Description
Core Product Summary (Brand / Model / Key Attributes)
The ABB NTAI05 is an analog input termination unit designed for use within the ABB Bailey INFI 90 and Network 90 Distributed Control System (DCS) architectures. It acts as the physical field-wiring interface, connecting field sensors and transmitters to the corresponding INFI 90 analog input modules (such as the SAI02 or DAI01 modules). By routing field signals into the control system, the NTAI05 plays a foundational role in process parameter monitoring across power generation, chemical, and continuous process industrial applications.
Constructed for high-density panel mounting, the ABB NTAI05 provides screw terminal blocks to terminate analog field signals safely and securely. The board routes input signals via specialized ribbon cables directly to the system module backplane or dip-bus, maintaining signal integrity and simplifies wiring management during cabinet assembly. Its passive PCB layout ensures stable signal routing with low thermal and electrical interference under standard cabinet operating conditions.
Key Technical Specifications
| Parameter | Specification |
| Manufacturer | ABB / Bailey Controls |
| Model / Part Number | NTAI05 |
| System Family | INFI 90 / Network 90 DCS |
| Module Type | Analog Input Termination Unit |
| Signal Type | Analog Input (4–20 mA, 1–5 VDC, voltage/current loop options depending on module) |
| Channel Capacity | Up to 8 or 16 channels (dependent on paired INFI 90 input module configuration) |
| Connection Type | Screw terminal blocks for field wiring; ribbon cable connector for module connection |
| Mounting Style | Standard INFI 90 termination unit mounting frame / DIN rail / Field termination panel |
| Operating Temperature | 0°C to +55°C (32°F to 131°F) operating cabinet range |
| Relative Humidity | 5% to 95% (non-condensing) |
Detailed Product Overview
The ABB NTAI05 Termination Unit functions as a passive interface board bridging field instrumentation and the Bailey INFI 90 processing hardware. In DCS architectures, field transmitters monitor process parameters such as flow, pressure, temperature, and level. The NTAI05 accepts incoming field cabling at its onboard screw terminals and conditions or routes those signals directly to the input processing card via standard multi-conductor cables.
By decoupling the physical field wiring from the active processing module, the NTAI05 simplifies installation, system maintenance, and hot-swapping procedures. Maintenance personnel can disconnect or replace the active INFI 90 input card without disturbing the physical field wiring attached to the NTAI05 terminal blocks.
The physical design of the unit focuses on noise rejection and reliable electrical connections. Traces on the printed circuit board are laid out to minimize crosstalk between channels, ensuring that high-accuracy analog signals reach the input card without signal degradation. The terminal blocks are clearly labeled per channel to assist technicians during initial cabinet wiring, loop testing, and routine troubleshooting.
Engineering Selection Highlights
- INFI 90 System Integration: Designed specifically to interface with Bailey INFI 90 / Network 90 analog input processing modules.
- Decoupled Field Wiring: Allows module removal or replacement without disconnecting individual field wires from the terminal panel.
- High-Density Channel Layout: Compact footprint optimizes space usage inside industrial control cabinets.
- Clear Channel Identification: Labeled terminal positions streamline signal verification, loop checking, and maintenance diagnostics.
- Passive Signal Routing: Robust printed circuit board design minimizes signal conditioning overhead and failure points.

NTAI05
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| Control System | ABB Bailey INFI 90 / Network 90 | Standard cabinet termination rack mounting. |
| Companion Module | INFI 90 Analog Input Modules (e.g., SAI02, DAI01 series) | Paired via standard Bailey cable assemblies. |
| Connecting Cable | Multi-conductor ribbon cable (e.g., NKAI series) | Interconnects the NTAI05 header to the module mounting unit. |
| Field Wiring | Twisted pair / shielded pair analog transmitter cabling | Connects directly to the terminal screw blocks. |
Dimensions, Mounting & Connection Notes
- Mounting Method: Mounts into standard INFI 90 termination unit chassis / sub-rack assemblies inside field cabinets.
- Field Connection: Heavy-duty screw terminals accepting stranded or solid copper wire (typically AWG 24 to 12).
- System Connection: Multi-pin male header connector for ribbon cable connection to the system module rack.
- Clearance Requirements: Ensure sufficient bend radius for incoming field wire bundles and system interconnect cables to prevent strain on the PCB connectors.
- Shielding & Grounding: Connect field cable shields according to standard INFI 90 grounding practices to prevent ground loops and ambient noise coupling.
FAQ
What is the primary function of the ABB NTAI05?
The ABB NTAI05 is an analog input termination unit used in Bailey INFI 90 DCS installations. It provides screw terminal connection points for incoming field instrumentation signals and routes them to active analog input processing modules.
Which control systems use the NTAI05?
The NTAI05 is compatible with ABB Bailey INFI 90 and Network 90 Distributed Control Systems.
Does the NTAI05 require external power?
The NTAI05 is primarily a passive termination board that routes signals. Power requirements for field transmitters (such as 24 VDC loop power) are typically supplied through the paired input module or a dedicated system power supply, rather than powered directly by the termination unit itself.
Can active INFI 90 modules be replaced without disconnecting wiring on the NTAI05?
Yes. Field wiring attaches permanently to the NTAI05 terminal blocks. The active input module can be unseated or replaced from the main module rack via its interconnect cable without disturbing the field wiring terminations on the NTAI05.
Verification & Troubleshooting Notes
- Field Signal Checks: Measure voltage across the terminal block points using a calibrated multimeter to confirm signal presence (e.g., 1–5 VDC across a precision shunt resistor or 4–20 mA loop current).
- Cable Connection Verification: Ensure the interconnecting ribbon cable between the NTAI05 header and the module rack is securely seated and locked. Corroded or loose cable connectors can cause intermittent channel readings or signal loss.
- Terminal Tightness: Inspect screw terminals periodically during routine preventive maintenance to ensure connections remain tight and free of oxidation.
- Grounding Inspection: Verify that shield drain wires are grounded at the designated system earth point to reduce high-frequency electrical noise on analog input channels.