Description
Core Product Summary
The Emerson VE4050S2K1C1 is a DeltaV M-series 8-wide I/O interface carrier with a carrier shield bar and carrier extension cable. It provides the mounting, mechanical interconnection, LocalBus power distribution, and field-power distribution path for up to eight DeltaV I/O cards and eight I/O terminal blocks.
The carrier connects to a DeltaV M-series power/controller carrier, which supplies 12 V DC LocalBus power and carries data between the I/O interfaces and the controller. The VE4050S2K1C1 includes a shield bar for field-cable shielding and an extension cable for carrier-to-carrier connection. It is intended for DeltaV M-series traditional I/O installations and is not mechanically compatible with S-series controller carriers.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Emerson |
| Model / order number | VE4050S2K1C1 |
| Product type | 8-wide I/O interface carrier |
| Control system family | Emerson DeltaV M-series traditional I/O |
| Carrier format | Horizontal |
| I/O capacity | 8 I/O cards and 8 I/O terminal blocks |
| Included feature | Carrier shield bar |
| Included cable | Carrier extension cable |
| Interconnecting board current | 8 A maximum supplied to I/O cards |
| Shield power bus current | 6.5 A maximum supplied to field terminals |
| Power-injection connector | Left extender only |
| Dimensions | 16.5 cm H × 33.6 cm W × 3.1 cm D |
| Operating temperature | -40 to 70°C (-40 to 158°F) |
| Storage temperature | -40 to 85°C (-40 to 185°F) |
| Relative humidity | 5 to 95%, non-condensing |
| Protection rating | IP20 |
| Conformal coating | ISA-S71.04-1985 Class G3 |
| Hazardous-area location rating | ATEX EEx nA IIC T4; Class I, Division 2, Groups A–D, T4 |
| Mechanical shock | 10 g half-sine for 11 ms |
| Vibration | 1 mm peak-to-peak from 5 to 16 Hz; 0.5 g from 16 to 150 Hz |
Detailed Product Overview
The VE4050S2K1C1 is the horizontal carrier used to assemble DeltaV M-series traditional I/O interfaces in a control-system cabinet. It provides the physical mounting positions, keyed I/O interfaces, LocalBus interconnection, and field-power distribution required by DeltaV I/O cards and their terminal blocks.
The carrier accepts up to eight I/O cards and eight I/O terminal blocks. Each I/O card plugs into its matching keyed terminal block, while the carrier distributes 12 V DC LocalBus power from the adjacent power/controller carrier. The interconnecting board is rated for up to 8 A supplied to the installed I/O cards.
The integrated carrier shield bar supports field-cable shielding at the I/O interface. Its shield power bus is rated for up to 6.5 A supplied to field terminals. This arrangement allows shielded field cabling to be terminated and bonded at the carrier rather than requiring a separate shield-termination arrangement for each I/O point.
The VE4050S2K1C1 includes a carrier extension cable. It connects the I/O interface carrier to the DeltaV M-series power/controller carrier, which provides LocalBus power and data communication between the I/O subsystem and the controller. The carrier’s power-injection connector is provided on the left extender only.
The carrier is part of the DeltaV M-series architecture and is physically incompatible with S-series controller carriers. An S-series carrier can be connected only through the DeltaV SIS adapter. For a redundant controller configuration, an additional power/controller carrier is required.
The VE4050S2K1C1 is rated for -40 to 70°C operation, 5 to 95% non-condensing relative humidity, and IP20 protection. Its conformal coating meets ISA-S71.04-1985 Class G3 airborne-contaminant requirements.

VE4050S2K1C1

VE4050S2K1C1
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Control system | Emerson DeltaV distributed control system | The carrier is part of the DeltaV M-series traditional I/O subsystem. |
| I/O architecture | DeltaV M-series traditional I/O | Provides mounting and interconnection for M-series I/O interfaces. |
| Controllers | DeltaV M-series controllers | M-series I/O carriers are not compatible with S-series controllers and carriers. |
| Power/controller carrier | DeltaV M-series 2-slot power/controller carrier | Supplies LocalBus power and data communication to the I/O carrier. |
| I/O cards | Up to 8 DeltaV M-series I/O cards | Card and terminal-block keying must match. |
| Terminal blocks | Up to 8 DeltaV I/O terminal blocks | One terminal block is required for each installed I/O card. |
| LocalBus power | 12 V DC supplied through the power/controller carrier | The carrier distributes LocalBus power to installed I/O cards. |
| Interconnecting board | 8 A maximum to I/O cards | Do not exceed the carrier-level current limit. |
| Shield power bus | 6.5 A maximum to field terminals | Applies to the integrated carrier shield bar. |
| Extension | Included carrier extension cable | Connects the I/O carrier to the power/controller carrier. |
| Power injection | Left extender only | The power-injection connector is located on the left extender. |
| S-series connection | DeltaV SIS adapter required | Required only when connecting an S-series carrier. |
| Redundant controllers | Additional power/controller carrier required | Applies to redundant controller configurations. |
Dimensions, Mounting & Connection Notes
- Carrier size: 16.5 cm high × 33.6 cm wide × 3.1 cm deep.
- Carrier capacity: Eight I/O cards and eight I/O terminal blocks.
- Mounting format: Horizontal DeltaV M-series I/O carrier.
- Included shielding: Carrier shield bar for field-cable shield termination.
- Included cable: Carrier extension cable for connection to the power/controller carrier.
- Power injection: Provided through the left extender only.
- Current limits: 8 A maximum on the interconnecting board to I/O cards; 6.5 A maximum on the shield power bus to field terminals.
- Environmental installation limits: -40 to 70°C operating temperature, 5 to 95% non-condensing relative humidity, and IP20 protection.
- Environmental protection: Conformal coating meeting ISA-S71.04-1985 Class G3 airborne-contaminant requirements.
- Mechanical environment: 10 g half-sine shock for 11 ms; 1 mm peak-to-peak vibration from 5 to 16 Hz and 0.5 g from 16 to 150 Hz.
- Hazardous-area installation: Refer to Emerson Zone 2 installation instructions, document 12P2046, and/or Class I, Division 2 installation instructions, document 12P1293.
FAQ
What is the Emerson VE4050S2K1C1?
It is an Emerson DeltaV M-series 8-wide I/O interface carrier with a carrier shield bar and carrier extension cable.
How many I/O interfaces does it support?
It supports up to eight DeltaV I/O cards and eight I/O terminal blocks.
What is included with the VE4050S2K1C1?
It includes the 8-wide I/O interface carrier, carrier shield bar, and carrier extension cable.
Which DeltaV controllers can it be used with?
It is intended for DeltaV M-series controllers and M-series traditional I/O. It is not mechanically compatible with S-series controller carriers.
What power does the carrier distribute?
It distributes 12 V DC LocalBus power from the M-series power/controller carrier to the installed I/O cards.
What are the carrier current limits?
The interconnecting board is limited to 8 A supplied to I/O cards, and the shield power bus is limited to 6.5 A supplied to field terminals.
Can it be connected to an S-series carrier?
Only through the DeltaV SIS adapter; the M-series and S-series carriers are otherwise physically incompatible.
What environmental limits apply?
The carrier is rated for -40 to 70°C operation, 5 to 95% non-condensing relative humidity, and IP20 protection.
Documented Performance Data
| Metric | Value / Range | Operating condition |
|---|---|---|
| I/O capacity | 8 I/O cards and 8 terminal blocks | 8-wide M-series I/O carrier |
| Interconnecting board current | 8 A maximum | Power supplied to installed I/O cards |
| Shield power bus current | 6.5 A maximum | Power supplied to field terminals |
| Operating temperature | -40 to 70°C | Carrier installation environment |
| Relative humidity | 5 to 95%, non-condensing | Carrier installation environment |
| Mechanical shock | 10 g half-sine for 11 ms | Normal operating conditions |
| Vibration | 1 mm peak-to-peak, 5 to 16 Hz; 0.5 g, 16 to 150 Hz | Operating limit |