Description
Core Product Summary
The Berghof C1CPU-4S is a cell-controller CPU module for the CANtrol automation system, a modular CAN-bus-based control platform used in industrial machinery and process-control applications. It functions as the controller node in a CANtrol installation, coordinating local control tasks and communication across the CAN network.
The C1CPU-4S is supplied in several variants. The base C1CPU-4S-00 configuration includes CPC++ runtime software and real-time CAN/CANopen software; other variants add CP1131 runtime capability or additional serial interfaces. The module operates from a 24 V DC supply within the CANtrol system’s specified 18 V to 32 V tolerance range and is intended for permanent installation in a switchgear cabinet.
Key Technical Specifications
| Item | Verified specification |
|---|---|
| Manufacturer | Berghof Automationstechnik |
| Model | C1CPU-4S |
| Product type | Cell-controller CPU module |
| Automation platform | CANtrol automation system |
| Network technology | CAN bus; CANopen |
| Runtime software | CPC++ runtime and real-time CAN/CANopen software on C1CPU-4S-00 |
| Optional runtime | CP1131 runtime system on designated variants |
| Serial interfaces | Variant-dependent: C1CPU-4S-01 includes 2 x RS-232C and 2 x RS-485; C1CPU-4S-02 includes 4 x RS-232 |
| Rated supply voltage | 24 V DC |
| Supply tolerance | 18 V to 32 V DC |
| Installation environment | Permanent installation in switchgear cabinets |
| Ingress protection | IP20 |
| Operating temperature | 0 °C to +50 °C, horizontal installation |
| Relative humidity | 5% to 95%, non-condensing |
| Maximum altitude | 2,000 m |
| EMC standards | EN 50081-2 and EN 50082-2 |
| Control-system standard | EN 61131-2 behavioral specifications |
Engineering Selection Highlights
- The C1CPU-4S is a Berghof CANtrol cell controller, so it should be selected for CANtrol-based installations rather than treated as an Allen-Bradley controller.
- The exact suffix determines the software and serial-interface configuration; C1CPU-4S-00, -01, -02, and -00-1131 are documented variants with different capabilities.
- CAN and CANopen support makes the module suitable where the control architecture relies on the CANtrol CAN network.
- The 24 V DC supply requirement, with an 18 V to 32 V tolerance, must be matched to the cabinet power distribution and SELV supply arrangement.
- IP20 construction and cabinet installation requirements mean the module requires an appropriate enclosure rather than exposed mounting.
- The CANtrol system’s EMC requirements assume installation on an electrically conductive, grounded mounting plate, so cabinet grounding and wiring practice affect compliance.
- Connection hardware is not automatically included; the documented C1CPU-4S-00 configuration uses three 9-pin plugs, which are not supplied.

C1CPU-4S
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Automation platform | Berghof CANtrol automation system | The controller is part of the CANtrol modular automation architecture. |
| Network | CAN bus and CANopen | The module provides CAN/CANopen-oriented control and communication capability. |
| Power supply | 24 V DC rated; 18 V to 32 V tolerance | Use an SELV supply consistent with EN 61131-2. |
| Software environment | CPC++ runtime; CP1131 runtime on designated variants | The required runtime depends on the exact C1CPU-4S suffix. |
| Serial communication | Variant-dependent RS-232 and RS-485 interfaces | Confirm the suffix before planning serial-device connections. |
| Mounting | CANtrol cabinet installation on a grounded conductive mounting plate | Cabinet grounding supports the stated EMC installation basis. |
| Connection accessories | 9-pin plugs for the documented C1CPU-4S-00 configuration | The plugs are not supplied with the module. |
Dimensions, Mounting & Connection Notes
The CANtrol system is designed for permanent installation in switchgear cabinets under normal operating conditions. The C1CPU-4S is part of this modular system and is installed in accordance with the CANtrol mechanical-layout and module-arrangement requirements.
The module is rated IP20 and is intended for horizontal installation within the stated 0 °C to +50 °C operating range. CANtrol modules are functionally grounded through the mounting rail rather than through a protective ground connection; supply voltages should nevertheless be grounded for operating safety, with a detachable ground connection at the load power supply or isolating transformer.
For the documented C1CPU-4S-00 configuration, connection uses three 9-pin plugs, which are not supplied. Cable selection, CAN termination, node addressing, and baud-rate configuration must follow the CANtrol project-planning requirements for the specific network.
Detailed Product Overview
The Berghof C1CPU-4S is the CPU module designation within Berghof’s CANtrol automation system. It is a cell controller intended to run the control application and provide CAN-based communication within a modular industrial automation installation. The CANtrol platform is based on the CAN bus and is documented for machinery and industrial-process control in low-voltage installations.
The exact C1CPU-4S suffix is important because it defines both the runtime environment and the available serial interfaces. The C1CPU-4S-00 configuration includes CPC++ runtime software together with real-time CAN/CANopen software. The C1CPU-4S-00-1131 variant adds the CP1131 runtime system. The C1CPU-4S-01 variant adds two RS-232C and two RS-485 interfaces, while the C1CPU-4S-02 variant provides four RS-232 interfaces and the CP1131 runtime system.
Power integration follows the CANtrol system requirements: the rated supply is 24 V DC, with an allowable 18 V to 32 V range. Berghof recommends remaining within the 19.2 V to 30 V band specified by EN 61131-2 where compatibility with other system components is required. The module is designed for cabinet installation, with IP20 protection and a 0 °C to +50 °C operating range under horizontal installation conditions.
The C1CPU-4S should therefore be specified by its complete suffix and verified against the installed CANtrol configuration. Matching only the base designation is insufficient when serial-interface count, runtime software, or connection requirements differ between variants.
Applications & System Role
In a CANtrol architecture, the C1CPU-4S acts as the cell-controller CPU: it executes the control application and communicates with other CANtrol modules over the CAN network. Its CANopen capability supports the CANtrol system’s distributed control approach, in which CPU, I/O, remote, and expansion modules form a coordinated automation system.
The module is appropriate for industrial control applications in the medium-to-high performance range, as defined for the CANtrol platform. Its role is controller-level coordination and network communication, while I/O expansion modules handle the associated field-signal interface.
FAQ
What is the Berghof C1CPU-4S?
It is a cell-controller CPU module for the Berghof CANtrol automation system.
Is C1CPU-4S an Allen-Bradley product?
No. The C1CPU-4S is a Berghof CANtrol controller module; “A-B” labeling in some listings is not a reliable identification of its manufacturer.
What network technology does it use?
It uses the CAN bus and supports CANopen-based communication within the CANtrol system.
What power supply does it require?
The CANtrol system uses a 24 V DC SELV supply, with an allowable module operating range of 18 V to 32 V DC.
What is the difference between C1CPU-4S variants?
The suffix determines the runtime software and serial-interface configuration: -00 includes CPC++ and CAN/CANopen software; -00-1131 adds CP1131 runtime; -01 adds 2 x RS-232C and 2 x RS-485; -02 provides 4 x RS-232 and CP1131 runtime.
Can it be mounted outside a cabinet?
The CANtrol system is intended for permanent installation in switchgear cabinets, and the modules have an IP20 protection rating.
Which environmental limits apply?
The CANtrol module environment is 0 °C to +50 °C during horizontal operation, 5% to 95% relative humidity without condensation, and a maximum altitude of 2,000 m.
Are connection plugs included?
For the documented C1CPU-4S-00 configuration, three 9-pin plugs are required and are not supplied.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626