Sale!

Emerson VE4005S1B3 DeltaV 8-Channel Analog Output Card

Parameter Specification
Manufacturer Emerson
Model / Part Number VE4005S1B3
System Family DeltaV Traditional I/O
Module Type Analog Output Card (Series 1)
Channel Density 8 Channels
Output Signal Range 4-20 mA DC
Signal Resolution 12-bit to 16-bit D/A conversion
Categories: , , , , SKU: VE4005S1B3 Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The Emerson VE4005S1B3 is an 8-channel analog output card designed for the DeltaV distributed control system. Operating within the DeltaV Traditional I/O subsystem, this Series 1 module converts digital control commands from DeltaV controllers into continuous 4-20 mA DC current signals to drive field actuators, control valve positioners, and variable speed drives.

This module features 8 independent 4-20 mA analog output channels with onboard digital-to-analog conversion and electrical isolation to safeguard system electronics from field noise and ground potential differences. Designed to mount on standard DeltaV I/O interface carriers, the VE4005S1B3 receives internal logic power directly from the 12V DC LocalBus backplane and pairs with compatible 8-channel analog output terminal blocks for field wiring connections.

 

Key Technical Specifications

Parameter Specification
Manufacturer Emerson
Model / Part Number VE4005S1B3
System Family DeltaV Traditional I/O
Module Type Analog Output Card (Series 1)
Channel Density 8 Channels
Output Signal Range 4-20 mA DC
Signal Resolution 12-bit to 16-bit D/A conversion
Channel Isolation Optical/galvanic isolation between field and backplane logic
LocalBus Power Consumption Nominal 12V DC backplane supply
External Field Power 24V DC bulk field power supply required at terminal base
Operating Temperature Range -40°C to +70°C (-40°F to +158°F)
Storage Temperature Range -40°C to +85°C (-40°F to +185°F)
Relative Humidity 5% to 95% non-condensing
Environmental Protection IP20 rating; G3 conformal coating option available
Shock / Vibration 10 g half-sine wave (11 ms); 1 mm peak-to-peak (5–16 Hz), 0.5 g (16–150 Hz)

 

Detailed Product Overview

The Emerson VE4005S1B3 analog output card serves as an executive signal conditioning interface within the DeltaV process control network. By converting system digital control commands into 8 independent 4-20 mA current loops, the card delivers stable analog driving signals required for continuous modulating control of field positioners, I/P transducers, and motor speed drives.

Internal module processing relies on 12V DC logic power supplied directly through the DeltaV LocalBus backplane. Field loop power is sourced from an external 24V DC bulk supply landed directly at the associated terminal block. Electrical isolation separates the field terminal loops from backplane processing logic, preventing electrical surges and ground noise from affecting system controllers.

The card features physical polarization keying on its enclosure. These keys align with designated slot positions on DeltaV I/O interface carriers and terminal bases, ensuring the card can only be installed into properly assigned slots to prevent miswiring and component damage.

 

Engineering Selection Highlights

  • 8-Channel 4-20 mA Signal Output: Generates 8 independent analog current loops for driving modulating valves, positioners, and process actuators.
  • Galvanic & Optical Isolation: Shields central DeltaV controller backplanes from field-side electrical surges and ground loops.
  • Dual Power Supply Architecture: Separates internal 12V DC LocalBus logic power from external 24V DC field circuit power.
  • Carrier Mechanical Keying: Features physical keying slots to restrict card insertion strictly to matching, correctly configured terminal bases.
  • Hot-Swappable Module Support: Designed to allow modular installation onto active DeltaV I/O interface carriers without interrupting adjacent field channels.
VE4005S1B3

VE4005S1B3

VE4005S1B3

VE4005S1B3

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Automation System Emerson DeltaV DCS Integrated into DeltaV controller hardware trees
Subsystem Series Traditional I/O Series 1 Plugs into Traditional I/O interface carriers
Carrier Mounting DeltaV 2-wide / 8-wide I/O Interface Carriers Snaps onto standard DIN-rail mounted interface carriers
Terminal Block 8-Channel Analog Output Terminal Block Requires matching 8-channel terminal block for field wiring
Backplane Power DeltaV LocalBus (12V DC) Draws operating logic power directly from the carrier backplane
External Field Power 24V DC Auxiliary Field Power Supply Landed at the terminal block to drive 4-20 mA output loops
Engineering Software DeltaV Explorer / Control Studio Configured via standard DeltaV hardware management software

 

Dimensions, Mounting & Connection Notes

  • Height: 10.7 cm (4.2 in.)
  • Width: 4.1 cm (1.6 in.)
  • Depth: 10.5 cm (4.1 in.)
  • Mounting Method: Direct snap-in mounting onto a DeltaV I/O interface carrier attached to standard T-section DIN rail (EN 50022).
  • Clearance Requirements: Maintain standard vertical ventilation clearance above and below the I/O carrier assembly to ensure natural thermal convection inside control enclosures.
  • Terminal Wiring: Output field conductors connect to the corresponding 8-channel terminal block using screw or spring-clamp terminals.
  • Shield Grounding: Field cable shields should be connected to the carrier’s dedicated ground bar to minimize high-frequency noise interference on analog current loops.

 

FAQ

What is the primary function of the Emerson VE4005S1B3?

The Emerson VE4005S1B3 is an 8-channel 4-20 mA analog output card used in the DeltaV DCS to drive field actuators, control valves, and positioners.

How many output channels are provided on the VE4005S1B3?

The card provides 8 independent 4-20 mA analog output channels.

What power sources are required for operation?

The card requires 12V DC power from the LocalBus backplane for internal logic, plus external 24V DC bulk field power connected at the terminal block to drive output loops.

What terminal block is required for installation?

The module requires a matching DeltaV 8-channel analog output terminal block mounted on an I/O interface carrier.

Does the VE4005S1B3 include channel-to-bus isolation?

Yes, the module incorporates electrical isolation to protect the central backplane and controller logic from field-side voltage spikes and ground loops.

 

Verification & Troubleshooting Notes

  • Status LED Inspection: Check the faceplate status LEDs upon power-up. A solid green status light confirms healthy LocalBus communication and active controller connection, while red or flashing states indicate internal faults or loss of backplane communication.
  • Output Current Verification: If an actuator fails to respond to a control signal, connect a digital multimeter in series with the loop at the terminal block to measure the 4-20 mA output current.
  • Field Power Inspection: Absence of current across all output channels usually indicates a missing or disconnected 24V DC field power supply at the terminal block.
  • Mechanical Keying Check: If the card does not seat smoothly into the carrier, inspect the mechanical polarization keys to ensure they match the slot assignment of the VE4005S1B3. Do not force insertion.