Description
Core Product Summary
The Allen-Bradley 1756-OB16E is a ControlLogix digital DC output module that provides 16 electronically fused sourcing outputs rated for 10…31.2 V DC. It mounts in any standard 1756 ControlLogix chassis and is designed for switching 12/24 V DC field loads such as solenoids, indicators, and pilot devices.
Outputs are organized into two groups of eight points, each with electronic fusing. The module supports a maximum of 1 A per point and 8 A per module at 60 °C, with programmable fault and program mode states. Field wiring connects through a separately ordered 20-pin removable terminal block (1756-TBNH or 1756-TBSH).
Key Technical Specifications
| Parameter | Value |
|---|---|
| Catalog Number | 1756-OB16E |
| Module Type | Digital DC Output, Electronically Fused |
| Number of Outputs | 16 (8 points per group) |
| Voltage Category | 12/24 V DC source |
| Operating Voltage Range | 10…31.2 V DC |
| Current per Point, max | 1 A @ 60 °C |
| Current per Module, max | 8 A @ 60 °C |
| Surge Current per Point | 2 A for 10 ms (repeatable every 2 s @ 0 °C, 24 V DC) |
| Output Delay (Off to On) | 70 µs nominal / 1 ms max |
| Output Delay (On to Off) | 360 µs nominal / 1 ms max |
| On-State Voltage Drop, max | 400 mV DC @ 1 A |
| Off-State Leakage Current, max | 1 mA per point |
| Minimum Load Current | 3 mA per point |
| Backplane Current | 250 mA @ 5.1 V, 2 mA @ 24 V |
| Total Backplane Power | 1.32 W |
| Power Dissipation, max | 4.1 W @ 60 °C |
| Thermal Dissipation | 13.98 BTU/hr |
| Isolation Voltage | 250 V continuous (outputs-to-backplane and group-to-group) |
| Removable Terminal Block | 1756-TBNH or 1756-TBSH |
| Slot Width | 1 |
| Operating Temperature | 0…60 °C |
| Enclosure Type | Open-style (none) |
Detailed Product Overview
The 1756-OB16E belongs to the ControlLogix I/O family and functions as a discrete sourcing output interface between a Logix controller and 12/24 V DC field devices. Electronic fusing is applied on a per-group basis, allowing the module to interrupt overcurrent conditions without external fuses. Fuse status and individual point status are reported to the controller for diagnostic visibility.
The module supports configurable output behavior in both Program mode and Fault mode (Hold Last State, On, or Off; Off is the default). Scheduled output synchronization relative to Coordinated System Time is available. Isolation is provided between the two output groups and between the groups and the backplane; individual points within a group share a common return.
Field power is supplied externally to the DC+ terminals of each group. The module draws only backplane power for its internal logic and does not supply field voltage. Status indicators on the module face show overall module health and per-point status, including fuse-trip indication.
This design is intended for applications that require protected 24 V DC discrete outputs in a ControlLogix architecture while minimizing external fuse hardware and simplifying fault recovery through electronic reset capability.

1756-OB16E
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Chassis | Any standard 1756 ControlLogix chassis | Single-slot width |
| Controller | ControlLogix or compatible Logix platform | Local or remote I/O via ControlNet/EtherNet/IP |
| Terminal Block | 1756-TBNH (screw) or 1756-TBSH (spring) | 20-pin RTB ordered separately |
| Field Power | External 10…31.2 V DC supply | Separate supply per output group |
| Keying | Electronic (software configurable) + mechanical RTB keying | User-defined mechanical keying on RTB |
| Software | Studio 5000 Logix Designer / RSLogix 5000 | Required for configuration and fuse reset |
Dimensions, Mounting & Connection Notes
The module occupies one slot in a 1756 ControlLogix chassis. Field connections are made exclusively through a 20-pin removable terminal block (1756-TBNH or 1756-TBSH). Wiring follows standard ControlLogix practices: each group has dedicated DC+ supply terminals and a common return. Daisy-chaining of field power between terminal blocks is supported when connecting the supply wire to the terminal directly tied to the supply source. Open-style construction requires installation inside a suitable enclosure.
FAQ
What is the Allen-Bradley 1756-OB16E?
It is a 16-point electronically fused DC sourcing output module for the ControlLogix platform, rated 10…31.2 V DC.
How many outputs does the 1756-OB16E provide and how are they grouped?
It provides 16 outputs arranged in two groups of eight points, with electronic fusing applied per group.
What is the maximum current rating?
1 A per point and 8 A per module at 60 °C.
Which terminal blocks are required?
A 20-pin removable terminal block is required: 1756-TBNH (screw-clamp) or 1756-TBSH (spring-clamp).
Can the electronic fuses be reset?
Yes. Fuse status is reported to the controller, and fuses can be reset through the programming software or by cycling power after the fault is cleared.
What is the operating temperature range?
0…60 °C (surrounding air temperature maximum 60 °C).
Does the module supply field power?
No. An external 10…31.2 V DC supply must be connected to the DC+ terminals of each output group.