Sale!

B&R X20BR9300 X2X Link Bus Receiver Module for X20 System

The B&R X20BR9300 is an X2X Link bus receiver module designed for the X20 distributed I/O system. It serves as the interface between the main controller and remote X20 I/O segments, receiving backplane communication while simultaneously providing a power feed for both the X2X Link bus and the internal I/O supply.

Categories: , , , , SKU: X20BR9300 Brand:

Description

Core Product Summary

The B&R X20BR9300 is an X2X Link bus receiver module designed for the X20 distributed I/O system. It serves as the interface between the main controller and remote X20 I/O segments, receiving backplane communication while simultaneously providing a power feed for both the X2X Link bus and the internal I/O supply.

This module is engineered for installation exclusively in the far-left slot of an X20 segment. It features electrical isolation between the power feed and the X2X Link supply, supports redundant operation through parallel connection of multiple supply modules, and includes integrated short-circuit and overload protection. It requires a compatible X20 power supply bus module (such as X20BM01 or X20BM05) and a 12-pin X20TB12 terminal block for operation.

 

Key Technical Specifications

Parameter Verified Specification
Module Type X2X Link bus receiver with supply for I/O and bus
Installation Position Far-left slot of the X20 segment only
X2X Link Input Voltage 24 VDC (-15% / +20%)
X2X Link Input Current Max. 0.7 A
X2X Link Output Power 7 W (nominal)
Internal I/O Power Consumption 0.6 W
Bus Power Consumption 1.62 W
Electrical Isolation X2X Link supply isolated from X2X Link power supply
Overload Protection Short-circuit proof, temporary overload protection (integrated fuse)
Redundancy Supported via parallel operation of multiple supply modules
Certifications CE, UKCA, ATEX Zone 2, cULus, HazLoc, KC

 

Engineering Selection Highlights

  • Remote Segment Interface: Enables the extension of the X20 system architecture by receiving X2X Link communication from a remote controller or bus transmitter segment.
  • Integrated Power Feed: Consolidates communication reception and power distribution (7 W nominal output) into a single 12.5 mm module, reducing cabinet space and wiring complexity.
  • Strict Positioning Requirement: Designed exclusively for the far-left slot of an X20 segment; it cannot be placed in intermediate positions.
  • Redundancy Capability: Supports parallel and redundant operation of the X2X Link supply, enhancing system availability for critical applications.
  • Critical Compatibility Constraint: Must not be used in conjunction with continuous power supply modules (e.g., X20BM11 or X20BM15) to prevent X2X Link communication conflicts.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
System Family B&R X20 System Functions as the receiving end of a remote X2X Link segment.
Installation Slot Far-left position only Mandatory for proper backplane communication and power distribution.
Mandatory Bus Module X20BM01 or X20BM05 Power supply bus module required; continuous bus modules (X20BM11/X20BM15) are explicitly prohibited.
Mandatory Terminal Block X20TB12 12-pin, 24 VDC keyed terminal block required for field wiring.
Cabling X2X Link Cable (e.g., X67CA0X99 series) Required to connect the remote transmitter to this receiver.

 

Dimensions, Mounting & Connection Notes

  • Module Pitch: 12.5 mm (+0.2 mm tolerance).
  • Mounting Orientation: Supported in both horizontal and vertical orientations.
  • Operating Temperature: -25 to 60°C (horizontal); -25 to 50°C (vertical).
  • Installation Elevation: No limitation up to 2000 m. Above 2000 m, ambient temperature must be reduced by 0.5°C per 100 m.
  • Degree of Protection: IP20.
  • Connection Method: Pluggable 12-pin terminal block (X20TB12, ordered separately).
  • Included Hardware: Left and right X20 locking plates (end cover plates) are included in the delivery.

 

Detailed Product Overview

The B&R X20BR9300 is a specialized bus receiver module engineered for the X20 distributed I/O system. In large or modular automation architectures, extending I/O capacity beyond the main controller rack requires a reliable, high-speed communication link. The X20BR9300 fulfills this role by acting as the receiving interface for remote X20 segments connected via the X2X Link network.

A defining characteristic of this module is its dual functionality: it receives X2X Link communication and simultaneously provides a regulated power feed for both the X2X Link bus and the internal I/O supply of the local segment. This consolidation reduces the need for additional power distribution hardware at the remote location. The module delivers a nominal output power of 7 W for the X2X Link supply, with an integrated, non-replaceable fuse providing short-circuit and temporary overload protection.

Electrical isolation is maintained between the power feed and the X2X Link supply, preventing ground loops and ensuring signal integrity across extended cable runs. For applications demanding high availability, the X20BR9300 supports redundant operation. Multiple supply modules can be operated in parallel to ensure continuous power to the X2X Link bus in the event of a single supply failure.

System integration requires strict adherence to placement rules. The X20BR9300 must be installed exclusively in the far-left slot of the X20 segment. Furthermore, it is explicitly incompatible with continuous power supply bus modules such as the X20BM11 or X20BM15; using these together can cause X2X Link communication failures. Instead, it must be paired with a dedicated power supply bus module like the X20BM01 or X20BM05, which interrupts the internal I/O power supply to the left, preventing backfeed conflicts.

The module operates within a wide temperature range (-25°C to 60°C horizontally) and holds comprehensive global certifications, including ATEX Zone 2, cULus, and HazLoc, making it suitable for deployment in demanding industrial and hazardous environments. Local LED indicators provide immediate visual diagnostics for module run status, X2X bus function, and overload conditions, while detailed status is also mapped to the controller’s software registers for predictive maintenance.

 X20BR9300

X20BR9300

 X20BR9300

X20BR9300

Applications & System Role

The B&R X20BR9300 serves as the critical entry point for remote X20 I/O segments within a distributed automation architecture. Its primary role is to terminate the X2X Link communication cable from a central controller or bus transmitter, converting the serial bus signal back into parallel backplane communication for the local X20 modules. By integrating the X2X Link power feed, it eliminates the need for separate power injection points at the remote segment, streamlining the design of distributed machine cabinets, process skids, and modular production lines.

 

FAQ

Q: What is the B&R X20BR9300?
A: The B&R X20BR9300 is an X2X Link bus receiver module for the X20 System, designed to receive remote segment communication and provide an integrated power feed for the X2X Link and internal I/O supply.

Q: Where must the X20BR9300 be installed in the X20 segment?
A: It must be installed exclusively in the far-left slot of the X20 segment. It cannot be placed in intermediate positions.

Q: Can the X20BR9300 be used with a standard X20BM11 bus module?
A: No. It is explicitly prohibited to use the X20BR9300 with continuous power supply modules like the X20BM11 or X20BM15, as this can cause X2X Link communication conflicts. It requires a power supply bus module such as the X20BM01 or X20BM05.

Q: Does the module support redundant power configurations?
A: Yes, it supports parallel and redundant operation of the X2X Link supply by allowing multiple supply modules to operate simultaneously.

Q: What is the power output capacity of the X20BR9300?
A: It provides a nominal output power of 7 W for the X2X Link supply, with an input voltage range of 24 VDC (-15% / +20%).

Q: What mandatory accessories are required for installation?
A: Installation requires one X20 power supply bus module (X20BM01 or X20BM05) and one 12-pin X20TB12 terminal block, both ordered separately. Left and right locking plates are included with the module.