Description
. Key Technical Specifications
- Number of circuits: 14 independent circuits (paired rear terminals)
- Current rating: 20 A continuous / 400 A for 1 s (MMLG01 / MMLB01 combination)
- Voltage rating: 300 V AC or DC continuous
- Contact design: Spring-loaded normally closed contacts; open on insertion of MMLB01 multi-finger test plug
- Safety feature: Automatic shorting of CT secondaries (make-before-break) before isolation
- Special terminals: Terminals 13 and 14 – short contact fingers; not for CT connections; used for trip-circuit isolation via cover probe
- Mounting: Flush panel / modular case, mounts adjacent to Midos relays
- Compatible test plugs: MMLB01 (multi-finger), MMLB02 (single-finger)
- Operating temperature: Typically –25 °C to +55 °C
- Insulation: 1 kV rms for 1 minute between finger contacts (typical)
- Note: Exact dimensional drawings, weight, and full type-test data should be confirmed from the GE/Alstom technical publication before installation.
4. Product Introduction
The Alstom MMLG01 is a standard test block from the Midos range, designed for safe monitoring, isolation, and secondary injection testing of power-system protection schemes. It mounts adjacent to modular relays and carries 14 circuits that remain closed under normal service.
When the matching MMLB01 multi-finger test plug is inserted, the internal contacts open cleanly, allowing injection and measurement without disturbing permanent wiring. The design incorporates make-before-break shorting for current-transformer circuits, preventing open-circuit CT hazards during testing.

MMLG01

MMLG01
5. Troubleshooting Quick Reference
| Symptom | Possible Cause | Relevance to this Part | Quick Check Method | Recommendation |
|---|---|---|---|---|
| Relay trips when test-block cover is removed | Trip circuit not routed through terminals 13–14 | ✅ High | Verify DC auxiliary / trip supply is wired through terminals 13 and 14 | Correct wiring so cover removal isolates the trip circuit |
| CT circuit remains open or high voltage appears | Failed make-before-break shorting contacts | ✅ High | Measure continuity across CT terminals before and during plug insertion | Replace the test block; never operate with open CT secondaries |
| No continuity through a circuit with plug removed | Contaminated or worn spring contacts | ✅ Medium | Check resistance of each closed contact pair with a low-ohm meter | Clean or replace the block if resistance is elevated |
| Test plug will not insert fully | Misaligned fingers or damaged guide | ✅ Medium | Inspect plug and block for bent contacts or debris | Use only genuine MMLB01 plug; do not force insertion |
| Intermittent readings during secondary injection | Poor contact pressure or oxidized sockets | ✅ Medium | Wiggle test leads and re-measure; check 4 mm socket condition | Clean sockets and verify plug finger integrity |
| Cover will not seat or probe fails to engage | Incorrect cover orientation or broken probe | ✅ High | Confirm cover orientation marks and probe length | Fit correct cover; never leave cover off in service |
If diagnostics remain unclear, photograph the block, wiring, and any labels, then contact technical support with the full model string.
6. Frequently Asked Questions (FAQ)
Q: What is the primary purpose of the Alstom MMLG01?
A: It provides a safe interface for isolating a protection relay or scheme and performing secondary injection tests without disconnecting permanent wiring. It is not a protection relay itself.
Q: Which test plug do I need?
A: Use the MMLB01 multi-finger test plug for simultaneous access to all circuits. The MMLB02 single-finger plug is available for monitoring individual circuits.
Q: Can terminals 13 and 14 be used for CT connections?
A: No. These terminals have short contact fingers and are intended for the auxiliary DC / trip-circuit isolation function. Using them for CTs creates a safety hazard.
Q: Is the MMLG01 still supported?
A: The original Alstom version is discontinued by the manufacturer, but New Surplus and equivalent GE-branded units (often with updated livery) remain available for maintenance of existing installations.
Q: Does the block short CT secondaries automatically?
A: Yes. The design provides make-before-break shorting so that CT circuits are shorted before they are isolated from the relay when the test plug is inserted.
Q: Can I leave the cover off after testing?
A: No. The cover must be correctly replaced and oriented. It provides both electrical isolation of the trip circuit (via the internal probe) and protection against accidental contact.
Q: What condition and warranty apply to units you supply?
A: We supply New Original / New Surplus stock. Each unit is inspected for contact integrity and mechanical condition. Standard coverage is a 1-year warranty against defects. Provide the full model MMLG01 (and any suffix if present) when ordering or requesting support.