GE Fanuc IC693ALG220 4-Channel Analog Input Module

  • Model: IC693ALG220
  • Brand: GE Fanuc / General Electric
  • Series: Series 90-30
  • Core Function: Converts analog voltage signals to PLC data
  • Product Type: Four-channel analog input module
  • Key Specs: ±10 VDC input range; 12-bit voltage resolution; 4 ms update rate
  • Current Input Option: −40 to +40 mA with precision shunt resistor
  • Input Filter: 17 Hz
  • Isolation: 1,500 VAC field side to logic side
  • Condition: Confirm New Original, New Surplus, or Refurbished (tested)
  • Availability: Legacy Series 90-30 module; verify stock and revision before purchase
Categories: , , , , SKU: IC693ALG220 Brand:

Description

Key Technical Specifications

Parameter Value
Catalog Number IC693ALG220
Product Family GE Fanuc Series 90-30
Product Type Analog voltage input module
Number of Channels 4
Voltage Input Range −10 to +10 VDC
Optional Current Range −40 to +40 mA with shunt resistor
Voltage Resolution 12-bit binary; 5 mV per LSB
Current Resolution 10-bit standard; up to 11-bit with precision resistor
Conversion Speed 1 ms per channel
Update Rate 4 ms for all four channels
Absolute Accuracy ±10 mV typical; ±30 mV maximum over operating temperature
Current Accuracy ±40 µA typical; ±160 µA maximum over operating temperature
Linearity Less than 1 LSB
Input Impedance Greater than 9 MΩ in voltage mode; 250 Ω in current mode
Input Filter Response 17 Hz
Field-to-Logic Isolation 1,500 VAC
Cross-Channel Rejection Greater than 80 dB
Backplane Consumption 27 mA from +5 VDC bus; 98 mA from isolated +24 VDC bus
Calibration Factory calibrated
PLC Data Format 16-bit two’s-complement format in %AI registers

 

The GE Fanuc IC693ALG220 is a four-channel analog input module for Series 90-30 PLC systems. It converts ±10 VDC signals into digital values and can also accept current signals when the specified shunt resistor is installed. Each channel converts in approximately 1 ms, producing a 4 ms update rate for all four channels.

The module provides factory calibration, 12-bit voltage resolution, 17 Hz input filtering, and 1,500 VAC field-to-logic isolation. Verify the exact hardware revision, wiring arrangement, current-input resistor, and PLC configuration before approving it as a replacement.

 

Troubleshooting Quick Reference

Symptom Possible Cause Relevance to This Part Quick Check Method Recommendation
Module is not detected by the PLC Backplane connection, rack power, slot configuration, or failed module ✅ High Check Series 90-30 rack power and inspect the module seating; review PLC hardware configuration Check rack and configuration before replacing the IC693ALG220
All four channels read zero Missing field supply, incorrect common wiring, or configuration fault ✅ Medium Measure the signal between each input terminal and COM with a calibrated multimeter Verify signal source, common reference, and terminal wiring
One channel is always full scale Open input, incorrect polarity, excessive signal, or failed channel ✅ High Measure the voltage directly at the channel and compare it with the PLC’s %AI value Isolate the field transmitter and test the channel with a known source
Reading is approximately half or double the expected value PLC scaling or two’s-complement interpretation error ❌ Low Compare raw %AI data with a known reference voltage and confirm engineering-unit scaling Correct the PLC scaling before replacing the hardware
Input value is noisy Ground loop, shield problem, unstable transmitter, or poor wiring ❌ Low Measure signal stability at the terminal and at the source; inspect shield termination Repair field wiring and grounding first
All channels show the same offset Common reference error, supply issue, or scaling error ❌ Low Apply a known voltage to each channel and compare raw counts Check COM wiring, transmitter reference, and PLC scaling
Current input reads incorrectly Shunt resistor absent, wrong value, or incorrect input configuration ✅ High Confirm the specified precision resistor is installed and measure loop current with a calibrated meter Do not use the voltage-input wiring assumptions for current operation
Input exceeds expected range Signal above ±10 VDC or noise spikes beyond the allowable input range ✅ High Measure peak signal voltage with a multimeter or oscilloscope Correct the transmitter range and protect the input before continuing
Channel response is slow Normal 17 Hz filtering, source impedance, or external signal conditioning ❌ Low Compare the response with a step change and verify the source impedance Confirm expected filter behavior before replacing the module
PLC reports an analog diagnostic fault Wiring, overrange, rack issue, or module electronics fault ✅ Medium Read the PLC fault table and compare diagnostics across all channels Resolve external faults first; replace only after a known-good signal test fails

If the fault remains unclear, contact technical support with photos of the module label, rack slot, terminal wiring, measured signal levels, %AI raw values, PLC fault table, and scaling configuration.

IC693ALG220

IC693ALG220

IC693ALG220

IC693ALG220

IC693ALG220

IC693ALG220

Frequently Asked Questions (FAQ)

 

What signal range does the IC693ALG220 accept?

The standard voltage range is −10 to +10 VDC across four analog input channels. The module can also process −40 to +40 mA signals when the applicable shunt resistor is installed.

 

Is the IC693ALG220 compatible with the Series 90-30 PLC?

Yes. It is designed for the GE Fanuc Series 90-30 backplane and uses the PLC’s +5 VDC and isolated +24 VDC supplies. Confirm the rack, slot configuration, hardware revision, and PLC programming software before installation.

 

Can I connect a 4–20 mA transmitter directly?

Do not assume direct compatibility. The current-input function requires the correct shunt resistor and wiring arrangement. Verify the resistor value, terminal connections, and current scaling in the applicable GE Fanuc manual.

 

What resolution does this module provide?

Voltage conversion uses 12-bit binary resolution, equivalent to 5 mV per LSB over the ±10 V range. Current resolution is lower unless the specified precision resistor is used.

 

Can I hot-swap the IC693ALG220?

Do not hot-swap it unless the machine documentation specifically authorizes that procedure. Remove power according to the Series 90-30 installation procedure, isolate the field signal, and follow site ESD controls before removing the module.

 

Will the PLC program remain after replacing the module?

The PLC program normally remains in the CPU, but the replacement must occupy the correct slot and use compatible hardware configuration settings. Confirm channel scaling, signal type, and %AI register mapping before returning the machine to automatic operation.

 

Why can this module cost less than a factory replacement?

The is a legacy Series 90-30 component commonly sourced through surplus, used, or refurbished inventory. Confirm whether the unit is New Original, New Surplus, or Refurbished (tested), and request the supplier’s test report, warranty, date code, and return terms.