Sale!

Emerson VE4003S2B3 DeltaV 16-Channel Isolated Analog Input Card

Parameter Specification
Manufacturer Emerson
Model / Part Number VE4003S2B3
System Family DeltaV Traditional I/O
Module Type Analog Input Card (Series 2)
Channel Density 16 Channels
Input Signal Types 4-20 mA HART, 1-5 VDC, mV, Thermocouple, RTD (depending on terminal block type)
Analog-to-Digital Conversion 16-bit resolution
Categories: , , , , SKU: VE4003S2B3 Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The Emerson VE4003S2B3 is a 16-channel isolated analog input card designed for the DeltaV distributed control system. Operating within the DeltaV Traditional I/O subsystem, this Series 2 module processes continuous analog signals from field instrumentation such as transmitters, thermocouples, RTDs, and 4-20 mA current loops, converting them into digital data for system controllers.

This module features 16 independent input channels equipped with channel-to-channel and channel-to-bus galvanic isolation to protect internal control hardware from ground loops and common-mode transients. Designed to mount on standard DeltaV 2-wide or 8-wide I/O interface carriers, the VE4003S2B3 interfaces with matching analog input terminal blocks and communicates process data back to the primary controllers across the redundant LocalBus backplane.

 

Key Technical Specifications

Parameter Specification
Manufacturer Emerson
Model / Part Number VE4003S2B3
System Family DeltaV Traditional I/O
Module Type Analog Input Card (Series 2)
Channel Density 16 Channels
Input Signal Types 4-20 mA HART, 1-5 VDC, mV, Thermocouple, RTD (depending on terminal block type)
Analog-to-Digital Conversion 16-bit resolution
Galvanic Isolation Optical/transformer isolation up to 250V AC continuous common-mode voltage
LocalBus Power Consumption 120 mA typical, 175 mA maximum (12V DC nominal)
Operating Temperature Range -40°C to +70°C (-40°F to +158°F)
Storage Temperature Range -40°C to +85°C (-40°F to +185°F)
Relative Humidity 5% to 95% non-condensing
Environmental Protection IP20 rating; G3 conformal coating option available
Mechanical Shock / Vibration 10 g half-sine wave (11 ms); 1 mm peak-to-peak (5–16 Hz), 0.5 g (16–150 Hz)

 

Detailed Product Overview

The Emerson VE4003S2B3 analog input card serves as a high-density data acquisition interface for industrial process measurement loops. It bridges field sensors and the DeltaV control architecture by continuously sampling analog voltage, current, or temperature signals and converting them into scaled engineering units via onboard 16-bit analog-to-digital converters.

Each input channel incorporates galvanic isolation to mitigate ground potential differences and electrical noise commonly found in large industrial installations. The module supports HART communication pass-through, allowing digital configuration, diagnostic polling, and calibration data from smart field transmitters to superimpose over standard 4-20 mA analog loops without signal degradation.

Power for internal module logic is drawn directly from the carrier backplane’s 12V DC LocalBus. Mechanical keying features on the housing ensure alignment with designated terminal blocks, preventing installation errors on live carriers.

 VE4003S2B3

VE4003S2B3

 VE4003S2B3

VE4003S2B3

Engineering Selection Highlights

  • High-Density 16-Channel Architecture: Accommodates up to 16 independent analog inputs on a single card slot, optimizing cabinet layout and I/O carrier footprint.
  • HART Protocol Pass-Through: Enables digital communication with smart field instruments for remote device configuration and diagnostics alongside standard 4-20 mA signals.
  • Galvanic Isolation: Provides robust channel isolation to prevent ground loops and protect internal processing logic from electrical surges.
  • High-Resolution Conversion: Integrates 16-bit A/D conversion to ensure precise measurement and detection of process variable fluctuations.
  • Series 2 Carrier Compatibility: Snaps directly onto standard DeltaV Traditional I/O interface carriers and works with designated personality terminal blocks.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Automation System Emerson DeltaV DCS Integrated within DeltaV controller environments
Subsystem Series Traditional I/O Series 2 Requires Series 2 compatible carrier backplanes
Carrier Mounting DeltaV 2-wide / 8-wide I/O Interface Carriers Installed on DIN-rail mounted system carriers
Terminal Block 16-Channel Analog Terminal Block Requires a matching analog terminal block for field wiring
Backplane Power DeltaV LocalBus (12V DC) Draws up to 175 mA maximum from carrier bus
Engineering Software DeltaV Explorer / Control Studio Configured via standard DeltaV software system configuration trees

 

Dimensions, Mounting & Connection Notes

  • Height: 10.7 cm (4.2 in.)
  • Width: 4.1 cm (1.6 in.)
  • Depth: 10.5 cm (4.1 in.)
  • Mounting Method: Plugs directly into a DeltaV I/O interface carrier mounted on standard T-section DIN rails (EN 50022).
  • Clearance Requirements: Ensure adequate vertical spacing above and below the I/O carrier assembly to maintain natural air circulation and cooling inside control cabinets.
  • Terminal Wiring: Field signal cables terminate at the corresponding 16-channel analog terminal block using screw or spring-clamp connections.
  • Shield Grounding: Shield wires from analog signal cables should be terminated at dedicated copper grounding bars provided on the carrier assembly to suppress electromagnetic interference.

 

FAQ

What is the Emerson VE4003S2B3?

The Emerson VE4003S2B3 is a 16-channel isolated analog input card designed for the DeltaV distributed control system to process continuous sensor and transmitter signals.

Does the VE4003S2B3 support HART communication?

Yes, the module supports HART pass-through, allowing digital diagnostics and configuration data to pass between smart field transmitters and the DeltaV system.

What is the resolution of the analog-to-digital conversion?

The module utilizes a 16-bit analog-to-digital converter to ensure precise signal measurement.

What power supply does the module require?

It draws internal operating power (12V DC nominal) directly from the DeltaV LocalBus carrier backplane.

Which terminal blocks are compatible with this module?

It requires a matching DeltaV 16-channel analog terminal block mounted on the I/O interface carrier.

 

Verification & Troubleshooting Notes

  • Module Status Indicators: Check the diagnostic LEDs on the front faceplate. A steady green status indicator confirms healthy LocalBus communication and normal operation, while red or flashing states indicate hardware faults or communication loss.
  • Loop Power Verification: If an analog input reads zero or out-of-range, verify that external loop power is active and that 4-20 mA loop current is flowing properly through the terminal block.
  • Signal Noise Inspection: In the event of erratic process variable readings, inspect shielded cable terminations at the carrier ground bar to ensure electromagnetic interference is adequately suppressed.
  • Terminal Block Seating Check: If the card experiences intermittent channel communication, ensure the module is fully latched and securely seated against its terminal block and carrier backplane.