Description
Core Product Summary
The Emerson VE4003S2B9 is the 16-channel 2-wire AI terminal block for the DeltaV M-series Traditional I/O Series 2 Plus analog input card. It provides the field-wiring interface for 16 channels of 4-20 mA HART signals from 2-wire transmitters.
This terminal block is ordered specifically for the AI Plus card configuration and mounts on the compatible I/O interface carrier. It is intended for use with simplex AI Plus hardware supporting 2-wire device connections and HART communication.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Product Type | 16-Channel 2-Wire AI Terminal Block |
| System Family | DeltaV M-series Traditional I/O, Series 2 Plus |
| Associated Card | AI Plus, 16-channel 4-20 mA HART |
| Channel Count | 16 |
| Signal Type | 4-20 mA HART (2-wire) |
| Nominal Signal Range | 4 to 20 mA |
| Full Signal Range (card) | 2 to 22 mA with over-range checking |
| Transmitter Power (card) | 13.5 V minimum at 20 mA (max current limited at 29 mA) |
| Isolation (card) | Optical per channel, factory tested to 1000 V DC |
| Accuracy (card) | 0.2 % of span over temperature range |
| Resolution (card) | 16-bit A/D converter |
| Repeatability (card) | 0.05 % of span |
| Form Factor | H 10.7 cm × W 4.1 cm × D 10.5 cm |
| Operating Temperature | –40 °C to +70 °C |
| Storage Temperature | –40 °C to +85 °C |
| Relative Humidity | 5 % to 95 %, non-condensing |
| Protection Rating | IP20 |
| Airborne Contaminants | ISA-S71.04 Class G3, conformal coating |
Engineering Selection Highlights
- Designed exclusively for the 16-channel AI Plus card in Series 2 Plus configurations, ensuring correct keying and interface match.
- Supports only 2-wire 4-20 mA HART transmitters; the companion VE4003S2B10 is required for 4-wire devices.
- Provides the physical termination interface on the M-series I/O carrier for high-density analog input.
- Compatible with simplex AI Plus installations; redundant arrangements use the VE4033S2B10 terminal block.
- Requires DeltaV software that supports Series 2 Plus I/O (typically v13.3.1 or later for full AI Plus functionality).
- Shares the standard M-series environmental and mechanical ratings for consistent cabinet integration.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| System / Family | DeltaV M-series Traditional I/O, Series 2 Plus | Requires M-series carriers |
| Associated Card | AI Plus 16-channel 4-20 mA HART (key position A6) | Card and block must match |
| Device Wiring | 2-wire transmitters only | Use VE4003S2B10 for 4-wire |
| Carrier | M-series horizontal or VerticalPlus | Not compatible with S-series carriers |
| Controllers | MQ, MX or PK (M-series) | Confirm software version supports Plus cards |
| Redundancy | Simplex only with this block | Redundant terminal block is VE4033S2B10 |
| Software | Supports Series 2 Plus AI cards | Confirm system revision for full feature set |
Dimensions, Mounting & Connection Notes
The terminal block follows the standard M-series I/O interface form factor of 10.7 cm height × 4.1 cm width × 10.5 cm depth. It mounts directly on the M-series I/O interface carrier. Field wiring for 16 channels of 2-wire 4-20 mA HART devices is terminated at the block. Installation must observe the keying rules that prevent incorrect card-to-block combinations. Environmental limits match the family ratings. Always verify mechanical engagement and wiring practices against the current installation documentation for the installed system.
Detailed Product Overview
The Emerson VE4003S2B9 is the official order number for the 16-channel 2-wire AI terminal block used with the Series 2 Plus analog input card in the DeltaV M-series Traditional I/O subsystem. In the modular Traditional I/O design, the AI Plus card and its matching terminal block form a complete 16-channel interface that plugs into a DIN-rail-mounted carrier.
This specific terminal block is listed for 2-wire device support. The card supplies loop power to the transmitters and performs 16-bit conversion with HART communication. Optical isolation is provided on each channel. The companion 4-wire terminal block (VE4003S2B10) is used when externally powered transmitters are required. Redundant configurations require the corresponding redundant terminal block order number.
The block inherits the common mechanical dimensions and environmental ratings of the M-series I/O family, including operation from –40 °C to +70 °C, IP20 protection, and Class G3 conformal coating. Keying ensures that only the correct AI Plus card can be inserted into this terminal block.
Selection of the VE4003S2B9 is appropriate when a project requires 16 channels of 2-wire 4-20 mA HART input on Series 2 Plus hardware. Confirm the exact software version, carrier type, controller model, and whether simplex or redundant I/O is specified before ordering. Physical keying and connector orientation must be verified against the installed hardware prior to energization.

VE4003S2B9

VE4003S2B9
Applications & System Role
The VE4003S2B9 serves as the field termination interface for a 16-channel AI Plus card within the DeltaV M-series Traditional I/O architecture. It connects 2-wire 4-20 mA HART transmitters to the high-density analog input card, enabling process variable acquisition and HART pass-through for diagnostics and secondary variables. It is typically installed in control cabinets or field junction boxes where Series 2 Plus Traditional I/O is used for higher channel density compared with standard 8-channel cards.
FAQ
What is the Emerson VE4003S2B9?
It is the 16-channel 2-wire AI terminal block for the Series 2 Plus analog input card in DeltaV M-series Traditional I/O.
Which card does the VE4003S2B9 mate with?
It mates with the AI Plus 16-channel 4-20 mA HART card.
What type of field devices does it support?
It supports 2-wire 4-20 mA HART transmitters only.
Can it be used for 4-wire transmitters?
No. The VE4003S2B10 terminal block is specified for 4-wire devices with the same AI Plus card.
Is the VE4003S2B9 suitable for redundant I/O?
No. It is for simplex installations. The redundant terminal block is VE4033S2B10.
What are the typical dimensions?
Approximately 10.7 cm height × 4.1 cm width × 10.5 cm depth, matching the standard M-series I/O form factor.
What environmental ratings apply?
Operating temperature –40 °C to +70 °C, IP20, ISA-S71.04 Class G3 with conformal coating.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626