Sale!

ABB PM511V16 3BSE011181R1 Processor Module

Parameter Specification
Manufacturer ABB
Model PM511V16
Order number 3BSE011181R1
Product type Processor module
Controller platform Advant Controller 450
Memory capacity 16 MB dynamic RAM
Memory protection Error correction code, ECC
Processor Motorola 68040
Processor clock 25 MHz
Categories: , , , , SKU: PM511V16 3BSE011181R1 Brand:

Description

Core Product Summary

ABB PM511V16 3BSE011181R1 is a processor module for Advant Controller 450 in the Advant OCS with Master software environment. The PM511V16 is the 16 MB memory version of the PM511V processor platform, providing memory for system software, controller configuration, and the application program. Its processing architecture uses a 25 MHz Motorola 68040 CPU and dynamic RAM with error correction.

The module fits RF533-series controller subracks and includes a Futurebus+ interface, an S100 I/O extension-bus interface, and a PCMCIA slot for system-software flash memory cards. PM511V hardware also supports a two-processor redundant arrangement. These system interfaces and installation requirements distinguish it from a standalone PLC CPU or a general-purpose industrial computer board.

 

Key Technical Specifications

Parameter Specification
Manufacturer ABB
Model PM511V16
Order number 3BSE011181R1
Product type Processor module
Controller platform Advant Controller 450
Memory capacity 16 MB dynamic RAM
Memory protection Error correction code, ECC
Processor Motorola 68040
Processor clock 25 MHz
Processor architecture 32-bit, with integrated floating-point unit
Processor caches Separate 4 kbyte instruction and data caches
System-bus interface Futurebus+, with 32-bit address/data lines
I/O interface S100 I/O extension bus
System-software media Flash memory card through a PCMCIA slot
Controller subrack RF533 series
Redundancy support Hardware support for two redundant PM511V processors
Front-panel facilities Status LEDs, start-mode selector, ENTER push button, service-tool connector

The model and order number identify the 16 MB version; the processor, interface, and installation characteristics apply to the PM511V platform covering PM511V16.

 

Engineering Selection Highlights

  • 16 MB dynamic RAM → identifies the PM511V16 memory configuration; preserve the complete model suffix when matching an existing controller specification.
  • RF533-series subrack installation → establishes the required controller hardware context rather than DIN-rail or standalone mounting.
  • S100 I/O extension-bus interface → supports connection to DSBC 174 or DSBC 176 bus extension boards in an S100 I/O rack.
  • PCMCIA slot for system-software flash cards → makes the installed software card a separate integration consideration from the processor hardware.
  • Two-processor redundancy support → permits a redundant PM511V arrangement when implemented as part of the controller configuration; a single module does not constitute a redundant system.
  • Front-panel status indicators → expose module error, running, halted, bus timeout, RAM backup-voltage, and redundant-processor readiness states for controller diagnostics.
PM511V16 3BSE011181R1

PM511V16 3BSE011181R1

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Controller platform Advant Controller 450 Match the processor to the AC 450 system architecture.
Controller subrack RF533 series The processor installs in the controller subrack, not as a standalone panel-mounted unit.
System bus Futurebus+ Provides the processor’s connection to the controller backplane.
S100 I/O connection Interface to DSBC 174 or DSBC 176 in an S100 I/O rack The bus extension board forms part of the I/O connection path.
System-software storage PCMCIA flash memory card The card carries system software; processor identification alone does not specify its contents.
Redundant operation Two PM511V processors in a redundant configuration Requires the paired processor arrangement and appropriate system configuration.

The RF533, S100, and software-card relationships are documented for the PM511V platform; the two-processor arrangement is a controller configuration rather than an inherent property of one installed module.

 

Dimensions, Mounting & Connection Notes

The PM511V16 installs in an RF533-series controller subrack. The subrack uses Futurebus+ as its system bus, making the chassis and backplane part of the processor’s installation environment.

The front panel provides a service-tool connector and an I/O connection interface. The S100 I/O extension-bus interface connects to a DSBC 174 or DSBC 176 bus extension board located in an S100 I/O rack. The PCMCIA slot accepts flash memory cards for system software.

 

Detailed Product Overview

The PM511V16 combines the processor and runtime memory of an Advant Controller 450 on a subrack-mounted module. Its 16 MB capacity distinguishes this version within the PM511V platform. The memory holds more than an application file: it also accommodates the active system software and controller configuration. For selection purposes, memory configuration is therefore part of the controller specification, not merely a general product attribute.

Processing is based on a 25 MHz Motorola 68040. The CPU incorporates a floating-point unit and separate instruction and data caches. These describe the processor architecture, but they should not be treated as a guaranteed controller scan time or application execution rate. The module’s identity and architecture do not establish the timing of a particular control application.

Integration depends on the surrounding AC 450 hardware. The RF533 subrack provides the Futurebus+ system-bus environment, while the processor’s S100 I/O extension-bus interface provides a connection path to DSBC 174 or DSBC 176 boards in an I/O rack. Identifying the CPU alone consequently does not describe the complete controller or I/O installation.

System software introduces another dependency. The PCMCIA slot accepts a flash memory card carrying system software, and the AC 450 software arrangement places the basic program module and selected software options on a program card at the processor. The hardware order number should therefore remain distinct from the software configuration in engineering records.

For redundant systems, PM511V hardware includes logic that copies primary-processor memory writes to the backup processor. This keeps the backup memory updated as part of the paired arrangement. The capability belongs to the configured two-processor system; it is not evidence that an individual spare module provides redundancy by itself.

Front-panel indicators complement these architectural features by showing operating and diagnostic states. In particular, RUN, HLT, TO, BC, and DUAL distinguish normal operation, a halted CPU, bus timeout, connected RAM backup voltage, and redundant-processor readiness. These indications help describe the controller’s state without implying that any single LED proves the health of the complete automation system.

 

Applications & System Role

The PM511V16 performs the central processing role in an Advant Controller 450. Its RAM holds the system program in use, controller configuration, and application program—the software and data required during runtime. It therefore serves a different architectural role from an I/O module, communication interface, or subrack power component.

Relevant technical-fit scenarios include an AC 450 configuration specifying the 16 MB processor version, an RF533-based controller connected to S100 I/O, or a controller designed around paired PM511V processors for redundant operation. These are system-architecture scenarios, not claims about particular customer installations.

 

FAQ

 

What is ABB PM511V16 3BSE011181R1?

ABB PM511V16 3BSE011181R1 is a 16 MB processor module for Advant Controller 450. It belongs to the Advant OCS with Master software controller environment.

 

How much memory does the PM511V16 provide?

The PM511V16 provides 16 MB of dynamic RAM. The PM511V platform uses this memory for the active system software, controller configuration, and application program.

 

Which processor does it use?

It uses a 25 MHz Motorola 68040 processor. The processor has an integrated floating-point unit and separate 4 kbyte instruction and data caches.

 

Which subrack does the module require?

The PM511V16 fits RF533-series controller subracks. The RF533 uses Futurebus+ as the controller system bus.

 

How does it connect to S100 I/O?

The processor has an S100 I/O extension-bus interface that connects to a DSBC 174 or DSBC 176 bus extension board in an S100 I/O rack.

 

Does the PM511V16 support redundant processors?

Yes. The PM511V platform supports two processors in a redundant arrangement, with hardware that copies primary-processor memory writes to the backup processor. Redundancy requires the complete paired configuration.

 

What is the PCMCIA slot used for?

The PCMCIA slot accepts flash memory cards for system software. The software card is a separate part of the controller’s hardware-and-software configuration.

 

What does the DUAL indicator mean?

The green DUAL indicator means the redundant processor is ready. Other front-panel indicators report module error, normal running, CPU halt, bus timeout, and connected RAM backup voltage.