Description
Core Product Summary (Brand / Model / Key Attributes)
The Emerson VE4003S2B6 (Assembly Part Number KJ3223X1-BA1) is an 8-channel analog input card for the DeltaV distributed control system. Operating within the DeltaV Traditional I/O subsystem, this Series 2 module converts continuous 4-20 mA analog signals from process transmitters and field sensors into digital data for DeltaV controllers.
This module features 8 isolated channels equipped with HART protocol pass-through, enabling bidirectional digital communication with smart field instruments alongside standard analog measurement loops. Designed to mount on standard DeltaV 2-wide or 8-wide I/O interface carriers, the VE4003S2B6 / KJ3223X1-BA1 receives internal logic power directly from the 12V DC LocalBus backplane and pairs with matching 8-channel analog input terminal blocks.
Key Technical Specifications
| Parameter | Specification |
| Manufacturer | Emerson |
| Model Number | VE4003S2B6 |
| Board Assembly Number | KJ3223X1-BA1 |
| System Family | DeltaV Traditional I/O |
| Module Type | Analog Input Card (Series 2) |
| Channel Density | 8 Channels |
| Input Signal Range | 4-20 mA DC (HART active) |
| Signal Resolution | 16-bit A/D conversion |
| Channel Isolation | Galvanic isolation, 1000V DC channel-to-system |
| LocalBus Power Rating | 12V DC at 150 mA maximum |
| Transmitter Loop Power | Requires external 24V DC field power supply |
| Operating Temperature | -40°C to +70°C (-40°F to +158°F) |
| Storage Temperature | -40°C to +85°C (-40°F to +185°F) |
| Relative Humidity | 5% to 95% non-condensing |
| Environmental Protection | IP20 rating; G3 conformal coating standard |
| Shock / Vibration | 10 g half-sine wave (11 ms); 1 mm peak-to-peak (5–16 Hz), 0.5 g (16–150 Hz) |
Detailed Product Overview
The Emerson VE4003S2B6 KJ3223X1-BA1 analog input module functions as a signal processing interface between process field transmitters and the DeltaV control architecture. By sampling 4-20 mA current loops across 8 independent channels, the card converts process variables—such as pressure, temperature, flow, and level—into digital values passed to the controller via the redundant LocalBus backplane.
The module supports HART dynamic data pass-through. This allows secondary process variables, device diagnostics, calibration parameters, and instrument health metrics to be communicated between smart field transmitters and DeltaV engineering software without interrupting primary analog control loops.
Each input channel features internal galvanic isolation to prevent ground potential loops and isolate control logic from field-side electrical surges. Low-voltage internal logic power is supplied via the 12V DC LocalBus, while field transmitter loop power is provided by landed 24V DC bulk supplies at the terminal block. Physical alignment keys on the module body match designated slot configurations on the interface carrier to ensure proper mechanical seating.

VE4003S2B6 KJ3223X1-BA1

VE4003S2B6 KJ3223X1-BA1
Engineering Selection Highlights
- 8-Channel HART Integration: Combines 4-20 mA analog input processing with HART digital communications on 8 independent channels.
- Galvanic Isolation: 1000V DC channel-to-system isolation protects central DeltaV controller electronics from field noise and ground voltage fluctuations.
- 16-Bit Resolution: High-resolution analog conversion ensures precise monitoring of continuous process variables.
- Dual Power Separation: Logic functions utilize 12V DC LocalBus backplane power, isolating system processing from external 24V DC transmitter field loop circuits.
- Polarized Carrier Keying: Integrates physical mechanical keys to restrict insertion to properly keyed carrier slots and terminal bases.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| Automation System | Emerson DeltaV DCS | Fully integrated within DeltaV control networks |
| Subsystem Series | Traditional I/O Series 2 | Requires Series 2 carrier hardware |
| Carrier Mounting | DeltaV 2-wide / 8-wide I/O Interface Carriers | Mounts directly onto standard DIN-rail carriers |
| Terminal Block | 8-Channel Analog Input Terminal Block | Requires matching 8-channel terminal block for field wiring |
| Backplane Power | DeltaV LocalBus (12V DC) | Draws up to 150 mA maximum from carrier backplane |
| External Power | 24V DC Auxiliary Field Power Supply | Landed at terminal block for 2-wire transmitter loop powering |
| Engineering Software | DeltaV Explorer / Control Studio | Configured via standard DeltaV software system hardware trees |
Dimensions, Mounting & Connection Notes
- Height: 10.7 cm (4.2 in.)
- Width: 4.1 cm (1.6 in.)
- Depth: 10.5 cm (4.1 in.)
- Mounting Method: Direct snap-in mounting onto a DeltaV I/O interface carrier fixed to standard T-section DIN rail (EN 50022).
- Clearance Requirements: Provide standard vertical ventilation clearance above and below the carrier assembly for natural thermal dissipation inside control enclosures.
- Terminal Wiring: Field instrument wiring connects directly to the associated 8-channel terminal block using screw or spring-clamp connections.
- Grounding: Functional grounding is established automatically through the metal grounding contact strip on the carrier base during installation.
FAQ
What is the difference between VE4003S2B6 and KJ3223X1-BA1?
VE4003S2B6 is the system model designation for the 8-channel HART analog input card, while KJ3223X1-BA1 refers to the printed circuit board assembly part number for the identical hardware unit.
How many channels are supported on the VE4003S2B6?
The module features 8 independent analog input channels.
Does the VE4003S2B6 support HART protocol communication?
Yes, all 8 channels support HART pass-through communication for smart transmitter diagnostics and secondary variable access.
What input signal type does this card accept?
It accepts standard 4-20 mA DC analog current loop signals.
What terminal block is required for installation?
The module requires a compatible DeltaV 8-channel analog input terminal block attached to an I/O interface carrier.
What voltage powers the internal logic of the module?
The card draws nominal 12V DC logic power directly from the DeltaV LocalBus backplane.
Verification & Troubleshooting Notes
- Status LED Inspection: Check the front faceplate LEDs. A steady green status LED indicates normal power delivery and active LocalBus communication. A solid or flashing red LED indicates internal self-test failure, configuration mismatch, or lost backplane communication.
- Transmitter Loop Current Measurement: If a channel reads 0 mA or indicates an under-range fault in DeltaV Explorer, place a digital multimeter in series with the loop to check for 4-20 mA current. Verify that 24V DC loop power is present at the field terminals.
- HART Communication Verification: If HART data is missing while the 4-20 mA analog signal remains steady, verify in DeltaV Explorer that HART processing is enabled for the specific channel and check field cable shielding for excessive noise.
- Carrier Seating Check: If the card experiences intermittent offline status, disengage the module release latches, re-seat the card firmly onto the carrier backplane connector, and ensure the retention latches snap securely into place.
- Keying Alignment: If the card resists insertion onto the carrier, verify that the carrier polarization keys match the slot keying configuration of the VE4003S2B6 / KJ3223X1-BA1. Do not force insertion.

WhatsApp: +86 16626708626