Description
Core Product Summary (Brand / Model / Key Attributes)
The Emerson SE4601T08 is a CHARMs Baseplate Assembly with Relay Output designed for the Emerson DeltaV Electronic Marshalling architecture. This DIN-rail mountable hardware assembly includes a 12-slot CHARMs Baseplate, a CHARM Address Terminal Block with screw terminals, twelve Relay Output CHARM Terminal Blocks, and a dedicated Baseplate Identifier.
Engineered to streamline field wiring and control cabinet layout, the assembly routes redundant power and dual RS-485 communication lines to up to twelve individual Characterized Modules (CHARMs). The included relay output terminal blocks feature three screw cage terminals per channel, supporting isolated switching connections rated up to 5 A at 28.8 VDC or 250 VAC. The assembly operates across a wide industrial temperature range and complies with ISA G3 severe environmental standards.
Key Technical Specifications
| Specification | Value / Detail |
| Product Type | CHARMs Baseplate Assembly with Relay Output |
| Control System Series | Emerson DeltaV S-Series / Electronic Marshalling |
| Subsystem Capacity | Holds up to 12 CHARMs and 12 Terminal Blocks |
| Included Baseplate Components | CHARM Baseplate, Address Terminal Block, 12 Relay Output Terminal Blocks, Baseplate Identifier |
| Terminal Block Type | 3 Screw Cage Terminals per channel |
| Wire Size Capacity | 0.32 mm² to 2.5 mm² (22 AWG to 14 AWG) |
| Wire Strip Length | 7 mm to 9 mm (0.28 in to 0.36 in) |
| Maximum Relay Rating | 5 A at 28.8 VDC / 0.4 A at 48 VDC / 0.2 A at 110 VDC / 5 A at 250 VAC |
| Operating Temperature | -40 °C to +70 °C (-40 °F to +158 °F) |
| Relative Humidity | 5% to 95%, non-condensing |
| Environmental Protection | IP20, NEMA 12; ISA-S71.04 Class G3 conformal coating |
| Vibration / Shock | 1 mm P-P (2–13.2 Hz), 0.7 g (13.2–150 Hz) / 10 g ½-sine wave (11 ms) |
Detailed Product Overview
The Emerson SE4601T08 forms a structural and electrical foundation for Emerson’s Electronic Marshalling technology within DeltaV distributed control systems (DCS). By eliminating traditional cross-wiring and multi-tier terminal strip marshalling cabinets, this baseplate allows individual field signals to connect directly to single-channel CHARM modules. Interleaving power and internal bus connectors allow multiple baseplates to join together on a single DIN rail, extending communication and power lines across a continuous I/O group.
Designed specifically for higher-power discrete output switching, the SE4601T08 comes equipped with relay output terminal blocks. Each block provides three screw cage terminals per channel, allowing field-side wiring for Normally Open (NO) and Normally Closed (NC) relay contact setups. The baseplate architecture incorporates mechanical keying posts that lock into terminal blocks upon initial CHARM insertion, ensuring that replacement modules match the established channel configuration and preventing improper hardware insertion during maintenance.

SE4601T08

SE4601T08
Engineering Selection Highlights
- 12-Channel Electronic Marshalling Base: Integrates twelve individual CHARM slots into a single DIN-rail assembly, reducing cabinet footprint and eliminating traditional cross-wiring.
- Dedicated Relay Output Terminals: Includes specialized 3-wire relay output terminal blocks designed to handle high-current switching signals up to 5 A.
- Interleaving Power and Communication Bus: Features built-in side connectors that link power and dual RS-485 communication buses across adjoining baseplates without external jumper wiring.
- Mechanical Hardware Keying: Prevents cross-insertion of incorrect CHARM types by setting physical keying positions when a module is first installed on a terminal block.
- Conformal-Coated Reliability: Conforms to ISA-S71.04 Class G3 airborne contaminant specifications, enabling deployment in harsh, chemically aggressive plant environments.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| System Platform | Emerson DeltaV DCS Electronic Marshalling | Requires DeltaV CHARM I/O Carrier (CIOC) for host system control |
| Compatible Modules | Relay Output CHARMs & standard CHARM types | Accommodates up to 12 individual CHARM signal conditioning modules |
| Bus Interconnect | DeltaV Baseplate Extenders / Extender Cables | Connects to adjacent baseplates or adjacent cabinet columns via approved extender cables |
| Mounting Surface | Standard T-type DIN rail | Clips onto DIN rail; top and bottom shield drain terminals accept shield grounding wires |
Dimensions, Mounting & Connection Notes
- Mounting: Snaps directly onto standard T-type DIN rails inside protective electrical enclosures or control cabinets.
- Field Wiring Terminals: Accepts wire gauges from 0.32 mm² to 2.5 mm² (22 to 14 AWG) with a recommended strip length of 7 mm to 9 mm.
- Relay Terminal Contacts: Each channel’s terminal block supplies 3 screw cage connections, accommodating isolated high-current load wiring.
- Shield Grounding: Top and bottom shield drain wire connections accept 2 screw cage terminals for continuous signal cable shielding.
FAQ
What is included in the Emerson SE4601T08 assembly?
The SE4601T08 package includes a 12-slot CHARMs Baseplate, a CHARM Address Terminal Block, twelve Relay Output CHARM Terminal Blocks, and a Baseplate Identifier.
What is the primary function of the SE4601T08?
It serves as a modular 12-channel fieldbus baseplate within DeltaV Electronic Marshalling systems, providing structural mounting, power/bus distribution, and relay terminal connections for individual CHARM modules.
What are the electrical ratings for the relay output terminal connections?
The included relay output terminal blocks are rated for up to 5 A at 28.8 VDC, 0.4 A at 48 VDC, 0.2 A at 110 VDC, and 5 A at 250 VAC.
How does the baseplate prevent inserting the wrong module type?
Each terminal block position utilizes two rotatable keying posts that automatically set to match the inserted CHARM type, preventing incompatible modules from seating in that slot later.
Verification & Troubleshooting Notes
- Address & Termination: Ensure the CHARM Address Terminal Block is properly seated and configured so the host CHARM I/O Card (CIOC) recognizes the baseplate’s position on the bus.
- Terminal Keying Inspection: If a new CHARM module will not insert fully into a slot, check the mechanical keying posts on the terminal block to confirm they match the intended CHARM hardware type.
- Bus Continuity Check: When connecting multiple baseplates, verify that side-interleaving bus connectors are fully mated to maintain continuous power and RS-485 redundant communication paths across the assembly segment.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626