTs) and Rotary Variable Differential Transformers (RVDTs), providing onboard AC excitation and signal demodulation.
How does the IMHSS03 communicate with the main process controller?
The IMHSS03 operates as a slave module on the INFI 90 backplane bus, exchanging setpoints, diagnostic status, and position values with a host controller (such as an IMMFP12 or BRC processor).
Verification & Troubleshooting Notes
- Module Seating: Ensure top and bottom captive screws are fully tightened after sliding the IMHSS03 card into the MMU rack slot to establish solid backplane pin engagement.
- LVDT Excitation Verification: If position feedback reads zero or flags an out-of-range alarm, measure the AC excitation voltage output across the LVDT excitation terminals to verify generator operation.
- Servo Null Adjustment: During system commissioning or valve setup, adjust servo coil offset currents per OEM procedure to ensure the valve stays at a stable zero position when setpoint equals feedback.
- Diagnostic LEDs: Inspect front-panel diagnostic indicators (Status / Error) after cabinet power-up to confirm successful self-test completion and active slave bus communication.