Description
Key Technical Specifications
| Parameter | Specification / Value |
| Part Number | KL2101X1-BA1 (Alternate P/N: 12P4987, SE6501T01) |
| System Architecture | Emerson DeltaV S-series CHARM I/O Subsystem |
| Capacity | Manages up to 96 Characterized I/O (CHARM) modules per CIOC pair |
| Input Power Nominal | 24 VDC ± 10% |
| Bus Power Consumption | 6.3 VDC at 3.25 A max (internal backplane) |
| Redundancy Support | Fully redundant pair configuration on CHARM carrier baseplate |
| Operating Temperature | −40 °C to +70 °C (−40 °F to +158 °F) |
| Storage Temperature | −40 °C to +85 °C (−40 °F to +185 °F) |
| Relative Humidity | 5% to 95% non-condensing |
| Hazardous Area Approvals | ATEX, IECEx Zone 2 (II 3G Ex ec IIC Gc), FM Class I, Div 2 |
| Isolation | Channel-to-bus galvanic isolation via baseplate and individual CHARM modules |
| Mounting Type | Direct insertion into CHARM I/O Carrier Baseplate (e.g., KL4201X1-BA1) |
Product Introduction & Supply Chain Strategy
The Emerson KL2101X1-BA1 CHARM I/O Card (CIOC) serves as the core communication bridge within the DeltaV Electronic Marshalling system. It processes digital signals, diagnostics, and field data from up to 96 individual CHARM modules, passing them seamlessly to the DeltaV control network over fault-tolerant Ethernet. Industrial facilities rely on the CIOC to eliminate traditional physical cross-marshalling cabinets, simplifying field wiring in chemical processing, refining, and pharmaceuticals.
Securing the KL2101X1-BA1 as New Surplus guarantees total operational reliability and lowest Total Cost of Ownership (TCO). In continuous DCS environments, buying a used or refurbished card introduces hidden risks like worn backplane contacts or heat-degraded capacitors. A failure on a primary CIOC drops an entire 96-channel field segment, driving unplanned downtime costs upward of $50,000 an hour. Keeping genuine New Surplus units on-site acts as essential buffer stock, securing instant replacement capabilities at a predictable capital cost.

KL2101X1-BA1

KL2101X1-BA1
Installation & Configuration Guide
Stage 1: Pre-Installation (Prep & Safety)
- Enforce Safety: Confirm the installation area complies with local electrical guidelines. Attach a grounded ESD wrist strap before handling the module.
- Document Existing Module: Prior to removal, record LED status colors (Power, Fault, Active) on the active unit. Verify that the replacement KL2101X1-BA1 matches the active firmware baseline.
- Inspect the Replacement: Remove the module from its anti-static bag and verify that backplane pin connections are straight, clean, and free of physical contamination.
Stage 2: Removal
- Unlatch Mechanism: Depress the top and bottom extraction latches on the target KL2101X1-BA1 card.
- Extract Cleanly: Pull the card straight out from the CHARM carrier slot using uniform, perpendicular force. Avoid twisting or rocking the card sideways to prevent bending backplane socket pins.
Stage 3: Installation (Clone & Seat)
- Align Guides: Align the card’s PCB edge guides with the carrier slot tracks.
- Seat the Module: Slide the card firm into the backplane connector until the retention latches engage with an audible click. Ensure both top and bottom latches are fully locked to maintain tight electrical continuity.
Stage 4: Power-On & Testing
- Verify Power: Confirm that the 24 VDC supply rail delivers steady voltage within specifications.
- Check Diagnostics: Monitor the card status LEDs upon power-up. The module must transition through self-test (flashing green) to solid green (Active/Standby).
- Confirm Verification: Check the DeltaV Diagnostics Explorer on the workstation; verify that all 96 connected CHARM channels communicate cleanly without backplane communication error flags.
Firmware/Software Versions & Upgrade Notes
- Recommended Baseline: Operate the KL2101X1-BA1 on DeltaV system software baseline v11.3.1, v12.3.1, or higher, matching the current controller firmware rev level.
- Compatibility Notes: Firmware on the CIOC must match the major release of the DeltaV System Controller (e.g., SX or SQ Controllers). Mismatches between the CIOC and the DeltaV database can trigger parameter download rejections or communication timeouts across the field bus.
- Hot-Swap & Downgrade Risk: While the CIOC supports live insertion in redundant baseplate configurations, flashing firmware during active plant operation is strongly discouraged. A power loss during an online firmware flash corrupts internal EEPROM memory, rendering the module unrecoverable. Perform all firmware updates off-process or during scheduled turnarounds.
Frequently Asked Questions (FAQ)
Q: Why buy a New Surplus Emerson KL2101X1-BA1 instead of a refurbished unit?
A: Refurbished I/O cards often carry hidden degradation from heat cycles and aging internal capacitors. Saving a small fraction upfront on a second-hand card exposes your DCS to sudden thermal faults and unannounced shutdowns. Our New Surplus units are 100% genuine OEM stock that have never been put into operational service, ensuring full factory design life and maximum reliability.
Q: How do I verify that the KL2101X1-BA1 I receive is truly unused?
A: Every unit undergoes a strict inbound quality control check. You will receive a module featuring untarnished gold/tin backplane pins, pristine OEM serial labels, zero solder rework marks, and protective anti-static packaging sealed after functional inspection.
Q: Can I hot-swap the KL2101X1-BA1 while the process is running?
A: Yes. If your DeltaV CHARM carrier is installed in a redundant configuration (dual CIOC cards), you can extract a faulted card and plug in the new KL2101X1-BA1 without removing power or interrupting control on the active card. The standby card automatically synchronizes its configuration from the active controller.
Q: Does the KL2101X1-BA1 require manual DIP switch or jumper configuration before installation?
A: No. The DeltaV Electronic Marshalling architecture auto-assigns node parameters. The CIOC receives its IP address, system binding, and channel configuration directly from the DeltaV Controller database upon insertion into the carrier.
Q: What warranty coverage applies to this module?
A: We provide a comprehensive 1-Year Comprehensive Warranty on all New Surplus Emerson components. If the module experiences an hardware issue under standard operating conditions within 12 months, we provide an immediate direct replacement or full repair service.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626