Sale!

Emerson KJ3003X1-EA1 DeltaV Serial Interface Terminal Block

  • Model: KJ3003X1-EA1 (12P0921X042)
  • Brand: Emerson
  • Series: DeltaV™ Electronic Marshalling (CHARMs)
  • Core Function: Serial communications interface terminal block
  • Product Type: Interface Terminal Block
  • Key Specs: 35 VDC @ 1 A input rating; −40 to +70 °C ambient; ISA-S71.04 G3 contaminants
  • Condition: New Original / New Surplus — factory packaging varies by lot
  • Availability: In stock — ships in 3–5 working days (typical)
Categories: , , , , SKU: KJ3003X1-EA1 Brand:

Description

Key Technical Specifications

  • Part Number: KJ3003X1-EA1 (alternate 12P0921X042)
  • Product Type: Serial Interface Terminal Block for DeltaV CHARMs
  • Input Power Rating: 35 VDC @ 1 A
  • Ambient Temperature Range: −40 °C to +70 °C
  • Relative Humidity: 5 to 95% non-condensing
  • Airborne Contaminants: ISA-S71.04–1985 Class G3
  • Shock: 10 g half-sine wave for 11 ms
  • Vibration: 1 mm p-p (2–13.2 Hz); 0.7 g (13.2–150 Hz)
  • Hazardous Area Ratings: II 3G Ex ec IIC Gc; CL I Div 2 GP A,B,C,D; CL I Zone 2 AEx/Ex ec IIC T4 Gc
  • Approvals: FM18ATEX0076U, IECEx FMG 18.0030U, FM21UKEX0199U, FM18US0277U, FM19CA0005U
  • Removal/Insertion: Not hot-swappable — must de-energize system power before removal or insertion
  • Dimensions (typical): ~120 × 70 × 55 mm (varies by packaging/lot)
  • Weight: ~0.09 kg (net); ~1 kg shipping weight

 

Product Introduction

The Emerson KJ3003X1-EA1 is a DeltaV™ Electronic Marshalling (CHARMs) serial interface terminal block used to bring RS-232/RS-485 serial field devices into a DeltaV DCS. It provides the physical termination and power/signal interface for serial I/O cards (e.g., M-series serial interface assemblies) and is commonly deployed where Modbus RTU or similar serial protocols must be integrated into DeltaV.

This unit is chosen for its hazardous-area certifications, wide temperature rating (−40 to +70 °C), and compatibility with DeltaV CHARMs carriers and I/O architectures. In practice, it shows up in VE4006P2-style serial interface assemblies and similar M-series configurations where a dedicated serial channel is required.

KJ3003X1-EA1

KJ3003X1-EA1

KJ3003X1-EA1

KJ3003X1-EA1

Troubleshooting Quick Reference

Symptom Possible Cause Relevance to this Part Quick Check Method Recommendation
No comms to serial device (timeout/no response) Wrong wiring/polarity on terminal block; incorrect RS-232 vs RS-485 mode ✅ High Verify wiring against DeltaV manual; check A/B (or TX/RX) at terminals with a known-good serial tester Re-terminate per OEM diagram; confirm device baud/parity matches driver
Intermittent serial errors under vibration Loose terminals or poor strain relief ✅ Medium Visually inspect terminal screws; gently tug-test wires; check for cracked insulation Re-secure terminals; add cable clamps; verify DIN rail is solid
Device works on bench but fails in panel Ground loops / shielding issues on RS-485 run ✅ Medium Measure ground potential between device and panel; check shield termination (single-point) Re-terminate shield at one end only; add isolated repeater if needed
CHARMs carrier faults after module swap Module inserted with power on (backplane stress) ❌ Low (carrier/module issue) Check carrier status LEDs; review DeltaV diagnostics for slot faults Always power down before inserting/removing CHARMs or terminal blocks
Terminal block physically won’t seat Wrong carrier or misaligned keying ❌ Low Compare part number and keying to existing blocks; verify carrier type (CHARMs vs legacy) Use correct CHARMs carrier; do not force fit

If you’re stuck, pull a photo of the wiring, terminal block label, and the DeltaV diagnostic buffer, then contact support with those details.

 

Frequently Asked Questions (FAQ)

Q: Is the KJ3003X1-EA1 hot-swappable?
A: No. Emerson explicitly states this unit cannot be removed or inserted with system power energized. Power down the CHARMs carrier before swapping.

Q: What serial protocols does this support?
A: The terminal block itself is physical interface hardware; protocol support comes from the paired serial I/O card/driver (commonly Modbus RTU, Data Highway Plus, etc.).

Q: Is this new or refurbished?
A: We supply this as New Original / New Surplus unless otherwise noted. Factory packaging may vary by lot; traceability is maintained via OEM labels and packing docs.

Q: Can I use this with non-CHARMs DeltaV carriers?
A: No. This is designed for DeltaV Electronic Marshalling (CHARMs) architectures. Mixing with legacy S-Series or other carriers can cause mechanical/electrical mismatches.

Q: What’s the lead time?
A: Typical ship time is 3–5 working days from stock. If your project needs a specific date, tell us up front so we can stage it.

Q: What warranty do you offer?
A: 1-year warranty against DOA and functional defects. We’ll replace or refund if it fails under normal use within that period.

Q: Why is this cheaper than buying direct from Emerson?
A: This is surplus channel stock — genuine OEM hardware, but sourced via secondary distribution. It’s the same part number, often with original factory packaging and labels.