Description
Key Technical Specifications
| Parameter | Specification / Value |
| Manufacturer | Emerson Process Management |
| Part Number / System ID | KJ2201X1-JA1 |
| Alternative Model Code | VE4035S2B1 / Assembly 12P3159X012 |
| System Compatibility | Emerson DeltaV Distributed Control System |
| Channel Capacity | 8 field I/O wiring termination points |
| Terminal Type | Screw terminal connections with integrated fuse holders |
| Backplane Interconnect | Plugs directly into DeltaV 8-slot local bus carrier |
| Field Voltage Isolation | 500 VAC channel-to-bus galvanic isolation |
| Fuse Protection | Individual channel power fusing (standard fast-acting fuse rating) |
| Operating Temperature | −40°C to +70°C (−40°F to +158°F) |
| Storage Temperature | −40°C to +85°C (−40°F to +185°F) |
| Relative Humidity | 5% to 95% non-condensing |
Product Introduction & Supply Chain Strategy
The Emerson DeltaV KJ2201X1-JA1 (VE4035S2B1) is an 8-channel fused I/O terminal block base engineered for the DeltaV I/O subsystem. It mounts directly onto a local bus carrier (such as the KJ1710X1-BA1), providing secure field wiring termination points, fused power distribution, and signal routing for analog and discrete I/O cards. Built for industrial environments, it features heavy-duty terminal connections that protect backplane electronics against field wiring surges.
Maintaining the KJ2201X1-JA1 as New Surplus protects plant operations against unexpected loop outages caused by shorted field wiring, stripped terminal screws, or severe electrical faults. Sourcing factory-fresh surplus guarantees pristine copper contact pins, unblemished screw terminals, and original insulation resistance—delivering full OEM reliability without factory lead times or high expediting costs.

KJ2201X1-JA1

KJ2201X1-JA1
Installation & Configuration Guide
1.Pre-Installation Preparation:Prerequisite & Safety Setup.
Isolate the 24 VDC field power feeds supplying the target I/O channel segment using proper lock-out/tag-out (LOTO) protocols. Wear a grounded ESD wrist strap before handling the terminal block base. Inspect the carrier backplane socket for dust, debris, or bent pins prior to mounting.
2.Removing an Existing Terminal Block:Hardware Disconnection.
Unplug the corresponding I/O module from the carrier slot above the terminal block. Disconnect field wiring leads from the screw terminals, noting wire numbers and polarity. Release the upper and lower locking tabs on the terminal block base and pull it straight off the carrier socket.
3.Mounting and Field Wire Connection:Base Mounting & Wiring.
Align the rear pin header of the new KJ2201X1-JA1 base with the designated slot on the local bus carrier. Press the terminal block firmly into the carrier until the locking tabs snap into place. Connect field instrument wires to the corresponding screw terminals according to your loop wiring drawing, tightening screws to the recommended torque specification.
4.Fuse Inspection, Module Re-insertion, and Testing:Loop Validation.
Inspect all channel fuses to ensure proper rating and continuity. Re-insert the I/O module into the slot above the base. Re-apply field power and verify that channel status LEDs illuminate green. Open the DeltaV Diagnostics application to confirm signal integrity and loop communication across all 8 channels.
Firmware/Software Versions & Upgrade Notes
- Hardware Compatibility: Fully compatible with standard Emerson DeltaV S-Series and M-Series I/O modules requiring fused terminal block bases on 8-slot local bus carriers.
- Passive Hardware Assembly: The KJ2201X1-JA1 operates as a passive termination base assembly. It contains no microcontrollers, memory chips, or firmware, requiring no software downloads or flashing during a hardware swap.
- Fuse Selection Precautions: Always verify that replacement fuses match the current rating specified for your connected field transmitter loops. Installing incorrect fuse ratings can leave field cards vulnerable to overcurrent damage or cause false channel open-circuit faults.
Frequently Asked Questions (FAQ)
Why is New Surplus preferred over refurbished DeltaV terminal bases?
Refurbished terminal bases frequently suffer from stripped screw threads, micro-fractured pin headers, and degraded internal fuse holder contacts caused by repeated field wiring changes and thermal stress. A bad contact on a terminal base can cause erratic analog signal drift or intermittent signal dropouts. Our New Surplus KJ2201X1-JA1 bases are uninstalled, factory-fresh original units that ensure pristine contact resistance and long-term operating life.
How do you verify that this terminal base is authentic and unused?
Every unit passes a thorough inbound quality inspection. We verify original Emerson packaging, inspect backplane contact pins for zero insertion wear, check screw terminals for flawless condition, and verify internal trace continuity. A complete QC verification report is included with every shipment.
Can I replace a terminal base while the field instrument loop is active?
No. Replacing a terminal base requires disconnecting field wiring and field power. Attempting to swap a base under load can cause short circuits, trip connected safety interlocks, or damage the mating I/O card. Always power down field power and remove the I/O module before replacing the base.
Does the include the plug-in I/O card or fuses?
Part number (VE4035S2B1) specifies the standalone 8-channel fused terminal block base assembly. Plug-in I/O modules are modular components sold separately based on your loop engineering requirements. Standard channel fuses are pre-installed or included as specified on the unit card.
What warranty coverage comes with this New Surplus unit?
We support this New Surplus Emerson DeltaV terminal base with a full 1-year functional replacement warranty. If any operational defect or hardware failure occurs under standard operating conditions within 12 months, we provide an immediate direct replacement or full refund to safeguard your plant maintenance budget.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626