Sale!

Bachmann RS204 4-Port Serial Interface Module

The Bachmann RS204 is a serial interface module that connects four asynchronous serial interfaces to a Bachmann M200 controller. It expands the controller’s serial communication capacity for field devices, drives, instruments, and other equipment that use RS232, RS422, or RS485 connections.

Categories: , , , , SKU: RS204 Brand:

Description

Core Product Summary

The Bachmann RS204 is a serial interface module that connects four asynchronous serial interfaces to a Bachmann M200 controller. It expands the controller’s serial communication capacity for field devices, drives, instruments, and other equipment that use RS232, RS422, or RS485 connections.

Each of the four ports can be configured as RS232, RS422, or RS485, and the port types can be combined on one module. The RS204 supports transfer rates up to 1.5 MBaud on RS422 and RS485, includes automatic flow control, provides switchable terminating resistors, and isolates each interface galvanically from the system and from the other interfaces.

 

Key Technical Specifications

Parameter Specification
Manufacturer Bachmann electronic GmbH
Model RS204
Order number 00021235-00
Product type Serial interface module
Controller system Bachmann M200 control system
Serial ports 4 asynchronous interfaces
Port types RS232, RS422, RS485; configurable per port
Maximum transfer rate, RS232 115.2 kBaud
Maximum transfer rate, RS422 1.5 MBaud
Maximum transfer rate, RS485 1.5 MBaud
RS232 operating mode Full duplex
RS422/RS485 operating mode Half duplex
FIFO buffer 128 bytes
Flow control Auto-flow control for automatic handshake
Terminating resistors Integrated; connectable/disconnectable via DIP switch on RS422/RS485
External supply voltage 18 VDC to 34 VDC
Current consumption 120 mA at 24 VDC
Galvanic isolation 500 V from system and between interfaces
Operating temperature -30 °C to +60 °C
Operating humidity 5% to 95%, non-condensing
Storage temperature -40 °C to +85 °C
Storage humidity 5% to 95%, with condensation
Pollution degree IEC 60664-1 Pollution Degree 2, non-condensing
Connector 9-pin D-sub connectors
General approvals CE, UKCA, cULus
Marine approvals ABS, BV, DNV, KR, LR, NK, RINA

 

Engineering Selection Highlights

  • The RS204 provides four independently configurable serial ports, so it suits applications requiring several RS232, RS422, or RS485 devices at one M200 controller.
  • RS422 and RS485 ports support up to 1.5 MBaud, while RS232 is limited to 115.2 kBaud; port type therefore determines the usable communication speed.
  • The module’s 128-byte FIFO buffer and auto-flow control support asynchronous serial communication with handshake-capable devices.
  • Integrated, DIP-switch-selectable terminating resistors simplify RS422 and RS485 bus termination without adding external components.
  • Each interface is galvanically isolated at 500 V from the controller system and from the other interfaces, supporting separation between serial field segments.
  • The module requires an external 18–34 VDC supply and draws 120 mA at 24 VDC, which must be included in the cabinet power budget.
  • The RS204 uses 9-pin D-sub connectors and mounts on the M200 backplane, making connector and backplane availability relevant to installation planning.
RS204

RS204

RS204

RS204

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Controller system Bachmann M200 controller The RS204 connects four asynchronous serial interfaces to the M200 controller.
Mounting location M200 backplane The module is installed on the controller backplane to add serial ports.
Serial interfaces , , Port types can be combined across the four ports.
Connectors 9-pin D-sub connectors Field cabling must match the selected serial standard and connector assignment.
External power 18 VDC to 34 VDC The module requires an external supply; specified consumption is 120 mA at 24 VDC.
RS422/RS485 termination Integrated terminating resistor, DIP-switch controlled Enable termination as required by the connected bus topology.
Configuration Transfer rate set through software Supported rates range from 300 bit/s to 1.5 Mbit/s, depending on interface type.
Fastbus SubDevices Interface extensions can be used on Fastbus SubDevices This extends serial-interface availability beyond the central M200 CPU location.

 

Dimensions, Mounting & Connection Notes

Item Verified data
Mounting method M200 backplane
Field connectors Four 9-pin D-sub connectors
External power connection 18–34 VDC supply
Termination Integrated RS422/RS485 terminating resistors, set by DIP switch
Operating temperature -30 °C to +60 °C
Operating humidity 5% to 95%, non-condensing
Applicable accessory KZ 51/02 B terminal, 2-pin, 5.08 mm pitch, cage-clamp type with labeling strips

The RS204 is installed on the M200 backplane rather than as a standalone DIN-rail device. Its four 9-pin D-sub connectors provide the physical field connections, while the external 24 VDC-class supply powers the module.

 

Detailed Product Overview

The Bachmann RS204 is a four-channel asynchronous serial interface module for the M200 controller system. Its primary role is to increase the number of serial communication ports available to an M200-based control application, using four 9-pin D-sub connectors on a single backplane-mounted module.

Each port can be independently configured for RS232, RS422, or RS485, and these standards may be mixed on the same module. This allows one RS204 to serve, for example, an RS232 device alongside RS485 fieldbus devices without requiring separate interface hardware for every signal standard. The RS232 interface operates in full duplex at up to 115.2 kBaud, while RS422 and RS485 operate in half duplex at up to 1.5 MBaud.

The module provides a 128-byte FIFO buffer and auto-flow control for automatic handshake. These functions are relevant when connecting serial equipment whose timing or handshake behavior requires buffered transmission and controlled data flow. Software-selectable transfer rates range from 300 bit/s to 1.5 Mbit/s, with the available maximum dependent on the selected interface type.

For RS422 and RS485 connections, the RS204 includes integrated terminating resistors that can be connected or disconnected through DIP switches. This supports proper bus termination at the module end of a serial segment. All four interfaces are galvanically isolated at 500 V, both from the controller system and from one another, which helps separate serial field circuits from the controller backplane and from each other.

The module requires an external supply of 18–34 VDC and consumes 120 mA at 24 VDC. It is rated for operation from -30 °C to +60 °C and for 5–95% non-condensing relative humidity. The standard RS204 carries CE, UKCA, and cULus approvals, and the documented marine approval scope includes ABS, BV, DNV, KR, LR, NK, and RINA.

Bachmann also documents an RS204 CC variant, order number 00021674-00, described as a Cold Climate version with the same four-port RS232/RS422/RS485 configuration. The standard RS204 order number is 00021235-00. The documented accessory KZ 51/02 B is a two-pin, 5.08 mm-pitch cage-clamp terminal with labeling strips.

 

Applications & System Role

The RS204 sits in the communication layer of a Bachmann M200 automation system. It adds serial ports to the controller, allowing the M200 system to communicate with devices that do not use Ethernet or the controller’s built-in serial interfaces.

Typical integration points are serial field equipment, remote devices, instruments, and subsystems using RS232, RS422, or RS485. Because the module supports multiple interface standards on one module and can be used in Fastbus SubDevices, it is applicable where serial devices are distributed across a Bachmann automation architecture rather than concentrated at the main controller.

 

FAQ

What is the Bachmann RS204?
It is a Bachmann serial interface module that adds four asynchronous serial ports to an M200 controller system.

Which serial standards does the RS204 support?
It supports RS232, RS422, and RS485. The four ports can use different standards and can be combined on one module.

What is the maximum communication speed?
RS422 and RS485 support up to 1.5 MBaud. RS232 supports up to 115.2 kBaud.

How is the RS204 connected to the controller?
It is mounted on the M200 backplane and provides four 9-pin D-sub serial connectors for field connections.

Does the RS204 provide bus termination?
Yes. It includes integrated terminating resistors for RS422 and RS485, which are connected or disconnected using DIP switches.

What power supply does the RS204 require?
It requires an external supply of 18–34 VDC and consumes 120 mA at 24 VDC.

Are the serial ports isolated?
Yes. Each interface is galvanically isolated at 500 V from the controller system and from the other interfaces.

Is there a cold-climate version?
Yes. The RS204 CC, order number 00021674-00, is the documented Cold Climate variant of the four-port RS204.