Sale!

GE Fanuc IC693ALG390 2-Channel Analog Voltage Output

  • Model: IC693ALG390
  • Brand: GE Fanuc / General Electric
  • Series: Series 90-30
  • Core Function: Converts PLC data into analog voltage outputs
  • Product Type: Two-channel analog voltage output module
  • Key Specs: ±10 VDC output range; 2.5 mV resolution; 5 ms update rate
  • Output Channels: 2
  • Maximum Load: 5 mA per channel; 2 kΩ minimum load resistance
  • External Supply: 18–30 VDC
  • Isolation: 1,500 VAC field side to logic side
  • Condition: Confirm New Original, New Surplus, or Refurbished (tested)
  • Availability: Mature Series 90-30 product; verify revision, stock, and lead time
Categories: , , , , SKU: IC693ALG390 Brand:

Description

Key Technical Specifications

Parameter Value
Catalog Number IC693ALG390
Product Family GE Fanuc Series 90-30
Product Type Analog voltage output module
Number of Channels 2
Output Range −10 to +10 VDC
Resolution 12-bit binary plus sign; 13-bit effective resolution
Resolution per Count 2.5 mV
Update Rate Approximately 5 ms for both channels
Absolute Accuracy ±5 mV at 25 °C
Maximum Offset 1 mV
Maximum Output Load 5 mA per channel
Minimum Load Resistance 2 kΩ
Maximum Load Capacitance 2,000 pF
Nominal Isolated Supply +24 VDC from the backplane or user supply
External Supply Range 18–30 VDC
External Supply Ripple 10% maximum
Field-to-Logic Isolation 1,500 VAC
Backplane Consumption 32 mA from +5 VDC; 120 mA from isolated +24 VDC
PLC Data Format 16-bit two’s-complement data in %AQ registers
Calibration Factory calibrated

 

The GE Fanuc IC693ALG390 is a two-channel analog voltage output module for Series 90-30 PLC systems. It converts %AQ digital data into −10 to +10 VDC control signals for drives, valve positioners, controllers, and other analog field devices. Both channels update in approximately 5 ms.

The module provides 2.5 mV resolution, a 5 mA maximum output load per channel, and 1,500 VAC field-to-logic isolation. Confirm the required isolated +24 VDC supply, output load resistance, terminal wiring, and PLC scaling before installing a replacement.

 IC693ALG390

IC693ALG390

 IC693ALG390

IC693ALG390

Troubleshooting Quick Reference

Symptom Possible Cause Relevance to This Part Quick Check Method Recommendation
Module is not detected by the PLC Backplane connection, rack power, slot configuration, or failed module ✅ High Check Series 90-30 rack power, module seating, and hardware configuration Inspect the rack and configuration before replacing the IC693ALG390
Both outputs remain at zero Missing isolated +24 VDC supply, disabled logic, or incorrect %AQ command ✅ High Measure +24 VDC at the module supply terminals and monitor the raw %AQ registers Check supply and PLC command data before condemning the module
One output remains at zero Open output circuit, wiring fault, failed channel, or incorrect register mapping ✅ High Command a known %AQ value and measure DC voltage directly at the output terminal Test the channel with a high-impedance meter and known PLC command
Output is stuck near +10 VDC or −10 VDC Incorrect scaling, saturated command, or failed output amplifier ✅ High Write several known %AQ test values and measure the output at each step Verify scaling first; replace the module only if the output remains fixed
Output is consistently offset Calibration drift, incorrect scaling, or external load effect ✅ Medium Apply zero and midscale commands, then compare measured voltage with expected values Correct PLC scaling and verify load resistance before replacing the module
Output collapses when connected to the field device Load below 2 kΩ, excessive current demand, or short circuit ✅ High Measure load resistance with power isolated; compare output voltage unloaded and loaded Repair or replace the field device and keep the load within the 5 mA limit
Output is unstable Ground loop, noisy supply, excessive capacitance, or poor shielding ❌ Low Measure supply ripple and output stability with the field cable disconnected Correct grounding, shielding, and supply quality before replacing the module
Both channels show the same error Shared supply, common scaling issue, or backplane problem ❌ Low Test both channels with the same known command and inspect isolated +24 VDC Investigate common power and PLC data before replacing hardware
Output updates slowly Normal PLC scan behavior, program logic, or external filtering ❌ Low Trend the %AQ command and measure the output response to a step change Confirm the application scan time; the module update rate is approximately 5 ms
Field actuator moves in the wrong direction Reversed actuator logic, incorrect scaling, or output wiring polarity ❌ Low Compare commanded voltage, terminal polarity, and actuator direction Correct the application scaling or wiring; do not assume module failure

If the fault remains unclear, contact technical support with photos of the module label, terminal wiring, measured output voltages, %AQ values, rack status, PLC fault table, and field-device load measurements.

 

Frequently Asked Questions (FAQ)

 

What output signal does the IC693ALG390 provide?

The IC693ALG390 provides two analog voltage outputs, each ranging from −10 to +10 VDC. It is not a current-output module; use the correct GE Fanuc analog output model if the application requires 4–20 mA.

 

What is the maximum load for each output?

Each channel can drive up to 5 mA, which corresponds to a minimum load resistance of approximately 2 kΩ. Loads below that resistance can cause voltage sag, output heating, or inaccurate control.

 

Does the module require an external 24 VDC supply?

The module normally uses isolated +24 VDC from the Series 90-30 backplane. It also provides terminals for a user-supplied source, which must remain within the 18–30 VDC range and the specified ripple limit.

 

Can I connect a 4–20 mA actuator to this module?

No. The IC693ALG390 produces voltage, not current. A current-output module such as the appropriate Series 90-30 analog current-output model is required for a 4–20 mA actuator or valve positioner.

 

How is the analog value scaled in the PLC?

The PLC sends the output command through %AQ registers using a 16-bit two’s-complement format. Verify the configured engineering-unit scaling and test zero, midscale, and full-scale commands before connecting the actuator.

 

Can I hot-swap the ?

Do not hot-swap it unless the machine documentation explicitly authorizes the procedure. Remove power according to the Series 90-30 installation procedure, isolate the analog field circuit, and observe ESD precautions.

 

Why can this module cost less than a factory replacement?

The is a mature Series 90-30 component commonly sourced through surplus, used, or refurbished inventory. Confirm the exact condition, hardware revision, test report, warranty, terminal hardware, and return policy before purchase.