Emerson VE4003S2B6 DeltaV 16-Channel 4–20 mA HART Analog Input Interface

Parameter Specification
Manufacturer Emerson
Model / order number VE4003S2B6
Product type 16-channel 4–20 mA HART analog input I/O interface
Control system family Emerson DeltaV traditional I/O
I/O card AI Plus, 16-channel, 4–20 mA HART
Input configuration 2-wire, 4–20 mA
Number of channels 16
Nominal signal range 4 to 20 mA
Full signal range 2 to 22 mA, with over-range checking
Transmitter power 13.5 V minimum at 20 mA; maximum current limited to 29 mA
Accuracy over temperature range 0.2% of span
Repeatability 0.05% of span
Resolution 16-bit A/D converter
Categories: , , , , SKU: VE4003S2B6 Brand:

Description

Core Product Summary

The Emerson VE4003S2B6 is a DeltaV 16-channel 4–20 mA HART analog input interface for the DeltaV traditional I/O subsystem. It combines the 16-channel AI Plus analog input card with the matching 16-channel 2-wire AI terminal block for Series 2 Plus, providing field-wiring termination for 2-wire HART transmitters.

The interface accepts a nominal 4–20 mA input span with a full signal range of 2 to 22 mA and over-range checking. It provides HART pass-through for AMS Device Manager and HART variable and status reporting for control functions. The AI Plus card uses a 16-bit A/D converter, requires no calibration, and can be installed in either simplex or redundant configuration with the appropriate DeltaV terminal block.

 

Key Technical Specifications

Parameter Specification
Manufacturer Emerson
Model / order number VE4003S2B6
Product type 16-channel 4–20 mA HART analog input I/O interface
Control system family Emerson DeltaV traditional I/O
I/O card AI Plus, 16-channel, 4–20 mA HART
Input configuration 2-wire, 4–20 mA
Number of channels 16
Nominal signal range 4 to 20 mA
Full signal range 2 to 22 mA, with over-range checking
Transmitter power 13.5 V minimum at 20 mA; maximum current limited to 29 mA
Accuracy over temperature range 0.2% of span
Repeatability 0.05% of span
Resolution 16-bit A/D converter
Anti-aliasing roll-off -3 dB at 2.7 Hz; -20.5 dB at 20 Hz
Calibration None required
LocalBus current, simplex 85 mA typical; 150 mA maximum at 12 V DC nominal
LocalBus current, redundant 110 mA typical; 200 mA maximum per card at 12 V DC nominal
Field circuit power 500 mA maximum at 24 V DC ±10% per card
Isolation Each channel optically isolated from the system; factory tested to 1000 V DC
HART support HART pass-through for AMS Device Manager; HART variable and status reporting for control functions
HART scan time 600 to 800 ms typical per enabled channel
Terminal block 16-channel 2-wire AI terminal block for Series 2 Plus
I/O card keying A6
Software requirement DeltaV v13.3.1 or later for AI Plus 16-channel cards
Operating temperature -40 to 70°C (-40 to 158°F)
Storage temperature -40 to 85°C (-40 to 185°F)
Relative humidity 5 to 95%, non-condensing
Protection rating IP20
Card dimensions 10.7 cm H × 4.1 cm W × 10.5 cm D
Conformal coating ISA-S71.04-1985 Class G3

 

Detailed Product Overview

The VE4003S2B6 provides a high-density analog input interface for DeltaV control systems that use 2-wire 4–20 mA HART transmitters. Its 16 channels allow a larger number of process measurements—such as pressure, flow, level, and analytical measurements—to be terminated in one I/O interface than an 8-channel AI card supports.

The interface is built around the DeltaV AI Plus 16-channel analog input card. Each channel accepts a 4–20 mA signal and supports a 2 to 22 mA full signal range with over-range checking. The card digitizes each input with a 16-bit A/D converter and provides an accuracy of 0.2% of span across its temperature range. No field calibration is required.

For 2-wire transmitters, the interface supplies loop power from the DeltaV field circuit. The AI Plus card provides at least 13.5 V at 20 mA and limits maximum loop current to 29 mA. The complete interface is limited to 500 mA of field circuit power at 24 V DC ±10%, so the connected transmitter load must be planned within that card-level limit.

HART communication is supported through HART pass-through to AMS Device Manager. The card also reports HART variables and status to DeltaV control functions. HART scanning typically takes 600 to 800 ms per enabled channel, which is relevant when HART data is used for diagnostics or advanced monitoring rather than fast control.

The AI Plus card is optically isolated from the DeltaV system on every channel and is factory tested at 1000 V DC. It can be installed as a simplex interface or as a redundant pair when used with the appropriate redundant 2-wire and 4-wire AI terminal block. In a redundant installation, DeltaV recognizes the two cards as one logical interface and performs automatic switchover if the active card or its communication path develops a fault.

The VE4003S2B6 uses the A6 key position and the 16-channel 2-wire AI terminal block for Series 2 Plus. DeltaV function keying prevents an incompatible I/O card from being installed in the terminal block. The AI Plus 16-channel card requires DeltaV v13.3.1 or later software.

VE4003S2B6

VE4003S2B6

VE4003S2B6

VE4003S2B6

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Control system Emerson DeltaV distributed control system Part of the DeltaV traditional I/O subsystem.
I/O architecture DeltaV M-series traditional I/O Requires M-series horizontal or VerticalPlus I/O carriers.
Controllers DeltaV MQ, MX, or PK controllers M-series traditional I/O hardware requires one of these controller types.
I/O card AI Plus, 16-channel, 4–20 mA HART Supports simplex or redundant installation.
Terminal block 16-channel 2-wire AI terminal block for Series 2 Plus Required for the 2-wire transmitter configuration.
Redundant terminal block Redundant 2- and 4-wire AI terminal block Required when installing the AI Plus card as a redundant pair.
I/O card keying A6 Ensures that only the matching AI Plus card is installed in the keyed terminal block.
Field signal 2-wire, 4–20 mA HART transmitters Nominal span is 4–20 mA; full range is 2–22 mA.
Field power 500 mA maximum per card at 24 V DC ±10% Plan the total connected transmitter load within this limit.
HART software AMS Device Manager for HART pass-through HART variables and status can also be reported to DeltaV control functions.
Software DeltaV v13.3.1 or later Required for AI Plus 16-channel I/O cards.

 

Dimensions, Mounting & Connection Notes

  • Card size: 10.7 cm high × 4.1 cm wide × 10.5 cm deep.
  • Mounting method: The AI Plus card plugs into a compatible DeltaV M-series I/O interface carrier.
  • Terminal-block installation: The 16-channel 2-wire AI terminal block plugs directly onto the carrier and can be pre-wired before the I/O card is installed.
  • Interface keying: The AI Plus card uses the A6 key position; the terminal block accepts only the matching keyed card.
  • Field wiring: Intended for 2-wire 4–20 mA HART transmitter circuits.
  • Field power: The interface supplies transmitter loop power, with a card-level limit of 500 mA at 24 V DC ±10%.
  • Environmental installation limits: -40 to 70°C operating temperature, 5 to 95% non-condensing relative humidity, and IP20 protection.
  • Environmental protection: Conformal coating meeting ISA-S71.04-1985 Class G3 airborne-contaminant requirements.
  • Mechanical environment: 10 g half-sine shock for 11 ms; 1 mm peak-to-peak vibration from 5 to 16 Hz and 0.5 g from 16 to 150 Hz.

 

FAQ

What is the Emerson VE4003S2B6?
It is an Emerson DeltaV 16-channel 4–20 mA HART analog input I/O interface, comprising the AI Plus 16-channel analog input card and the matching 16-channel 2-wire AI terminal block for Series 2 Plus.

How many analog inputs does the VE4003S2B6 support?
It supports 16 analog input channels.

What signal type does it accept?
It accepts 2-wire 4–20 mA HART transmitter signals, with a full signal range of 2 to 22 mA and over-range checking.

Does it support HART communication?
Yes. It provides HART pass-through for AMS Device Manager and reports HART variables and status to DeltaV control functions.

What field power does it provide?
The AI Plus interface supplies transmitter loop power, providing at least 13.5 V at 20 mA and limiting loop current to 29 mA. The card-level field circuit power limit is 500 mA at 24 V DC ±10%.

Can the VE4003S2B6 be used redundantly?
Yes. The AI Plus 16-channel card supports redundant installation when used with the appropriate redundant 2- and 4-wire AI terminal block.

Which terminal block does it require?
For the 2-wire configuration, it requires the 16-channel 2-wire AI terminal block for Series 2 Plus. The card uses A6 keying.

What DeltaV software version is required?
The AI Plus 16-channel analog input card requires DeltaV v13.3.1 or later.

 

Documented Performance Data

Metric Value / Range Test / operating condition
Input channels 16 AI Plus 16-channel analog input card
Nominal input span 4 to 20 mA 2-wire transmitter input
Full signal range 2 to 22 mA With over-range checking
Transmitter power 13.5 V minimum at 20 mA Maximum loop current limited to 29 mA
Accuracy 0.2% of span Over the card temperature range
Repeatability 0.05% of span Analog input measurement
Resolution 16-bit A/D converter Analog-to-digital conversion
Anti-aliasing roll-off -3 dB at 2.7 Hz; -20.5 dB at 20 Hz Analog input filter response
HART scan time 600 to 800 ms typical per enabled channel HART communication
LocalBus current 85 mA typical; 150 mA maximum, simplex 12 V DC nominal LocalBus supply
LocalBus current, redundant 110 mA typical; 200 mA maximum per card 12 V DC nominal LocalBus supply
Field circuit power 500 mA maximum per card 24 V DC ±10%
Channel isolation 1000 V DC factory test Optical isolation between channel and system