Description
Core Product Summary
The Allen-Bradley 1794-IT8 is an 8-channel FLEX I/O thermocouple and millivolt input module. It converts thermocouple or millivolt signals into data for an Allen-Bradley programmable controller through a FLEX I/O communication adapter.
The module provides eight differential-ended inputs and accepts thermocouple signals as well as millivolt inputs within a range of -76.5 to 76.5 mV. It operates from a 24 V DC supply, mounts on a compatible FLEX I/O terminal base, and includes two cold-junction compensators for thermocouple-mode operation. Its 16-bit input resolution and support for grounded or ungrounded thermocouples make it suitable for distributed temperature-measurement points in a FLEX I/O system.
Key Technical Specifications
| Item | Specification |
|---|---|
| Brand | Allen-Bradley, Rockwell Automation |
| Catalog number | 1794-IT8 |
| Product family | FLEX I/O |
| Product type | Thermocouple / millivolt input module |
| Number of inputs | 8 differential-ended channels |
| Input types | Thermocouple and millivolt |
| Millivolt input range | -76.5 to 76.5 mV |
| Input resolution | 16 bits; 2.384 µV typical |
| Supply voltage | 24 V DC nominal; 19.2–31.2 V DC, including 5% AC ripple |
| Supply current | 95 mA at 24 V DC |
| FLEXBUS current | 15 mA at 5 V DC |
| Operating temperature | 0–55 °C (32–131 °F) |
| Isolation voltage | 850 V |
| Terminal bases | 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS |
| Cold-junction compensators | Two 1794-CJC2 compensators included; additional units available as 1794-CJC2 |
| Communication function | Block-transfer module for Allen-Bradley programmable controllers with block-transfer capability |
| Programming / configuration | FLEX I/O module configuration and calibration through the applicable controller software |
| Reference documentation | 1794-IN021 installation instructions; 1794-UM007 user manual |
Engineering Selection Highlights
- The 1794-IT8 provides eight differential-ended thermocouple or millivolt input channels. Use it where multiple temperature or low-level millivolt signals must be brought into a FLEX I/O system through one module.
- Its millivolt range is -76.5 to 76.5 mV. Signals outside this range require signal conditioning or a different input-module type.
- It supports grounded and ungrounded thermocouples. Grounded-thermocouple installations must follow the guidelines in the module user manual because grounding arrangements affect measurement behavior.
- Cold-junction compensation is required in thermocouple mode. Two 1794-CJC2 compensators are supplied with the module; additional compensators must be ordered as 1794-CJC2.
- The module requires a compatible FLEX I/O terminal base. It mounts on 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS terminal bases, and shield-termination location varies by terminal-base type.
- The module draws 95 mA at 24 V DC and 15 mA from the FLEXBUS. Power-supply and adapter capacity must include both the module supply load and FLEXBUS load.
- Open-input detection behavior depends on module series and revision. Series A revision D or earlier detects an open input within 0–3.8 seconds; Series A revision E or later and Series B detect it immediately, within a maximum of two scans.

1794-IT8
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| I/O system | Allen-Bradley FLEX I/O | The 1794-IT8 is a FLEX I/O module. |
| Controller interface | Allen-Bradley programmable controller with block-transfer capability | The module is a block-transfer module and interfaces analog signals through this capability. |
| Terminal base | 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS | The terminal base must be compatible with the module and the selected wiring arrangement. |
| Thermocouple mode | Cold-junction compensation required | Use the supplied 1794-CJC2 compensators or order additional 1794-CJC2 units. |
| Shield termination | Dedicated shield pins on 1794-TB2, 1794-TB3, or 1794-TB3T | The shield-termination location depends on the terminal base used. |
| Power supply | 19.2–31.2 V DC | The supply range includes 5% AC ripple and must support the module’s 95 mA current draw. |
| FLEXBUS power | 5 V DC, 15 mA | Include this load when calculating adapter and FLEXBUS capacity. |
| Configuration | FLEX I/O module configuration and calibration | The applicable controller software provides module configuration and calibration functions. |
Dimensions, Mounting & Connection Notes
| Item | Verified information |
|---|---|
| Mounting method | Installs onto a compatible FLEX I/O terminal base |
| Compatible terminal bases | 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS |
| Input channels | Eight differential-ended channels |
| Thermocouple wiring | Supports grounded and ungrounded thermocouples, subject to the user-manual guidelines |
| Cold-junction compensation | Connect CJC wiring for thermocouple operation; on 1794-TB3T or 1794-TB3TS, CJC wiring for inputs 0–3 uses terminals 36, 37, and 38 |
| Shield termination | Dedicated shield pins are available on 1794-TB2, 1794-TB3, and 1794-TB3T terminal bases |
| Power restriction | Do not wire AC power directly to the module |
| Terminal-base current limit | Total current through the terminal base is limited to 10 A; separate power connections may be necessary |
Detailed Product Overview
The Allen-Bradley 1794-IT8 is a FLEX I/O thermocouple and millivolt input module with eight differential-ended input channels. It is designed to interface low-level analog temperature signals with an Allen-Bradley programmable controller through the FLEX I/O architecture.
The module accepts thermocouple signals and millivolt signals in the range of -76.5 to 76.5 mV. Its 16-bit resolution, specified as 2.384 µV typical, defines the measurement granularity available from the input circuitry. This makes the module suitable for temperature measurement applications where thermocouple signals are already available at the I/O location and do not require external signal conversion.
Thermocouple measurement requires cold-junction compensation. The 1794-IT8 includes two 1794-CJC2 cold-junction compensators, and additional compensators can be ordered under the same catalog number. In thermocouple mode, the compensation wiring must be connected according to the installation instructions. On a 1794-TB3T or 1794-TB3TS terminal base, the CJC wiring for inputs 0 through 3 is connected to terminals 36, 37, and 38.
The module mounts on one of several compatible FLEX I/O terminal bases: 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS. The terminal base is not merely a mechanical carrier; it determines part of the wiring and shield-termination arrangement. The 1794-IT8 has dedicated shield-termination pins on the 1794-TB2, 1794-TB3, and 1794-TB3T terminal bases, while the exact shield-termination location varies with the base selected.
Electrically, the module requires a 24 V DC nominal supply within 19.2–31.2 V DC, including 5% AC ripple. It draws 95 mA at 24 V DC and 15 mA from the 5 V DC FLEXBUS. These loads must be included when sizing the FLEX I/O power supply and calculating the total FLEXBUS demand across the installed modules.
The module is a block-transfer module. It interfaces analog signals with any Allen-Bradley programmable controller that has block-transfer capability. Configuration and calibration are performed through the applicable controller software, and the module’s read and write data words define the channel data, status, and configuration interface used by the controller.
Open-input detection is revision-dependent. For Series A revision D or earlier, detection occurs within 0–3.8 seconds. For Series A revision E or later, and for Series B modules, detection is immediate and occurs within a maximum of two scans. This distinction can matter in applications where rapid detection of a disconnected thermocouple is part of the control or alarming strategy.
Applications & System Role
The Allen-Bradley 1794-IT8 sits in the analog-input layer of a FLEX I/O system. Its role is to acquire low-level thermocouple or millivolt signals from field temperature sensors and make the resulting data available to the connected programmable controller.
It is appropriate where multiple temperature-measurement points are distributed across a FLEX I/O installation and the signals are compatible with thermocouple or millivolt input ranges. The module supports grounded and ungrounded thermocouples, but grounded-thermocouple use requires adherence to the wiring guidelines in the module user manual.
The module is not an RTD input module. For resistance-temperature-detector signals, the related 1794-IR8 FLEX I/O RTD input module is the corresponding eight-channel RTD product. The 1794-IT8 is selected when the field signals are thermocouple or millivolt signals within its specified input range.
FAQ
What is the Allen-Bradley 1794-IT8?
It is an 8-channel FLEX I/O thermocouple and millivolt input module used to interface thermocouple or low-level millivolt signals with an Allen-Bradley programmable controller.
How many input channels does it provide?
It provides eight differential-ended input channels.
What input signals does it accept?
It accepts thermocouple signals and millivolt signals in the range of -76.5 to 76.5 mV.
What is its input resolution?
Its input resolution is 16 bits, with a typical resolution of 2.384 µV.
Does it require cold-junction compensation?
Yes. Cold-junction compensation is required in thermocouple mode. Two 1794-CJC2 compensators are included with the module.
Which terminal bases can it use?
It mounts on 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS terminal bases.
What supply voltage does it require?
It requires a 24 V DC nominal supply within 19.2–31.2 V DC, including 5% AC ripple.
Can it measure RTD signals?
No. The 1794-IT8 is a thermocouple and millivolt input module; the corresponding FLEX I/O RTD input module is the 1794-IR8.