Sale!

EPRO PR6423/010-010+CON021 8 mm Eddy Current Sensor System

Item Verified Information
Manufacturer / product family EPRO / Emerson, PR6423 eddy-current sensor series
Exact configuration PR6423/010-010 + CON021
Sensor type Non-contact 8 mm eddy-current sensor
Linear measuring range 2 mm (80 mils)
Initial air gap 0.5 mm (20 mils)
Incremental scale factor 8 V/mm (203.2 mV/mil), ±5% over 0 to +45 °C
Deviation from best-fit straight line ±0.025 mm (±1 mil) over 0 to +45 °C
Target material Ferromagnetic steel; 42CrMo4 / AISI-SAE 4140 standard
Minimum shaft diameter 25 mm (0.79 in)
Categories: , , , , SKU: PR6423/010-010+CON021 Brand:

Description

Core Product Summary

The EPRO PR6423/010-010 + CON021 is a non-contact eddy-current measuring chain for rotating-machinery monitoring. It consists of an 8 mm PR6423 sensor with a 2 mm linear measuring range and 5 m armored cable, together with a CON021 signal converter.

The system measures radial and axial shaft dynamic displacement, position, eccentricity and speed/key signals. It is intended for critical turbomachinery such as steam, gas and hydro turbines, compressors, pumps and fans, where the conditioned converter output is supplied to machinery monitoring or protection equipment.

 

Key Technical Specifications

Item Verified Information
Manufacturer / product family EPRO / Emerson, PR6423 eddy-current sensor series
Exact configuration PR6423/010-010 + CON021
Sensor type Non-contact 8 mm eddy-current sensor
Linear measuring range 2 mm (80 mils)
Initial air gap 0.5 mm (20 mils)
Incremental scale factor 8 V/mm (203.2 mV/mil), ±5% over 0 to +45 °C
Deviation from best-fit straight line ±0.025 mm (±1 mil) over 0 to +45 °C
Target material Ferromagnetic steel; 42CrMo4 / AISI-SAE 4140 standard
Minimum shaft diameter 25 mm (0.79 in)
Cable length 5 m armored cable, identified by the /010 designation
Sensor thread M10 x 1
Sensor protection IP66
Converter CON021 signal converter
Converter frequency range 0–20 kHz at -3 dB with 10 nF load
Converter rise time Less than 15 µs with 1 nF load
Converter supply voltage -23 to -32 V DC for -4 to -20 V output; -21 to -32 V DC for -2 to -18 V output
Converter protection / weight IP20; 0.42 kg

 

Engineering Selection Highlights

  • Complete measuring chain: The PR6423/010-010 probe and CON021 converter form a matched eddy-current measuring system; the converter conditions the probe signal for the monitoring or protection system.
  • 2 mm measuring range: The /010 designation identifies the 2 mm-range sensor configuration, so the expected shaft movement and monitoring-system calibration must fit this span.
  • 5 m armored cable: The /010 designation also identifies the 5 m armored-cable version, which should match the installed distance and mechanical-protection requirements.
  • Shaft-displacement monitoring: The sensor measures relative radial and axial shaft displacement and dynamic vibration without contacting the shaft.
  • Calibration dependency: The 8 V/mm incremental scale factor, 0.5 mm initial air gap and 2 mm measuring range must match the configured converter and monitoring-system input.
  • Target requirements: The measured shaft or target must be ferromagnetic steel, with a minimum shaft diameter of 25 mm to keep target-size error negligible.
  • Converter supply match: The CON021 requires a negative DC supply within its documented range; the selected output range determines the required supply window.
PR6423/010-010+CON021

PR6423/010-010+CON021

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Sensor / converter pairing PR6423/010-010 probe with CON021 converter The CON021 completes the calibrated measuring chain and supplies the conditioned output signal.
Sensor family EPRO / Emerson PR6423 The PR6423/010-010 is an 8 mm eddy-current sensor in the PR6423 series.
Converter sensor compatibility PR6422, PR6423, PR6424, PR6425 and PR6426 sensors The CON021 is designed for EPRO PR642x eddy-current measuring chains.
Target material Ferromagnetic steel; 42CrMo4 / AISI-SAE 4140 standard The measured shaft or target surface must be compatible with the eddy-current measurement principle and calibration.
Target geometry Shaft diameter of 25 mm or greater Smaller target surfaces may introduce a target-size error of 1% or greater.
Monitoring-system input Conditioned converter output The output range and calibration must match the monitoring system input configuration.
Converter supply Negative DC supply Use -23 to -32 V DC for the -4 to -20 V output setting, or -21 to -32 V DC for the -2 to -18 V output setting.
Measurement applications Radial and axial shaft displacement, vibration, position, eccentricity and speed The appropriate measurement function depends on probe orientation, target geometry and monitoring-system configuration.

 

Dimensions, Mounting & Connection Notes

Item Verified Information
Sensor type 8 mm eddy-current sensor
Sensor thread M10 x 1
Cable length 5 m armored cable
Initial air gap 0.5 mm
Linear measuring range 2 mm
Sensor protection IP66
Converter mounting Panel-mount converter for installation in a mounting box
Converter protection IP20
Converter weight 0.42 kg
Converter operating temperature -30 to +100 °C
Converter shock and vibration 5 g at 60 Hz and +25 °C

The sensor must be mounted so that its tip is positioned at the specified initial air gap from the shaft or target surface. The 5 m armored cable connects the sensor to the CON021 converter. Cable shielding, grounding and separation from power wiring should follow the applicable installation requirements for the monitoring system.

 

Detailed Product Overview

The EPRO PR6423/010-010 + CON021 is a complete eddy-current measuring chain consisting of an 8 mm PR6423 sensor and a CON021 signal converter. The PR6423/010-010 is a 2 mm-range probe fitted with a 5 m armored cable, while the CON021 provides signal conditioning and the voltage output required by machinery monitoring or protection equipment.

The PR6423 sensor operates without contacting the shaft. It measures relative displacement between the sensor tip and a ferromagnetic steel target, with an incremental scale factor of 8 V/mm and a tolerance of ±5% over 0 to +45 °C. The initial air gap is 0.5 mm, and the deviation from the best-fit straight line is ±0.025 mm over the same temperature range.

The sensor is intended for cylindrical steel shafts with a minimum diameter of 25 mm. Smaller target surfaces may introduce an error of 1% or greater. The sensor uses an M10 x 1 housing thread and provides IP66 protection. The 5 m armored cable connects the probe to the CON021 converter.

The CON021 converts the sensor signal into a voltage output. Its frequency response extends to 20 kHz at -3 dB with a 10 nF load, and its rise time is less than 15 µs with a 1 nF load. The converter requires a negative DC supply: -23 to -32 V DC when configured for -4 to -20 V output, or -21 to -32 V DC when configured for -2 to -18 V output. It is IP20-rated, weighs 0.42 kg and operates from -30 to +100 °C.

For integration, the probe and converter should be treated as a calibrated pair. The target material, probe range, air gap, converter output range, monitoring-system input scaling and cable routing must all be consistent with the installed machinery-monitoring configuration.

 

Applications & System Role

The PR6423/010-010 + CON021 forms the front-end measuring chain of a machinery monitoring or protection system. The non-contact sensor observes shaft movement relative to its mounted position, while the CON021 converts the eddy-current sensor signal into a conditioned voltage output.

Typical measurement roles include radial shaft vibration, axial shaft displacement, shaft position, eccentricity and speed/key monitoring. In a turbomachinery protection architecture, the conditioned output can be supplied to a monitoring module or protection system for alarm evaluation, trip logic and machinery-condition analysis.

The system is intended for critical rotating equipment, including steam, gas and hydro turbines, compressors, pumps and fans. Its suitability depends on correct sensor mounting, target material, air-gap setting, cable integrity and matching converter output configuration.

 

FAQ

What is the EPRO PR6423/010-010 + CON021?
It is a non-contact eddy-current measuring chain consisting of an 8 mm PR6423 sensor with a 2 mm measuring range and 5 m armored cable, plus a CON021 signal converter.

What does the PR6423/010-010 measure?
It measures radial and axial shaft dynamic displacement, vibration, position, eccentricity and speed/key signals.

What does the CON021 do?
The CON021 conditions the PR6423 sensor signal and provides a voltage output for machinery monitoring or protection equipment.

What is the measuring range of this configuration?
The sensor has a 2 mm linear measuring range.

What is the sensitivity of the PR6423/010-010?
Its incremental scale factor is 8 V/mm (203.2 mV/mil), ±5%, over 0 to +45 °C.

What air gap is required?
The initial air gap is 0.5 mm.

What cable length does the /010 designation indicate?
The /010 designation identifies the 5 m armored-cable version of the PR6423/010 sensor.

What supply voltage does the CON021 require?
It requires -23 to -32 V DC for a -4 to -20 V output setting, or -21 to -32 V DC for a -2 to -18 V output setting.

Where is this measuring chain used?
It is used in critical turbomachinery such as steam, gas and hydro turbines, compressors, pumps and fans for shaft displacement, vibration, position, eccentricity and speed monitoring.