Description
Core Product Summary
The Bachmann RS204 is a serial interface module that connects four asynchronous serial interfaces to a Bachmann M200 controller. It expands the controller’s serial communication capacity for field devices, drives, instruments, and other equipment that use RS232, RS422, or RS485 connections.
Each of the four ports can be configured as RS232, RS422, or RS485, and the port types can be combined on one module. The RS204 supports transfer rates up to 1.5 MBaud on RS422 and RS485, includes automatic flow control, provides switchable terminating resistors, and isolates each interface galvanically from the system and from the other interfaces.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Bachmann electronic GmbH |
| Model | RS204 |
| Order number | 00021235-00 |
| Product type | Serial interface module |
| Controller system | Bachmann M200 control system |
| Serial ports | 4 asynchronous interfaces |
| Port types | RS232, RS422, RS485; configurable per port |
| Maximum transfer rate, RS232 | 115.2 kBaud |
| Maximum transfer rate, RS422 | 1.5 MBaud |
| Maximum transfer rate, RS485 | 1.5 MBaud |
| RS232 operating mode | Full duplex |
| RS422/RS485 operating mode | Half duplex |
| FIFO buffer | 128 bytes |
| Flow control | Auto-flow control for automatic handshake |
| Terminating resistors | Integrated; connectable/disconnectable via DIP switch on RS422/RS485 |
| External supply voltage | 18 VDC to 34 VDC |
| Current consumption | 120 mA at 24 VDC |
| Galvanic isolation | 500 V from system and between interfaces |
| Operating temperature | -30 °C to +60 °C |
| Operating humidity | 5% to 95%, non-condensing |
| Storage temperature | -40 °C to +85 °C |
| Storage humidity | 5% to 95%, with condensation |
| Pollution degree | IEC 60664-1 Pollution Degree 2, non-condensing |
| Connector | 9-pin D-sub connectors |
| General approvals | CE, UKCA, cULus |
| Marine approvals | ABS, BV, DNV, KR, LR, NK, RINA |
Engineering Selection Highlights
- The RS204 provides four independently configurable serial ports, so it suits applications requiring several RS232, RS422, or RS485 devices at one M200 controller.
- RS422 and RS485 ports support up to 1.5 MBaud, while RS232 is limited to 115.2 kBaud; port type therefore determines the usable communication speed.
- The module’s 128-byte FIFO buffer and auto-flow control support asynchronous serial communication with handshake-capable devices.
- Integrated, DIP-switch-selectable terminating resistors simplify RS422 and RS485 bus termination without adding external components.
- Each interface is galvanically isolated at 500 V from the controller system and from the other interfaces, supporting separation between serial field segments.
- The module requires an external 18–34 VDC supply and draws 120 mA at 24 VDC, which must be included in the cabinet power budget.
- The RS204 uses 9-pin D-sub connectors and mounts on the M200 backplane, making connector and backplane availability relevant to installation planning.

RS204

RS204
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Controller system | Bachmann M200 controller | The RS204 connects four asynchronous serial interfaces to the M200 controller. |
| Mounting location | M200 backplane | The module is installed on the controller backplane to add serial ports. |
| Serial interfaces | , , | Port types can be combined across the four ports. |
| Connectors | 9-pin D-sub connectors | Field cabling must match the selected serial standard and connector assignment. |
| External power | 18 VDC to 34 VDC | The module requires an external supply; specified consumption is 120 mA at 24 VDC. |
| RS422/RS485 termination | Integrated terminating resistor, DIP-switch controlled | Enable termination as required by the connected bus topology. |
| Configuration | Transfer rate set through software | Supported rates range from 300 bit/s to 1.5 Mbit/s, depending on interface type. |
| Fastbus SubDevices | Interface extensions can be used on Fastbus SubDevices | This extends serial-interface availability beyond the central M200 CPU location. |
Dimensions, Mounting & Connection Notes
| Item | Verified data |
|---|---|
| Mounting method | M200 backplane |
| Field connectors | Four 9-pin D-sub connectors |
| External power connection | 18–34 VDC supply |
| Termination | Integrated RS422/RS485 terminating resistors, set by DIP switch |
| Operating temperature | -30 °C to +60 °C |
| Operating humidity | 5% to 95%, non-condensing |
| Applicable accessory | KZ 51/02 B terminal, 2-pin, 5.08 mm pitch, cage-clamp type with labeling strips |
The RS204 is installed on the M200 backplane rather than as a standalone DIN-rail device. Its four 9-pin D-sub connectors provide the physical field connections, while the external 24 VDC-class supply powers the module.
Detailed Product Overview
The Bachmann RS204 is a four-channel asynchronous serial interface module for the M200 controller system. Its primary role is to increase the number of serial communication ports available to an M200-based control application, using four 9-pin D-sub connectors on a single backplane-mounted module.
Each port can be independently configured for RS232, RS422, or RS485, and these standards may be mixed on the same module. This allows one RS204 to serve, for example, an RS232 device alongside RS485 fieldbus devices without requiring separate interface hardware for every signal standard. The RS232 interface operates in full duplex at up to 115.2 kBaud, while RS422 and RS485 operate in half duplex at up to 1.5 MBaud.
The module provides a 128-byte FIFO buffer and auto-flow control for automatic handshake. These functions are relevant when connecting serial equipment whose timing or handshake behavior requires buffered transmission and controlled data flow. Software-selectable transfer rates range from 300 bit/s to 1.5 Mbit/s, with the available maximum dependent on the selected interface type.
For RS422 and RS485 connections, the RS204 includes integrated terminating resistors that can be connected or disconnected through DIP switches. This supports proper bus termination at the module end of a serial segment. All four interfaces are galvanically isolated at 500 V, both from the controller system and from one another, which helps separate serial field circuits from the controller backplane and from each other.
The module requires an external supply of 18–34 VDC and consumes 120 mA at 24 VDC. It is rated for operation from -30 °C to +60 °C and for 5–95% non-condensing relative humidity. The standard RS204 carries CE, UKCA, and cULus approvals, and the documented marine approval scope includes ABS, BV, DNV, KR, LR, NK, and RINA.
Bachmann also documents an RS204 CC variant, order number 00021674-00, described as a Cold Climate version with the same four-port RS232/RS422/RS485 configuration. The standard RS204 order number is 00021235-00. The documented accessory KZ 51/02 B is a two-pin, 5.08 mm-pitch cage-clamp terminal with labeling strips.
Applications & System Role
The RS204 sits in the communication layer of a Bachmann M200 automation system. It adds serial ports to the controller, allowing the M200 system to communicate with devices that do not use Ethernet or the controller’s built-in serial interfaces.
Typical integration points are serial field equipment, remote devices, instruments, and subsystems using RS232, RS422, or RS485. Because the module supports multiple interface standards on one module and can be used in Fastbus SubDevices, it is applicable where serial devices are distributed across a Bachmann automation architecture rather than concentrated at the main controller.
FAQ
What is the Bachmann RS204?
It is a Bachmann serial interface module that adds four asynchronous serial ports to an M200 controller system.
Which serial standards does the RS204 support?
It supports RS232, RS422, and RS485. The four ports can use different standards and can be combined on one module.
What is the maximum communication speed?
RS422 and RS485 support up to 1.5 MBaud. RS232 supports up to 115.2 kBaud.
How is the RS204 connected to the controller?
It is mounted on the M200 backplane and provides four 9-pin D-sub serial connectors for field connections.
Does the RS204 provide bus termination?
Yes. It includes integrated terminating resistors for RS422 and RS485, which are connected or disconnected using DIP switches.
What power supply does the RS204 require?
It requires an external supply of 18–34 VDC and consumes 120 mA at 24 VDC.
Are the serial ports isolated?
Yes. Each interface is galvanically isolated at 500 V from the controller system and from the other interfaces.
Is there a cold-climate version?
Yes. The RS204 CC, order number 00021674-00, is the documented Cold Climate variant of the four-port RS204.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626