Sale!

Bender RCM475LY-13 Residual Current Monitor

The Bender RCM475LY-13 is a Type A residual current monitor for grounded TN and TT power systems. It continuously measures residual current in single-phase and three-phase circuits and detects both sinusoidal AC and pulsating DC leakage currents.

Categories: , , , , SKU: RCM475LY-13 Brand:

Description

Core Product Summary

The Bender RCM475LY-13 is a Type A residual current monitor for grounded TN and TT power systems. It continuously measures residual current in single-phase and three-phase circuits and detects both sinusoidal AC and pulsating DC leakage currents.

The monitor uses an internal current transformer with an 18 mm conductor window and provides an adjustable response value from 10 mA to 10 A at 50/60 Hz. Its response delay is adjustable from 0 to 10 seconds. The RCM475LY-13 operates from AC 90–132 V and is identified by Bender article number B 9401 2035.

 

Key Technical Specifications

Parameter Specification
Manufacturer Bender
Model RCM475LY-13
Article number B 9401 2035
Product type Residual current monitor / ground-fault monitor
Detection type Type A
Monitored current types Sinusoidal AC and pulsating DC residual currents
System compatibility Grounded TN and TT systems
Measuring range 10 mA to 10 A
Frequency range 50/60 Hz
Response-value adjustment Stepless, 10 mA to 10 A
Response-delay adjustment 0 to 10 seconds
Current transformer Internal, 18 mm conductor window
Measuring-current connection Internal or external, selectable
Supply voltage AC 90–132 V
Supply frequency 50/60 Hz
Display LED bar graph
Relay outputs Alarm and prewarning relay contacts
Test and reset Test/reset button
External test/reset input Available
Fault-memory function Selectable
PE and N-PE conductor monitoring Available
Approvals CE, GL
Standards EN 62020, IEC/TR 60755
Dimensions 96 mm × 45 mm × 72 mm
Weight 0.2 kg

 

Engineering Selection Highlights

  • The RCM475LY-13 is a Type A residual current monitor, so it detects both sinusoidal AC leakage and pulsating DC residual currents in grounded TN and TT systems.
  • Its 10 mA to 10 A adjustable response range allows the alarm threshold to be matched to the monitored circuit’s expected leakage level and protection requirement.
  • The 0–10 second adjustable delay supports selective alarming or delayed response, helping distinguish a developing leakage condition from transient events.
  • The internal 18 mm current transformer accepts the monitored conductors through its window; all live conductors, including the neutral where applicable, must be routed through the transformer.
  • The monitor provides alarm and prewarning relay outputs, allowing leakage conditions to be signaled to a PLC, DCS, annunciator, or building-management system.
  • The selectable internal or external measuring-current connection and available PE/N-PE monitoring functions support flexible installation in grounded distribution systems.
  • The AC 90–132 V supply range must be matched to the available auxiliary supply; other RCM475LY variants use different supply voltages and response ranges.
RCM475LY-13

RCM475LY-13

RCM475LY-13

RCM475LY-13

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Power-system type Grounded TN and TT systems The monitor is intended for residual-current monitoring in these grounded architectures.
Current measurement Internal 18 mm current transformer The monitored conductors pass through the transformer window.
Measuring-current connection Internal or external, selectable The installation must use the configured measuring-current path.
Auxiliary supply AC 90–132 V, 50/60 Hz The control-power supply must remain within this range.
Alarm integration Alarm and prewarning relay contacts Relay outputs can signal leakage conditions to supervisory or protection systems.
Test function Front test/reset button and external test/reset input Supports local and remote functional testing.
Standards EN 62020 and IEC/TR 60755 The device is a Type A residual current monitor under these standards.

 

Dimensions, Mounting & Connection Notes

Item Specification
Dimensions 96 mm × 45 mm × 72 mm
Weight 0.2 kg
Current-transformer window 18 mm internal diameter
Mounting Screw mounting or DIN-rail adapter
Conductor routing Monitored circuit conductors pass through the internal current-transformer window
Auxiliary supply AC 90–132 V, 50/60 Hz
User controls Test/reset button, adjustable response value, adjustable response delay
Indication LED bar graph showing residual current as a percentage of the set response value

 

Detailed Product Overview

The Bender RCM475LY-13 is a Type A residual current monitor designed for continuous leakage-current monitoring in grounded TN and TT power systems. It detects both sinusoidal AC residual currents and pulsating DC residual currents, making it suitable for circuits where electronic loads, rectifiers, or other non-sinusoidal equipment may produce DC fault-current components.

The monitor uses an internal current transformer with an 18 mm conductor window. The monitored circuit conductors pass through this window, and the device evaluates the resulting residual-current signal continuously. The measuring-current connection can be configured as internal or external, and the device includes selectable PE and N-PE conductor monitoring.

The response value is steplessly adjustable from 10 mA to 10 A at 50/60 Hz. The response delay is adjustable from 0 to 10 seconds. These settings allow the monitor to be matched to the leakage behavior and protection philosophy of the monitored circuit.

The RCM475LY-13 provides alarm and prewarning relay outputs. An LED bar graph indicates the measured residual current as a percentage of the set response value, while the test/reset button supports local functional testing. An external test/reset input is also available, and a selectable fault-memory function can retain alarm information after the initiating condition clears.

The device operates from AC 90–132 V at 50/60 Hz and is supplied as Bender article number B 9401 2035. It is CE and GL approved and conforms to EN 62020 and IEC/TR 60755. The RCM475LY-13 is a monitoring relay rather than a circuit-breaking device; its relay outputs are used to signal conditions to downstream protection or supervisory equipment.

 

Applications & System Role

The RCM475LY-13 occupies the residual-current monitoring position in a grounded TN or TT distribution system. It measures the vector sum of the currents passing through its current transformer and identifies leakage or earth-fault current that is not returning through the intended conductors.

Its relay outputs provide early warning and alarm signaling for leakage-current conditions. The monitor is therefore used as a condition-monitoring and alarm device for distribution circuits, allowing developing insulation or earth-fault conditions to be identified before they escalate.

 

FAQ

 

What is the Bender RCM475LY-13?

The Bender RCM475LY-13 is a Type A residual current monitor for grounded TN and TT systems that detects AC and pulsating DC leakage currents.

 

What leakage-current range does it cover?

The response value is adjustable from 10 mA to 10 A at 50/60 Hz.

 

What supply voltage does it require?

The RCM475LY-13 operates from AC 90–132 V at 50/60 Hz.

 

What is the adjustable response delay?

The response delay is adjustable from 0 to 10 seconds.

 

What type of current transformer does it include?

It includes an internal current transformer with an 18 mm conductor window.

 

Does it detect DC fault currents?

Yes. As a Type A residual current monitor, it detects both sinusoidal AC and pulsating DC residual currents.

 

What outputs does it provide?

It provides alarm and prewarning relay contacts for connection to alarms, PLCs, DCS, or other supervisory systems.

 

What standards apply to the RCM475LY-13?

The device conforms to EN 62020 and IEC/TR 60755 and is CE and GL approved.