Sale!

Emerson SE4003S2B1 DeltaV S-Series 8-Channel HART Analog Input

Item Specification
Manufacturer / model Emerson SE4003S2B1
Product type Analog input I/O interface
System family Emerson DeltaV S-series Traditional I/O
Number of channels 8
Input signal 4–20 mA span; 2-wire and 4-wire
Full signal range 1 to 22.5 mA, with over-range checking
Transmitter power, 2-wire 13.5 V minimum at 20 mA; current limited at 29 mA maximum
Accuracy over temperature range 0.1% of span
Categories: , , , , SKU: SE4003S2B1 Brand:

Description

Core Product Summary

The Emerson SE4003S2B1 is a DeltaV S-series traditional I/O analog input interface with eight 4–20 mA HART channels. It combines the AI card with an AI 8-channel terminal block and accepts both 2-wire and 4-wire transmitters.

The module provides a 16-bit A/D converter, 0.1% of span accuracy across its temperature range, and optical isolation from the system factory tested to 1500 V DC. It supports HART pass-through for AMS Device Manager and HART variable and status reporting for control functions. The SE4003S2B1 installs in an S-series horizontal I/O carrier and is intended for use with DeltaV SQ or SX controllers.

 

Key Technical Specifications

Item Specification
Manufacturer / model Emerson SE4003S2B1
Product type Analog input I/O interface
System family Emerson DeltaV S-series Traditional I/O
Number of channels 8
Input signal 4–20 mA span; 2-wire and 4-wire
Full signal range 1 to 22.5 mA, with over-range checking
Transmitter power, 2-wire 13.5 V minimum at 20 mA; current limited at 29 mA maximum
Accuracy over temperature range 0.1% of span
Repeatability 0.05% of span
Resolution 16-bit A/D converter
Anti-aliasing roll-off -3 dB at 2.7 Hz; -20.5 dB at half the sampling frequency
Calibration None required
Local bus current, simplex 120 mA typical; 150 mA maximum at 12 V DC nominal
Local bus current, redundant 175 mA typical; 250 mA maximum per card at 12 V DC nominal
Field circuit power 300 mA maximum at 24 V DC ± 10%
Isolation Each channel optically isolated from the system; factory tested to 1500 V DC
Optional fuse 2.0 A, available on the fused terminal-block option
HART support HART pass-through for AMS Device Manager; HART variables and status for control functions
HART scan time 600–800 ms typical per enabled channel
Operating temperature -40 to 70 °C
Storage temperature -40 to 85 °C
Relative humidity 5 to 95%, non-condensing
Protection rating IP20
Contaminant rating ISA-S71.04-1985 Class G3 conformal coating
Terminal block AI 8-channel terminal block; supports 2-wire and 4-wire devices
Card keying A1

 

Detailed Product Overview

The Emerson SE4003S2B1 provides eight isolated analog input channels for DeltaV S-series control systems. It is configured as an AI card and AI 8-channel terminal block, making it suitable for 2-wire loop-powered transmitters and 4-wire transmitters with 4–20 mA outputs.

The card measures the full 1 to 22.5 mA signal range and checks for over-range conditions. Its 16-bit converter, 0.1% span accuracy, and 0.05% repeatability support process-variable acquisition without routine field calibration. For 2-wire transmitters, the card supplies loop power with a minimum of 13.5 V at 20 mA and limits output current to 29 mA maximum.

Each channel is optically isolated from the system and factory tested to 1500 V DC. The card supports HART communication through pass-through to AMS Device Manager and can report HART variables and status to DeltaV control functions. HART scanning is typically 600 to 800 ms per enabled channel.

The SE4003S2B1 is part of the S-series traditional I/O architecture. It plugs into an S-series horizontal carrier, where field power distribution and terminal-block wiring are handled by the carrier. The terminal block remains in place when the card is removed, allowing the I/O card to be replaced without disconnecting field wiring. The card’s A1 keying prevents installation into a terminal block intended for a different I/O type.

For critical field circuits, the same AI card can be installed in a redundant configuration on the AI 8-channel redundant terminal block. The controller recognizes the pair as redundant, scans both cards, and switches automatically to the standby card when a qualifying fault is detected.

 SE4003S2B1

SE4003S2B1

 SE4003S2B1

SE4003S2B1

Dimensions, Mounting & Connection Notes

The SE4003S2B1 plugs into an S-series horizontal I/O interface carrier. The carrier snaps onto a T-DIN rail, and the I/O card snaps into its I/O slot without tools. Field wiring terminates on the AI 8-channel terminal block, which connects to the carrier rather than directly to the removable I/O card.

The I/O interface is keyed with position A1. The terminal block’s keying mechanism uses two rotating keying posts, each with positions A–F and 1–6, to prevent installation of an incompatible card type.

The card includes power and internal-error indicators, and eight-channel cards include visible channel-status LEDs. The S-series carrier provides individually fused 24 V DC bussed field power to odd- and even-numbered slots through separate primary and secondary power sections.

The module is rated IP20 and uses ISA Class G3 conformal coating. It operates from -40 to 70 °C, stores from -40 to 85 °C, and tolerates 5 to 95% non-condensing relative humidity. It is rated for 10 g half-sine shock for 11 ms and vibration of 1 mm peak-to-peak from 5 to 13.2 Hz or 0.7 g from 13.2 to 150 Hz.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Control system Emerson DeltaV DCS Part of the DeltaV S-series Traditional I/O subsystem
Controller DeltaV SQ or SX controller Required for S-series traditional I/O
Carrier S-series horizontal I/O carrier S-series traditional I/O does not install on vertical carriers
Terminal block AI 8-channel terminal block Included in the SE4003S2B1 configuration; supports 2-wire and 4-wire devices
Alternative terminal blocks Fused 8-channel, 8-channel, 16-pin Mass, or 24-pin Mass terminal block Compatible terminal-block options for the same AI card type
Redundant option AI 8-channel redundant terminal block Uses two AI cards as a 1:1 redundant pair
Field signals 4–20 mA, 2-wire or 4-wire Full signal range is 1 to 22.5 mA
Field power 24 V DC ± 10%, 300 mA maximum per card Used for field circuit power
HART software AMS Device Manager for HART pass-through HART variables and status can also be used by control functions
DeltaV software v11.3.1 or later for S-series and M-series controllers on the same network The SE4003S2B1 is not a Plus card, so the v13.3 Plus-card requirement does not apply
Physical compatibility S-series horizontal carrier only Not physically compatible with M-series horizontal controller carriers

 

FAQ

What is the Emerson SE4003S2B1?
It is an Emerson DeltaV S-series analog input interface with eight 4–20 mA HART channels and an AI 8-channel terminal block.

What types of transmitters can it accept?
It accepts 2-wire and 4-wire transmitters with 4–20 mA signals. Its full signal range is 1 to 22.5 mA.

Does the SE4003S2B1 provide transmitter power?
Yes. For 2-wire transmitters, it provides a minimum of 13.5 V at 20 mA and limits current to 29 mA maximum.

Which DeltaV controllers are required?
The S-series traditional I/O subsystem requires DeltaV SQ or SX controllers and S-series horizontal carriers.

Does it support HART communication?
Yes. It provides HART pass-through for AMS Device Manager and supports HART variable and status reporting for control functions.

Can the SE4003S2B1 be redundant?
Yes. The same AI card can be used in a redundant configuration when installed with another AI card on an AI 8-channel redundant terminal block.

What isolation does it provide?
Each channel is optically isolated from the system and factory tested to 1500 V DC.

What environmental rating does it have?
It is rated IP20, uses ISA Class G3 conformal coating, operates from -40 to 70 °C, and tolerates 5 to 95% non-condensing relative humidity.

 

Documented Performance Data

Metric Value / Range Test / Operating Condition
Accuracy 0.1% of span Over the card’s temperature range
Repeatability 0.05% of span AI card, 8-channel, 4–20 mA HART
Resolution 16-bit A/D converter AI card, 8-channel, 4–20 mA HART
HART scan time 600–800 ms typical Per enabled channel
Field circuit power 300 mA maximum 24 V DC ± 10%
Redundant switchover Within two scans of the I/O bus Traditional I/O card redundancy
Analog-output overlap during switchover Less than 5 ms Applies to analog output cards; not applicable to the SE4003S2B1 input card