Description
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Emerson Automation Solutions |
| Model | KJ2201X1-HA1 |
| Ordering number | 12P3322X022 |
| System | DeltaV SIS |
| Product type | SLS Terminal Block |
| Compatible logic solver | SLS 1508 |
| Configuration | Simplex |
| Maximum input voltage | 30 VDC |
| A-B circuit current | 30 mA/channel maximum |
| A-C circuit current | 1 A/channel maximum |
| Ambient temperature | -40°C to +70°C |
| Relative humidity | 5–95% non-condensing |
| Shock | 10 g, half-sine, 11 ms |
| Vibration | 1 mm peak-to-peak, 2–13.2 Hz; 0.7 g, 13.2–150 Hz |
| Airborne contaminants | ISA-S71.04-1985 Class G3 |
| Hazardous-area certification | II 3G Ex ec IIC Gc; Class I Div. 2; Zone 2 |
| User serviceability | None |
| Calibration | Not required |
| Energized removal/insertion | Not permitted |
The Emerson ATEX instruction sheet specifically identifies the KJ2201X1-HA1 as an SLS Terminal Block and specifies the 30 VDC maximum input, channel-current limits, environmental ratings, and hazardous-area approvals.
Product Introduction
The Emerson KJ2201X1-HA1 is an SLS terminal block used in the DeltaV SIS safety-system architecture with the SLS 1508 logic solver. Its function is to provide the terminal interface for field circuits associated with the safety system rather than perform the logic-solving function itself. The commonly associated ordering number is 12P3322X022.
The HA1 designation is important when selecting a replacement. Available technical references identify KJ2201X1-HA1 as the simplex SLS terminal block, while KJ2201X1-JA1 is identified separately as the redundant version. The two should not be treated as interchangeable without checking the installed DeltaV SIS architecture and wiring documentation.

KJ2201X1-HA1

KJ2201X1-HA1
Installation & Configuration Guide
Stage 1 — Pre-Installation
- Verify the complete part number KJ2201X1-HA1 on the existing terminal block.
- Confirm the associated ordering number, commonly 12P3322X022.
- Verify that the application uses an SLS 1508 safety logic solver.
- Confirm that the existing installation requires the simplex HA1 terminal configuration.
- Compare the terminal assignments against the approved DeltaV SIS wiring drawings.
- Verify the applicable hazardous-area classification and installation requirements.
- Isolate system power and field power before beginning replacement.
- Record the existing field wiring before disconnecting any terminals.
Stage 2 — Removal
- Place the safety system in the approved maintenance state according to site procedures.
- Remove the applicable field power.
- Verify that the terminal block is de-energized.
- Label or document all field connections before disconnecting them.
- Disconnect the field wiring using the approved maintenance procedure.
- Remove the KJ2201X1-HA1 from its installed carrier/interface.
- Inspect the mating connections and surrounding wiring for damage or contamination.
Safety warning: Emerson’s instruction sheet explicitly states that this unit cannot be removed or inserted with system power energized. Hazardous-area installation must also follow the applicable DeltaV SIS Zone 2 installation instructions.
Stage 3 — Installation
- Verify the replacement part number and hardware identification.
- Confirm that the replacement is the HA1 simplex version rather than the JA1 redundant version.
- Inspect the terminal interface before installation.
- Install the in the correct DeltaV SIS position.
- Reconnect field wiring according to the approved SIS drawings.
- Verify terminal-to-terminal wiring before applying power.
- Check conductor routing, shielding, grounding, and hazardous-area requirements.
- Confirm that field-circuit voltage and current remain within the documented limits.
Stage 4 — Power-On and Testing
- Restore power according to the approved SIS commissioning procedure.
- Check for wiring-related diagnostics.
- Verify the SLS 1508 logic solver recognizes the expected terminal configuration.
- Confirm field signals at the safety-system interface.
- Test applicable safety inputs and outputs using the plant’s approved proof-test procedure.
- Verify alarm, trip, interlock, and diagnostic functions as required.
- Document the replacement and test results in the SIS maintenance record.
FAQ
What is the Emerson ?
It is an SLS Terminal Block used with the Emerson DeltaV SIS SLS 1508 safety logic solver. It provides the physical field-terminal interface; it is not the SLS logic solver itself.
What is the ordering number for ?
The commonly associated ordering number is 12P3322X022. For replacement procurement, match both the KJ model designation and the complete ordering/nameplate information.
Is simplex or redundant?
is identified as the simplex SLS terminal block. KJ2201X1-JA1 is separately identified as the redundant SLS terminal block. Verify the installed system architecture before substitution.
What is the maximum voltage rating?
The Emerson instruction sheet specifies 30 VDC as the input-power limit. Maximum current is 30 mA per channel between A-B terminals and 1 A per channel between A-C terminals.
What is the operating temperature range?
The specified ambient temperature range is -40°C to +70°C. Relative humidity is specified at 5–95% non-condensing.
Can be removed while energized?
No. The Emerson instruction sheet explicitly states that the unit cannot be removed or inserted with system power energized. Follow the applicable DeltaV SIS hazardous-area installation procedure.
Does the require calibration?
No. The Emerson instruction sheet states that the unit contains no user-serviceable parts and that calibration is not required.
Is suitable for hazardous locations?
Yes, the Emerson instruction sheet lists hazardous-area approvals including II 3G Ex ec IIC Gc and Class I Division 2 / Class I Zone 2 AEx/Ex ec IIC T4 Gc. The actual installation must comply with the applicable area classification and Emerson installation instructions.
What should be checked before ordering a replacement?
Verify:
- complete model number
- 12P3322X022 ordering number where applicable
- SLS 1508 compatibility
- Simplex versus redundant system architecture
- Terminal assignments
- Hardware/nameplate information
- Hazardous-area installation requirements
- Existing SIS wiring drawings
Do not substitute the JA1 redundant terminal block solely because it has the same basic SLS function.