Eaton MC2-442-57CQB-1-2A 5.7 in IR Touch HMI

  • Model: Eaton MC2-442-57CQB-1-2A
  • Brand: Eaton / Moeller
  • Series: MICRO PANEL, equivalent to XV400 5.7 in
  • Core Function: Machine visualization, operation, and optional local control
  • Product Type: HMI / integrated HMI-PLC touch panel
  • Key Specs: 5.7 in CSTN color LCD; 320 x 240 resolution; infrared touch; 24 VDC supply
  • ⚠️ Obsolete Model – Limited Stock Available
  • Condition: Confirm per unit—New Original / New Surplus, refurbished, or used/tested
Categories: , , , , , Brand:

Description

Key Technical Specifications

Parameter Value
Manufacturer Eaton / Moeller
Model MC2-442-57CQB-1-2A
Equivalent XV400 model XV-442-57CQB-1-2A
Display type 5.7 in CSTN color LCD
Display resolution 320 x 240 pixels, QVGA
Visible display area 115 x 86 mm
Touch technology Infrared touch matrix
Front style 4-hole mounting front
Supply voltage 24 VDC from a SELV AC/DC power supply
Power protection Internal fuse and reverse-polarity protection
Ethernet 10Base-T port
Serial interface RS-232 system port, 9-pin D-Sub male
CAN interface CAN port with CAN ACT status LED
USB ports USB Host and USB Device
Storage CompactFlash slot 0 for operating system and normally PLC/visualization projects
Dimensions 220 mm wide x 170 mm high x 81 mm deep
Mounting cutout material thickness 2-20 mm for 4-hole-front devices
Operating position Horizontal or vertical panel mounting
Ventilation clearance At least 3 cm from ventilation slots; at least 15 cm from major heat sources
Intended use Visualization, operation, and control of machines and systems
Safety-function limitation Not approved for implementing personnel or machinery safety functions

 

Product Introduction

The Eaton MC2-442-57CQB-1-2A is a 5.7 in MICRO PANEL operator interface for machine visualization, operation, and control. It is the MC2 designation for the equivalent Eaton XV-442-57CQB-1-2A and uses an infrared touch sensor with a 320 x 240 CSTN color display.

This 4-hole-front version is intended for control cabinets, panels, and operator desks. It includes Ethernet, RS-232, CAN, USB Host, and USB Device interfaces, and can operate as an HMI or, with the appropriate software/license, as an integrated HMI/PLC device.

MC2-442-57CQB-1-2A

MC2-442-57CQB-1-2A

MC2-442-57CQB-1-2A

MC2-442-57CQB-1-2A

Troubleshooting Quick Reference

Symptom Possible Cause Relevance to this Part Quick Check Method Recommendation
Panel completely dead Missing 24 VDC, failed SELV power supply, blown internal fuse, or wiring fault ✅ High Measure 24 VDC at the power connector; verify 0 V and functional-earth connections Check the external 24 VDC supply and wiring before replacing the panel
SUPPLY OK LED off Internal voltage fault or inadequate input supply ✅ High Confirm input voltage and inspect the rear/service-side LEDs If input power is correct but SUPPLY OK remains off, arrange panel repair or replacement
Panel boots but touch does not work Contaminated IR frame, touch calibration issue, or touch electronics fault ✅ High Check TOUCH ACT and TOUCH ERROR LEDs; clean the IR frame with a soft, dry cloth Clean the IR frame first; recalibrate if required, then replace the panel if the fault remains
TOUCH ERROR LED flashes Dirty infrared frame or incorrect touch calibration ✅ High Inspect the bezel and IR frame for dust, film, moisture, or obstruction Clean the IR frame; recalibrate the touch sensor if cleaning does not clear the fault
No Ethernet communication Wrong IP address, cable fault, subnet mismatch, or switch/port issue ❌ Medium Check link LEDs and ping the panel from a PC on the same subnet Verify IP configuration and Ethernet cable before replacing the HMI
CAN communication failure Wiring, termination, baud-rate mismatch, or GND potential difference ✅ Medium Inspect CAN wiring, termination, baud rate, and CAN ACT LED activity Correct bus wiring and configuration; connect GND terminals of all bus stations
CF card errors or project will not load Damaged/incorrect CompactFlash, corrupted project, or card removed during write ✅ High Check CF ACT LED and verify the CF card/project on a known-good system Never remove the CF card while CF ACT is lit; restore the project from a verified backup
Display dark or distorted Backlight/LCD aging, power issue, or internal display fault ✅ High Confirm stable 24 VDC input and observe boot behavior If power is stable but display remains faulty, panel replacement or component-level repair is required
Condensation present Temperature/humidity change caused moisture inside or on the panel ✅ High Inspect for visible moisture before applying power Do not power a condensation-affected unit; allow it to reach room temperature first

❗ Do not use this panel for safety functions. Eaton specifically prohibits using the MICRO PANEL to implement personnel- or machinery-protection safety functions.

If the panel still will not start or communicate, send photos of the nameplate, rear connectors, LED status, and CompactFlash/project details before ordering a replacement.

 

Frequently Asked Questions

Is the MC2-442-57CQB-1-2A the same as an XV-442-57CQB-1-2A?
Functionally, yes. Eaton states that XV400 5.7 in and MC2 5.7 in are two names for equivalent products; this MC2 version corresponds to the XV-442-57CQB-1-2x 4-hole-front infrared-touch configuration.

What type of touchscreen does it use?
It uses an infrared touch matrix, not a resistive touchscreen. It detects a finger or suitable object of at least 7 mm diameter interrupting the infrared light matrix.

What display resolution does it have?
The 5.7 in CSTN color LCD provides 320 x 240 pixel QVGA resolution, with a visible area of 115 x 86 mm.

What power supply does it require?
It requires 24 VDC from an AC/DC converter with safe isolation (SELV). The panel includes an internal fuse and reverse-polarity protection.

Can it run PLC logic locally?
Yes. Eaton describes the MICRO PANEL as usable either as an HMI or as an integrated HMI/PLC device, subject to the installed operating system, software, and licensing.

Can I remove the CompactFlash card while it is running?
No. Remove the CF card only after the panel is de-energized and the CF ACT LED is off. A power failure or card removal during a write operation can cause data loss or damage the card.

Why is this panel cheaper than a new Eaton HMI?
It is an obsolete legacy MICRO PANEL, so available units are typically refurbished or surplus stock rather than newly manufactured panels. The lower price reflects limited availability and legacy-market sourcing; verify the test scope, warranty, CF-card contents, and project compatibility before purchase.