Sale!

GE 362A1052P104 RS-FS-9001 Two-Wire Flame Sensor

Parameter Value
Manufacturer GE Reuter-Stokes (General Electric)
Model RS-FS-9001
GE Part Number 362A1052P104
Sensor type Silicon carbide (SiC) photodiode UV sensor
Output signal 4–20 mA DC (two-wire)
Power supply 12–30 VDC (typical)
Response time < 25 ms
Primary application Gas turbine flame detection
Construction Stainless steel body and housing
Categories: , , , , SKU: 362A1052P104 RS-FS-9001 Brand:

Description

Core Product Summary

The GE Reuter-Stokes RS-FS-9001 (GE part number 362A1052P104) is a silicon carbide (SiC) photodiode-based ultraviolet flame sensor designed for continuous flame monitoring on industrial gas turbines. It provides a two-wire 4–20 mA output signal and is used to detect flame presence or absence for safe fuel control and trip functions.

Key Technical Specifications

Parameter Value
Manufacturer GE Reuter-Stokes (General Electric)
Model RS-FS-9001
GE Part Number 362A1052P104
Sensor type Silicon carbide (SiC) photodiode UV sensor
Output signal 4–20 mA DC (two-wire)
Power supply 12–30 VDC (typical)
Response time < 25 ms
Primary application Gas turbine flame detection
Construction Stainless steel body and housing

Detailed Product Overview

The RS-FS-9001 Flame Tracker uses a silicon carbide photodiode that is sensitive to the ultraviolet radiation produced by the combustion flame. This technology was developed to improve detection reliability in applications involving liquid fuels, dry low-NOx combustors, and water or steam injection, where shorter-wavelength UV can be attenuated.

The sensor delivers a continuous 4–20 mA current-loop signal proportional to flame intensity. It is intended for integration into the turbine control system to provide flame-on confirmation and rapid flame-out detection for fuel shutoff. The device is constructed for the high-temperature, high-vibration environment of gas turbine combustors and is commonly installed on GE and other heavy-duty gas turbines.

362A1052P104 RS-FS-9001

362A1052P104 RS-FS-9001

362A1052P104 RS-FS-9001

362A1052P104 RS-FS-9001

System Compatibility & Integration Requirements

  • Designed for use with GE gas turbine control systems and compatible burner management or turbine control platforms that accept a 4–20 mA flame intensity signal.
  • Two-wire loop-powered connection; requires a suitable 12–30 VDC power source and current-loop input on the control system.
  • Process connection is typically a ¾-inch NPT female thread (confirm exact configuration for the specific unit).
  • Electrical connector is a MIL-style multi-pin connector; use of the manufacturer-specified cable is required.
  • Installation must follow GE Reuter-Stokes and turbine OEM guidelines for sighting, cooling (if applicable), and hazardous-area compliance.
  • Hazardous-location ratings (Class I Division 2 / Zone 2, ATEX, IECEx) apply to the certified versions of this model.

Consult the official GE Reuter-Stokes Operation & Maintenance Manual and the specific gas turbine technical manuals for mounting, wiring, calibration, and functional test procedures.

FAQ

What is the GE RS-FS-9001 / 362A1052P104?
It is a silicon carbide ultraviolet flame sensor (Flame Tracker) used primarily for continuous flame monitoring on industrial gas turbines.

What signal does it provide?
A two-wire 4–20 mA DC current-loop output representing flame intensity.

What is the typical power requirement?
12–30 VDC.

What is the main application?
Detection of flame presence or absence in gas turbine combustors to support safe fuel control and trip functions.