Description
3. Key Technical Specifications
- LocalBus Power Rating: +5 VDC at 1.4 A maximum
- Ambient Temperature: –40 to 70 °C
- Shock: 10 G ½-sinewave for 11 ms
- Vibration: 1 mm peak-to-peak (5–16 Hz); 0.5 g (16–150 Hz)
- Relative Humidity: 5 % to 95 % non-condensing
- Airborne Contaminants: ISA-S71.04-1985 Class G3
- Weight: Approx. 0.35–0.75 kg (varies by packaging)
- Communication: DeltaV Control Network (Ethernet-based)
- Redundancy Support: Yes (primary/backup configurations)
- Control Execution: Supports continuous and batch strategies
- Memory: Expanded capacity relative to standard MD controllers for large batch and memory-intensive applications
4. Product Introduction
The Emerson KJ2003X1-BB1 (also ordered as VE3006 or 12P3439X012) is an MD Plus Controller module for the DeltaV distributed control system. It executes control strategies, manages communication between field I/O and other network nodes, and provides the additional memory needed for large batch processes or complex control applications.
Plant engineers select the KJ2003X1-BB1 when replacing a failed MD Plus controller or expanding an existing DeltaV node. It retains full compatibility with earlier DeltaV configurations and supports redundant operation, making it a direct form-fit replacement that keeps existing control strategies intact.

KJ2003X1-BB1

KJ2003X1-BB1
5. Troubleshooting Quick Reference
| Symptom | Possible Cause | Relevance to this Part | Quick Check Method | Recommendation |
|---|---|---|---|---|
| No power LED / module not recognized | Missing or low +5 V LocalBus supply | ✅ High | Measure 5 VDC at the carrier backplane; confirm current capacity ≥1.4 A | Restore proper LocalBus power before replacing the controller |
| Status LED red or continuous fault | Hardware fault or corrupted configuration | ✅ High | Note exact LED pattern; attempt controlled restart from DeltaV Explorer | If fault persists after confirmed good power and carrier, replace the module |
| Loss of communication with I/O or network | Network cable or switch issue; controller not online | ✅ Medium | Verify Ethernet link lights and control-network connectivity; check other nodes | Isolate whether the problem is local to this controller or system-wide |
| Configuration will not download | Memory or firmware mismatch | ✅ Medium | Confirm controller type and firmware version match the downloaded database | Match firmware revision to the existing system or request specific revision |
| Redundant pair fails to switch | Partner controller offline or configuration mismatch | ✅ High | Check status of both primary and backup controllers in DeltaV Diagnostics | Verify both units are the same hardware revision and configuration is synchronized |
| Intermittent freezes under load | Over-temperature or excessive memory demand | ✅ Medium | Monitor ambient temperature and controller CPU/memory usage | Ensure cooling and that the application stays within MD Plus capacity |
If diagnostics remain inconclusive, capture DeltaV diagnostic logs, LED status photos, and the exact part number/revision from the nameplate before contacting support.
6. Frequently Asked Questions (FAQ)
Q: Is the KJ2003X1-BB1 the same as VE3006?
A: Yes. VE3006 is the common catalog designation for the same MD Plus Controller hardware. Cross-references also include 12P3439X012 and 12P3439X032.
Q: Can I hot-swap the KJ2003X1-BB1?
A: In a redundant pair the backup can take over, but the physical module itself should be replaced only after the node is properly switched or powered down according to Emerson procedures. Do not pull a simplex controller under power.
Q: Does it support redundancy?
A: Yes. The MD Plus Controller is designed for 1:1 primary/backup operation on the DeltaV control network.
Q: Will my existing control strategies work after replacement?
A: Control strategies and configurations created on earlier DeltaV systems are compatible. After physical replacement you will need to download the existing database to the new controller.
Q: What power does the module require?
A: It draws its power from the DeltaV carrier LocalBus at +5 VDC, rated 1.4 A maximum. Confirm the carrier and system power supply can deliver this current.
Q: Why is surplus pricing lower than a new factory quote?
A: These units are new surplus or carefully tested stock that meet original Emerson specifications. They carry a standard warranty but may not include the latest factory packaging or current-production firmware.
Q: How do I confirm the exact revision before ordering?
A: Check the nameplate for the full part number (including any trailing revision letters) and, if possible, the firmware version reported in DeltaV Diagnostics. Matching revision reduces configuration risk.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626