Description
Core Product Summary
The Emerson VE4002S1T2B5 is a DeltaV discrete output card that provides 32 channels of 24 V DC high-side switching for field devices such as solenoid valves, interposing relays, and status indicators. It belongs to Emerson’s DeltaV traditional I/O architecture and is supplied with a standard I/O termination block for field wiring.
Each channel switches the positive leg of a 24 V DC field circuit and is optically isolated from the control system. The card draws its logic power from the DeltaV LocalBus and requires a compatible DeltaV I/O interface carrier, controller, and matching 32-channel DO termination block. Its high-density channel count makes it suitable when a controller cabinet must drive a large number of low-current discrete loads without adding separate interposing output hardware.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Emerson |
| Model / order number | VE4002S1T2B5 |
| Product type | Discrete output (DO) card |
| Control system family | Emerson DeltaV traditional I/O |
| Number of output channels | 32 |
| Output configuration | 24 V DC, high-side switching |
| Output rating | 100 mA continuous per channel |
| Output range | 24 V DC ±10% |
| Off-state leakage | 0.1 mA maximum |
| LocalBus current | 100 mA typical; 150 mA maximum at 12 V DC nominal |
| Field circuit power per card | 3.2 A at 24 V DC (+20% / -15%) |
| Isolation | Each channel optically isolated from the system; factory tested to 1500 V DC |
| Terminal block | Standard 32-screw I/O termination block |
| Operating temperature | -40 to 70°C (-40 to 158°F) |
| Storage temperature | -40 to 85°C (-40 to 185°F) |
| Relative humidity | 5 to 95%, non-condensing |
| Protection rating | IP20 |
| Card dimensions | 10.7 cm H × 4.1 cm W × 10.5 cm D |
| Conformal coating | ISA-S71.04-1985 Class G3 |
Detailed Product Overview
The VE4002S1T2B5 converts discrete commands from a DeltaV controller into 24 V DC high-side outputs. Because it switches the positive leg of each field circuit, no current flows in the field wiring when an output is off; this can simplify troubleshooting and reduce unintended energization of loads during an output-off condition.
With 32 output channels on one card, the module is intended for applications that require many low-current digital outputs in a compact I/O footprint. Typical loads include solenoid-operated valves, relay coils, and panel indicators, provided each channel load remains within the 100 mA per-channel rating and the complete card remains within its 3.2 A field-circuit power limit.
Each output channel is optically isolated from the DeltaV system and is factory tested at 1500 V DC. This isolation separates the controller-side logic from the field-side switching circuit, which is important when field wiring, power distribution, and control-system grounding are designed as separate electrical domains.
The card uses the DeltaV LocalBus for communication and internal power. It must be installed in a compatible DeltaV I/O interface carrier together with the correct keyed 32-channel DO termination block. The keyed interface helps ensure that the output card is installed only in a termination block intended for its function, reducing the risk of mismatched field wiring during maintenance or replacement.
The VE4002S1T2B5 is a simplex discrete output interface. It should be selected where the required load current per point is modest and where high-side 24 V DC switching matches the field-device wiring design. Loads requiring higher current, isolated channels, AC switching, or per-channel fusing require a different DeltaV DO card and terminal-block configuration.

VE4002S1T2B5

VE4002S1T2B5
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Control system | Emerson DeltaV distributed control system | The card is part of the DeltaV traditional I/O subsystem. |
| I/O architecture | DeltaV traditional I/O interface | The card plugs into a compatible DeltaV I/O interface carrier. |
| Controller | DeltaV controller supporting the installed traditional I/O subsystem | Controller and I/O subsystem must be configured in the DeltaV engineering environment. |
| Carrier | DeltaV I/O interface carrier | The card and terminal block mount in the carrier slot arrangement. |
| Terminal block | Standard 32-screw DO I/O termination block | The card and terminal block are keyed as a matched I/O interface. |
| Field power | 24 V DC field circuit power, 3.2 A maximum per card | Field supply must accommodate the connected load and card-level limit. |
| LocalBus power | 12 V DC nominal; 100 mA typical, 150 mA maximum | Supplied through the DeltaV I/O interface carrier. |
| Field wiring | High-side 24 V DC output circuits | Each channel is limited to 100 mA. |
| Software | DeltaV system software supporting the installed I/O hardware | The I/O card and channels must be assigned and configured in DeltaV Explorer. |
Dimensions, Mounting & Connection Notes
- Card size: 10.7 cm high × 4.1 cm wide × 10.5 cm deep.
- Mounting: Inserts into a compatible DeltaV traditional I/O interface carrier.
- Field connection: Uses a standard 32-screw I/O termination block.
- Interface keying: The card and terminal block use DeltaV I/O function keying to prevent installation of an incompatible card in a terminal block.
- Environmental installation limits: -40 to 70°C operating temperature, 5 to 95% non-condensing relative humidity, and IP20 protection.
- Environmental protection: Conformal coating meeting ISA-S71.04-1985 Class G3 airborne-contaminant requirements.
- Mechanical environment: 10 g half-sine shock for 11 ms; 1 mm peak-to-peak vibration from 5 to 16 Hz and 0.5 g from 16 to 150 Hz.
FAQ
What is the Emerson VE4002S1T2B5?
It is an Emerson DeltaV discrete output card with 32 channels of 24 V DC high-side switching and a standard I/O termination block.
How many outputs does the VE4002S1T2B5 provide?
It provides 32 discrete output channels.
What type of output does it use?
It uses 24 V DC high-side switching, with a continuous rating of 100 mA per channel.
What field loads can it drive?
It is intended for low-current 24 V DC loads such as solenoid valves, interposing relays, and indicator lights, within the per-channel and card-level current limits.
What power does the card require?
It receives 12 V DC nominal LocalBus power from the DeltaV I/O interface carrier and requires 24 V DC field-circuit power for the outputs, with a card-level limit of 3.2 A.
Which terminal block does it require?
It requires the matching keyed standard 32-screw DO I/O termination block in the DeltaV traditional I/O interface.
Is each output isolated from the DeltaV system?
Yes. Each channel is optically isolated from the system and is factory tested to 1500 V DC.
What environmental limits apply?
The I/O interface is rated for -40 to 70°C operation, 5 to 95% non-condensing relative humidity, and IP20 protection.
Documented Performance Data
| Metric | Value / Range | Operating condition |
|---|---|---|
| Output current | 100 mA continuous per channel | 24 V DC high-side output |
| Output voltage range | 24 V DC ±10% | Field output circuit |
| Off-state leakage | 0.1 mA maximum | Output off |
| Field circuit power | 3.2 A maximum per card | 24 V DC, +20% / -15% supply range |
| LocalBus current | 100 mA typical; 150 mA maximum | 12 V DC nominal LocalBus supply |
| Channel isolation | 1500 V DC factory test | Optical isolation between channel and system |