Sale!

Emerson SLS1508 SIL 3 Safety Logic Solver with HART I/O

The Emerson SLS1508 is the Smart Logic Solver for the DeltaV SIS process safety system. It combines dual CPUs and 16 configurable I/O channels in a single safety logic solver, providing the processing capability and field interface for Safety Instrumented Functions (SIFs).

Categories: , , , , SKU: SLS1508 Brand:

Description

Core Product Summary

The Emerson SLS1508 is the Smart Logic Solver for the DeltaV SIS process safety system. It combines dual CPUs and 16 configurable I/O channels in a single safety logic solver, providing the processing capability and field interface for Safety Instrumented Functions (SIFs).

Each SLS1508 channel can be configured as a discrete input, discrete output, HART analog input, or HART two-state output. The logic solver installs in the odd-numbered slots of an 8-wide carrier, communicates over the SISnet local peer bus, and can be installed as a redundant pair for increased process availability. It is rated suitable for SIL 3 applications and requires DeltaV v8.3 software or later.

 

Key Technical Specifications

Item Specification
Manufacturer / model Emerson SLS1508
Product type Smart Logic Solver
System family Emerson DeltaV SIS
CPUs Dual CPUs
I/O channels 16 configurable channels
Channel types Discrete input, discrete output, HART analog input, HART two-state output
Input power 24 V DC ± 20%, 1.0 A plus field power; 5.0 A total
Field power 4 A maximum; actual value depends on channel and field-device type
Redundant logic-solver power 2 A at 24 V DC plus digital-output field loads
Redundant logic-solver heat dissipation 24 W
Redundant logic-solver weight 1.20 kg
Isolation Each channel optically isolated from the system; factory tested to 1500 V DC; no channel-to-channel isolation
Carrier position SIS yellow terminal blocks in odd-numbered slots 1, 3, 5, and 7 of an 8-wide carrier
Redundant installation Four slots for a redundant pair
Event time-stamp resolution Less than 1 ms
Software prerequisite DeltaV v8.3 or later
Operating temperature -40 to 70 °C
Storage temperature -40 to 85 °C
Relative humidity 5 to 95%, non-condensing
Contaminant rating ISA-S71.04-1985 Class G3 conformal coating
Protection rating IP20
Shock rating 10 g half-sine wave for 11 ms
Vibration rating 1 mm peak-to-peak from 5 to 16 Hz; 0.5 g from 16 to 150 Hz

 

Detailed Product Overview

The Emerson SLS1508 executes safety logic and interfaces directly with field devices in a DeltaV SIS architecture. Its dual CPUs and 16 integrated I/O channels allow each logic solver to perform both the logic-solving function and field-signal interface without requiring additional processors to expand the system.

The SLS1508 supports four configurable channel types: discrete input, discrete output, HART analog input, and HART two-state output. Analog-input channels accept a 4–20 mA nominal signal across a 1–24 mA full range, provide 2-wire transmitter power, and offer 16-bit resolution. HART communication supports diagnostics and condition monitoring of intelligent field devices.

Discrete-input channels are compatible with NAMUR sensors and dry contacts. With appropriate configuration and external resistors, dry-contact inputs can detect open-circuit and short-circuit field-wiring faults. Discrete-output channels provide field power minus 2 V at the output, support 0.5 A continuous per channel, and include short-circuit protection and optional pulse testing for open-loop detection.

The SLS1508 communicates with other logic solvers through the two-channel SISnet local peer bus. Local logic solvers are hosted by the same DeltaV controller, while remote logic solvers communicate through SISnet Repeaters over a fiber-optic remote peer ring. The SLS1508 is powered from a 24 V DC supply that is separate from the supply used by the DeltaV controller and standard I/O.

A redundant pair of SLS1508 logic solvers occupies four carrier slots and operates in parallel: both units read inputs, execute logic, and drive outputs. The system automatically recognizes the redundant pair and provides a bumpless transition to simplex operation if one logic solver fails. The failed unit de-energizes its outputs while the remaining unit continues to operate.

SLS1508

SLS1508

SLS1508

SLS1508

Dimensions, Mounting & Connection Notes

The SLS1508 installs in SIS yellow terminal blocks in odd-numbered slots—1, 3, 5, or 7—on an 8-wide DeltaV carrier. A redundant pair uses four slots. The redundant logic solver weighs 1.20 kg, dissipates 24 W, and consumes 2 A at 24 V DC plus digital-output field loads.

The logic solver requires a separate 24 V DC power supply. Input power is 24 V DC ± 20%, 1.0 A plus field power, with a total limit of 5.0 A. Field power is limited to 4 A, with the actual requirement depending on the configured channel types and connected field devices.

Each I/O channel is optically isolated from the system and factory tested to 1500 V DC. There is no channel-to-channel isolation. HART analog inputs provide 2-wire transmitter power of at least 15.0 V terminal-to-terminal at 20 mA and limit current to 24 mA maximum.

Discrete-output channels provide field power minus 2 V, support 0.5 A continuous per channel, and are limited to 4.0 A per card. Short-circuit protection limits output current to 2.0 A typical. Optional pulse testing applies a 24 V DC pulse for 1.0 ms every 50 ms and can be disabled for field devices that cannot support it.

The module is rated IP20 and uses ISA Class G3 conformal coating. It operates from -40 to 70 °C, stores from -40 to 85 °C, and tolerates 5 to 95% non-condensing relative humidity.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Safety system Emerson DeltaV SIS SLS1508 is the Smart Logic Solver for DeltaV SIS
Software DeltaV v8.3 or later Required for the SLS1508
Carrier 8-wide carrier SLS1508 and its termination block install on the 8-wide carrier
Carrier position Odd-numbered slots 1, 3, 5, and 7 SIS yellow terminal blocks are used
Redundancy Two SLS1508 units as a redundant pair A redundant pair occupies four carrier slots
Communication SISnet local peer bus Two-channel bus; must be terminated at both ends
Remote communication SISnet Repeaters and fiber-optic remote peer ring Used for logic solvers hosted by different DeltaV controllers
Local bus DeltaV Local Bus Connects DeltaV controllers and logic solvers
Power supply Separate 24 V DC supply Emerson recommends separate supplies for the SLS and DeltaV controller/I/O
Field devices HART transmitters, NAMUR sensors, dry contacts, and discrete loads Channel type is software configurable
Event recording DeltaV SIS Event Chronicle Events are time-stamped with less than 1 ms resolution
Higher-resolution SOE DeltaV Discrete Input Card for Sequence of Events Provides 0.25 ms event resolution when wired in parallel

 

FAQ

What is the Emerson SLS1508?
It is the Emerson DeltaV SIS Smart Logic Solver, combining dual CPUs and 16 configurable I/O channels for Safety Instrumented Functions.

What I/O types does the SLS1508 support?
Each of its 16 channels can be configured as a discrete input, discrete output, HART analog input, or HART two-state output.

Is the SLS1508 suitable for SIL 3 applications?
Yes. The SLS1508 is rated suitable for use in SIL 3 applications in simplex mode.

How is the SLS1508 installed?
It installs in SIS yellow terminal blocks in odd-numbered slots 1, 3, 5, or 7 on an 8-wide carrier.

How many slots does a redundant SLS1508 pair require?
A redundant pair occupies four slots on the 8-wide carrier.

What power supply does the SLS1508 require?
It requires a separate 24 V DC supply rated 24 V DC ± 20%, 1.0 A plus field power, with a total limit of 5.0 A.

What software is required?
DeltaV v8.3 software or later is required for the SLS1508.

How does the SLS1508 communicate with other logic solvers?
It communicates through the two-channel SISnet local peer bus. Remote logic solvers communicate through SISnet Repeaters over a fiber-optic remote peer ring.

 

Documented Performance Data

Metric Value / Range Test / Operating Condition
Event time-stamp resolution Less than 1 ms DeltaV SIS function-block execution
Analog-input resolution 16 bits HART analog-input channel
Analog-input accuracy 2.0% of span Safety / diagnostic accuracy
Analog-input filtering -3 dB at 5.68 Hz; -20.0 dB at 40 Hz 2-pole filter; 40 Hz is half the sample rate
HART two-state output accuracy 5.0% of span Safety / diagnostic accuracy
HART two-state output resolution 12 bits HART two-state output channel
Discrete-output current 0.5 A continuous per channel; 4.0 A maximum per card Discrete-output channel
Discrete-output short-circuit protection 2.0 A typical Discrete-output channel
Higher-resolution event recording 0.25 ms DeltaV Discrete Input Card for Sequence of Events