Sale!

Berghof C1CPU-4S CANtrol Cell Controller CPU Module

Item Verified specification
Manufacturer Berghof Automationstechnik
Model C1CPU-4S
Product type Cell-controller CPU module
Automation platform CANtrol automation system
Network technology CAN bus; CANopen
Runtime software CPC++ runtime and real-time CAN/CANopen software on C1CPU-4S-00
Optional runtime CP1131 runtime system on designated variants
Serial interfaces Variant-dependent: C1CPU-4S-01 includes 2 x RS-232C and 2 x RS-485; C1CPU-4S-02 includes 4 x RS-232
Rated supply voltage 24 V DC
Categories: , , , , SKU: C1CPU-4S Brand:

Description

Core Product Summary

The Berghof C1CPU-4S is a cell-controller CPU module for the CANtrol automation system, a modular CAN-bus-based control platform used in industrial machinery and process-control applications. It functions as the controller node in a CANtrol installation, coordinating local control tasks and communication across the CAN network.

The C1CPU-4S is supplied in several variants. The base C1CPU-4S-00 configuration includes CPC++ runtime software and real-time CAN/CANopen software; other variants add CP1131 runtime capability or additional serial interfaces. The module operates from a 24 V DC supply within the CANtrol system’s specified 18 V to 32 V tolerance range and is intended for permanent installation in a switchgear cabinet.

 

Key Technical Specifications

Item Verified specification
Manufacturer Berghof Automationstechnik
Model C1CPU-4S
Product type Cell-controller CPU module
Automation platform CANtrol automation system
Network technology CAN bus; CANopen
Runtime software CPC++ runtime and real-time CAN/CANopen software on C1CPU-4S-00
Optional runtime CP1131 runtime system on designated variants
Serial interfaces Variant-dependent: C1CPU-4S-01 includes 2 x RS-232C and 2 x RS-485; C1CPU-4S-02 includes 4 x RS-232
Rated supply voltage 24 V DC
Supply tolerance 18 V to 32 V DC
Installation environment Permanent installation in switchgear cabinets
Ingress protection IP20
Operating temperature 0 °C to +50 °C, horizontal installation
Relative humidity 5% to 95%, non-condensing
Maximum altitude 2,000 m
EMC standards EN 50081-2 and EN 50082-2
Control-system standard EN 61131-2 behavioral specifications

 

Engineering Selection Highlights

  • The C1CPU-4S is a Berghof CANtrol cell controller, so it should be selected for CANtrol-based installations rather than treated as an Allen-Bradley controller.
  • The exact suffix determines the software and serial-interface configuration; C1CPU-4S-00, -01, -02, and -00-1131 are documented variants with different capabilities.
  • CAN and CANopen support makes the module suitable where the control architecture relies on the CANtrol CAN network.
  • The 24 V DC supply requirement, with an 18 V to 32 V tolerance, must be matched to the cabinet power distribution and SELV supply arrangement.
  • IP20 construction and cabinet installation requirements mean the module requires an appropriate enclosure rather than exposed mounting.
  • The CANtrol system’s EMC requirements assume installation on an electrically conductive, grounded mounting plate, so cabinet grounding and wiring practice affect compliance.
  • Connection hardware is not automatically included; the documented C1CPU-4S-00 configuration uses three 9-pin plugs, which are not supplied.
C1CPU-4S

C1CPU-4S

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Automation platform Berghof CANtrol automation system The controller is part of the CANtrol modular automation architecture.
Network CAN bus and CANopen The module provides CAN/CANopen-oriented control and communication capability.
Power supply 24 V DC rated; 18 V to 32 V tolerance Use an SELV supply consistent with EN 61131-2.
Software environment CPC++ runtime; CP1131 runtime on designated variants The required runtime depends on the exact C1CPU-4S suffix.
Serial communication Variant-dependent RS-232 and RS-485 interfaces Confirm the suffix before planning serial-device connections.
Mounting CANtrol cabinet installation on a grounded conductive mounting plate Cabinet grounding supports the stated EMC installation basis.
Connection accessories 9-pin plugs for the documented C1CPU-4S-00 configuration The plugs are not supplied with the module.

 

Dimensions, Mounting & Connection Notes

The CANtrol system is designed for permanent installation in switchgear cabinets under normal operating conditions. The C1CPU-4S is part of this modular system and is installed in accordance with the CANtrol mechanical-layout and module-arrangement requirements.

The module is rated IP20 and is intended for horizontal installation within the stated 0 °C to +50 °C operating range. CANtrol modules are functionally grounded through the mounting rail rather than through a protective ground connection; supply voltages should nevertheless be grounded for operating safety, with a detachable ground connection at the load power supply or isolating transformer.

For the documented C1CPU-4S-00 configuration, connection uses three 9-pin plugs, which are not supplied. Cable selection, CAN termination, node addressing, and baud-rate configuration must follow the CANtrol project-planning requirements for the specific network.

 

Detailed Product Overview

The Berghof C1CPU-4S is the CPU module designation within Berghof’s CANtrol automation system. It is a cell controller intended to run the control application and provide CAN-based communication within a modular industrial automation installation. The CANtrol platform is based on the CAN bus and is documented for machinery and industrial-process control in low-voltage installations.

The exact C1CPU-4S suffix is important because it defines both the runtime environment and the available serial interfaces. The C1CPU-4S-00 configuration includes CPC++ runtime software together with real-time CAN/CANopen software. The C1CPU-4S-00-1131 variant adds the CP1131 runtime system. The C1CPU-4S-01 variant adds two RS-232C and two RS-485 interfaces, while the C1CPU-4S-02 variant provides four RS-232 interfaces and the CP1131 runtime system.

Power integration follows the CANtrol system requirements: the rated supply is 24 V DC, with an allowable 18 V to 32 V range. Berghof recommends remaining within the 19.2 V to 30 V band specified by EN 61131-2 where compatibility with other system components is required. The module is designed for cabinet installation, with IP20 protection and a 0 °C to +50 °C operating range under horizontal installation conditions.

The C1CPU-4S should therefore be specified by its complete suffix and verified against the installed CANtrol configuration. Matching only the base designation is insufficient when serial-interface count, runtime software, or connection requirements differ between variants.

 

Applications & System Role

In a CANtrol architecture, the C1CPU-4S acts as the cell-controller CPU: it executes the control application and communicates with other CANtrol modules over the CAN network. Its CANopen capability supports the CANtrol system’s distributed control approach, in which CPU, I/O, remote, and expansion modules form a coordinated automation system.

The module is appropriate for industrial control applications in the medium-to-high performance range, as defined for the CANtrol platform. Its role is controller-level coordination and network communication, while I/O expansion modules handle the associated field-signal interface.

 

FAQ

What is the Berghof C1CPU-4S?
It is a cell-controller CPU module for the Berghof CANtrol automation system.

Is C1CPU-4S an Allen-Bradley product?
No. The C1CPU-4S is a Berghof CANtrol controller module; “A-B” labeling in some listings is not a reliable identification of its manufacturer.

What network technology does it use?
It uses the CAN bus and supports CANopen-based communication within the CANtrol system.

What power supply does it require?
The CANtrol system uses a 24 V DC SELV supply, with an allowable module operating range of 18 V to 32 V DC.

What is the difference between C1CPU-4S variants?
The suffix determines the runtime software and serial-interface configuration: -00 includes CPC++ and CAN/CANopen software; -00-1131 adds CP1131 runtime; -01 adds 2 x RS-232C and 2 x RS-485; -02 provides 4 x RS-232 and CP1131 runtime.

Can it be mounted outside a cabinet?
The CANtrol system is intended for permanent installation in switchgear cabinets, and the modules have an IP20 protection rating.

Which environmental limits apply?
The CANtrol module environment is 0 °C to +50 °C during horizontal operation, 5% to 95% relative humidity without condensation, and a maximum altitude of 2,000 m.

Are connection plugs included?
For the documented C1CPU-4S-00 configuration, three 9-pin plugs are required and are not supplied.