Description
Core Product Summary
The BEMAC UGS-21 is an automatic generator controller designed for marine power stations and heavy-duty industrial generator control systems. Manufactured by BEMAC Corporation (formerly Uzushio Electric Co., Ltd.), the module manages automatic sequence control, synchronization, load sharing, and power management across multi-generator installations on commercial vessels, offshore platforms, and industrial power plants.
Engineered to integrate directly into main switchboards (MSB) and emergency switchboards (ESB), the UGS-21 continuously monitors busbar and generator voltage, frequency, phase alignment, and current loads. It manages automatic generator starting, automatic synchronizing, breaker closing, proportional active load sharing, and standby generator blackout prevention logic to ensure continuous power availability in marine environments.
Key Technical Specifications
| Parameter | Specification |
| Manufacturer | BEMAC Corporation (Uzushio Electric) |
| Model / Type | UGS-21 |
| Product Type | Automatic Generator Controller / Auto Power Management Module |
| Application | Marine Main Switchboard (MSB) & Industrial Power Generation |
| Bus Voltage Input Rating | AC 110 V (Secondary Rating, 50/60 Hz) |
| Current Transformer Input | AC 5 A (Secondary Rating) |
| Control Power Supply | DC 18 V to 32 V (Nominal 24 V DC auxiliary supply) |
| Control Functions | Auto Start/Stop, Auto Synchronizing, Auto Load Sharing, Blackout Protection |
| Installation / Mounting | Switchboard panel embedded / rack-mounted unit |
| Target Environment | Marine classification compliance for high humidity, vibration, and temperature |
Detailed Product Overview
The BEMAC UGS-21 serves as the central control logic block within BEMAC marine switchboard automation systems. On modern commercial vessels, managing auxiliary diesel generator sets requires coordinated control to handle varying electrical loads—ranging from dynamic propulsion drives and heavy bow thrusters to routine hotel loads.
Automatic Synchronizing & Paralleling
When an oncoming generator reaches operational speed, the UGS-21 matches the incoming generator’s voltage, frequency, and phase angle to the live busbar. Once phase alignment falls within pre-set synchronization windows, the controller issues a high-speed breaker close command to parallel the incoming set safely without mechanical shock or voltage dips.
Load Sharing & Power Management
When multiple generators run in parallel, the UGS-21 manages active power sharing across governor speed controls to distribute load proportionally. It continuously evaluates total bus load against installed capacity, automatically initiating standby generator start sequences when demand spikes, or shedding non-essential loads during low-capacity events to prevent full-ship blackouts.

UGS-21

UGS-21
Engineering Selection Highlights
- Integrated Generator Automation: Combines automatic starting, frequency matching, synchronizing, and load sharing into a single switchboard module.
- Standardized PT/CT Interface: Accepts standard AC 110 V potential transformer (PT) bus sensing and AC 5 A current transformer (CT) input loops.
- Marine-Grade Reliability: Built to withstand constant engine room vibration, high ambient thermal stress, and humid marine atmospheres.
- Blackout Prevention Logic: Monitors main bus stability and automatically initiates emergency start-up and transfer sequences if main bus voltage drops below threshold limits.
- Front-Panel Status Monitoring: Provides clear status verification for bus voltage, generator readiness, paralleling conditions, and alarm states.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| Switchboard Infrastructure | BEMAC Main Switchboard (MSB) / Emergency Switchboard (ESB) | Slots into designated generator control section cutouts. |
| Potential Transformers (PT) | Standard AC 110 V secondary voltage transformers | Must be connected to monitor busbar and generator phase voltages. |
| Current Transformers (CT) | Standard AC 5 A secondary current transformers | Install CTs on generator feeder phases for active current measurement. |
| Auxiliary Supply | Regulated DC 24 V (18–32 V DC range) system power | Wire from essential battery-backed switchboard DC supply lines. |
| Governor & AVR Interface | Speed Governor Actuator / Automatic Voltage Regulator (AVR) | Output relays wire into engine speed trim and AVR fine-voltage adjust terminals. |
Dimensions, Mounting & Connection Notes
- Mounting Method: Panel-mount into the front face of the generator control cubicle. Secure via front-panel mounting screws or side clamping brackets.
- Wiring Separation: Route AC voltage sensing (110 V) and CT current loops (5 A) separately from low-voltage DC control signal lines to prevent noise coupling.
- CT Secondary Circuit Safety: Never open-circuit the secondary terminals of an energized current transformer. Ensure shorting blocks are engaged before disconnecting CT lines from the UGS-21 rear terminal block.
- Grounding: Connect the rear metal chassis terminal directly to the main switchboard copper earth bar using a short, low-impedance ground strap.
FAQ
What is the main function of the BEMAC UGS-21?
The UGS-21 is an automatic generator controller used in marine switchboards to perform auto-start, auto-synchronization, parallel load sharing, and power monitoring for diesel generator sets.
What are the voltage and current secondary ratings for the UGS-21?
The module accepts standard AC 110 V for busbar/generator potential transformer (PT) sensing and AC 5 A for current transformer (CT) load monitoring.
Can the UGS-21 be used for emergency generator control?
Yes, it is suitable for both main generator paralleling and emergency power station auto-start and bus transfer operations on marine vessels and offshore installations.
What auxiliary power supply is required to operate the controller?
The UGS-21 requires a nominal 24 V DC auxiliary supply (operating within an 18 V to 32 V DC range).
Verification & Troubleshooting Notes
- Synchronization Failures (Breaker Will Not Close):
- Check PT sensing lines for balanced 110 V AC input across incoming generator and bus terminals.
- Confirm that engine governor speed controls respond to raise/lower pulse commands sent by the UGS-21 during frequency matching routines.
- Verify phase rotation order on both busbar and generator sides using a phase rotation meter.
- Unequal Load Sharing in Parallel Operation:
- Check CT input connections (5 A loops) on all parallel channels for correct polarity and wiring integrity.
- Inspect governor droop settings or analog speed bias signal interfaces between the UGS-21 and generator speed controllers.
- Auxiliary Power Fault / Module Dead:
- Measure incoming DC supply across control power terminals using a multimeter. Ensure voltage remains stable within 18–32 V DC under engine cranking conditions.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626