Description
Core Product Summary
The Emerson SE4001S2T2B1 is a DeltaV S-series Traditional I/O discrete input card assembly that provides eight channels of 24 V DC dry-contact input sensing together with a standard 8-channel terminal block. It is designed for use on S-series I/O carriers within Emerson DeltaV distributed control systems.
Each channel detects dry-contact or discrete-state field signals, supports pulse counting up to 75 Hz, and is optically isolated from the system. The card is known to operate with many NAMUR sensors when used with an appropriate field resistor pack for fault detection. Local-bus current draw is low, and field-circuit power is limited to 100 mA at 24 V DC per card.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Product type | Discrete Input Card (Dry Contact) |
| Model | SE4001S2T2B1 |
| Number of channels | 8 |
| Input type | 24 V DC dry contact |
| Detection level – On | > 2.2 mA |
| Detection level – Off | < 1 mA |
| Input impedance | Approximately 5 kΩ |
| Wetting voltage | 15 V |
| Configurable channel types | Discrete Input; Pulse Count |
| Pulse count frequency | < 75 Hz |
| Local bus current (12 V DC) | Simplex: 75 mA typ. / 100 mA max.; Redundant: 90 mA typ. / 150 mA max. |
| Field circuit power per card | 100 mA at 24 V DC (±10 %) |
| Isolation | Optical isolation per channel, factory tested to 1500 V DC |
| Terminal block | Standard 8-channel terminal block |
| Optional fuse | 2.0 A (terminal-block option) |
Engineering Selection Highlights
- Eight dry-contact channels with 15 V wetting voltage allow direct connection of unpowered switches, relay contacts, and many NAMUR sensors.
- Optical isolation of each channel from the system (tested to 1500 V DC) provides robust protection against field transients.
- Supports both discrete-input and pulse-count channel types, enabling simple counting applications up to 75 Hz without additional hardware.
- Standard 8-channel terminal block simplifies field wiring; a fused terminal-block variant (SE4001S2T2B2) is available when over-current protection is required.
- Low local-bus current consumption supports high channel density on S-series carriers.
- Compatible with field resistor packs for open-circuit / short-circuit fault detection when used with NAMUR-style sensors.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| System platform | Emerson DeltaV S-series | Traditional I/O subsystem |
| Carrier | S-series I/O interface carrier | Installs in any available I/O slot |
| Terminal block | Standard 8-channel terminal block (included in SE4001S2T2B1) | Keyed to accept only matching replacement cards |
| Redundant configuration | Supported via SE4031S2T2B1 assembly | Uses two DI cards with redundant terminal block |
| Field devices | Dry contacts, discrete sensors, many NAMUR sensors | Fault detection requires field resistor pack for NAMUR sensors |
| Power | Local bus 12 V DC; field circuit 24 V DC | Field power limited to 100 mA per card |
Dimensions, Mounting & Connection Notes
The SE4001S2T2B1 is a standard S-series I/O interface consisting of the discrete-input card and its matching 8-channel terminal block. It mounts on an S-series I/O interface carrier. The terminal block is keyed so that only a compatible card can be inserted after the terminal block is installed. Field wiring is connected to the screw terminals of the 8-channel terminal block. An optional fused terminal block (2.0 A) is available under the related model SE4001S2T2B2.
Detailed Product Overview
The Emerson SE4001S2T2B1 is an eight-channel discrete-input assembly for the DeltaV S-series Traditional I/O family. It combines a dry-contact input card with a standard 8-channel terminal block, providing a complete, keyed I/O interface that plugs directly into an S-series carrier.
Each of the eight channels supplies a 15 V wetting voltage and senses current to determine the open or closed state of a field contact. Detection thresholds are greater than 2.2 mA for the On state and less than 1 mA for the Off state. Input impedance is approximately 5 kΩ. Channels may be configured either as ordinary discrete inputs or as pulse-count inputs capable of tracking pulse trains up to 75 Hz.
Optical isolation between each field channel and the system (factory-tested to 1500 V DC) protects the controller from field-side transients. Local-bus current consumption remains modest (75 mA typical simplex), while field-circuit power is limited to 100 mA at 24 V DC for the entire card. When a field resistor pack is fitted, the card can detect open-circuit and short-circuit conditions on many NAMUR sensors, adding diagnostic capability without additional hardware.
Installation follows the standard S-series procedure: the terminal block is mounted on the carrier first and keyed; the card is then inserted and automatically sensed by the controller. A fused terminal-block version (SE4001S2T2B2) is available when individual channel fusing is required. For higher availability, a redundant pair can be ordered as SE4031S2T2B1.
The SE4001S2T2B1 is therefore a compact, reliable solution for acquiring dry-contact and discrete-state signals in DeltaV process control applications that require optical isolation, optional fault detection, and simple pulse counting.

SE4001S2T2B1

SE4001S2T2B1
Applications & System Role
The SE4001S2T2B1 functions as a discrete-input interface within DeltaV S-series Traditional I/O subsystems. It acquires binary field signals from dry contacts, limit switches, relay contacts, and compatible discrete sensors, and makes those signals available to control modules running in the DeltaV controller.
Channels can be configured for standard discrete input or for pulse counting of signals below 75 Hz. The card is typically used for status monitoring, interlock inputs, and simple totalizing applications in process plants. When installed with a field resistor pack it can also provide open-circuit and short-circuit diagnostics for many NAMUR sensors.
FAQ
What is the Emerson SE4001S2T2B1?
It is a DeltaV S-series Traditional I/O discrete input card assembly providing eight 24 V DC dry-contact channels with a standard 8-channel terminal block.
How many channels does it have and what signal type does it accept?
It has eight channels that accept dry-contact or discrete-state field signals and can also be configured for pulse counting up to 75 Hz.
What are the detection thresholds?
On is detected above 2.2 mA; Off is detected below 1 mA. Wetting voltage is 15 V.
Does the card provide channel isolation?
Yes. Each channel is optically isolated from the system and factory-tested to 1500 V DC.
Can it be used with NAMUR sensors?
Yes. It is known to operate with many NAMUR sensors; fault detection is available when a field resistor pack is used.
What terminal block is included?
The SE4001S2T2B1 includes the standard 8-channel terminal block. A fused version is available as SE4001S2T2B2.
Is redundant operation supported?
Yes. A redundant assembly is ordered as SE4031S2T2B1 (two DI cards with redundant terminal block).

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626