Description
Core Product Summary (Brand / Model / Key Attributes)
The GE IS220PDIOH1B is a discrete input/output (I/O) pack designed for the GE Mark VIe and Mark VIeS distributed control platforms. Mounted directly onto a companion TDBS or TDBT discrete terminal board, this module provides the electrical and network interface between one or two Mark VIe I/O Ethernet networks and field discrete signals, combining the functions of discrete input (PDIA) and discrete output (PDOA) packs into a single assembly.
Equipped with a BPPC processor board and a dedicated discrete data acquisition board, the IS220PDIOH1B processes up to 24 contact inputs and controls up to 12 relay output channels while monitoring terminal-board feedback signals. It operates from a 28.0 VDC nominal power input (27.4 VDC to 28.6 VDC range), connects to the terminal board via a DC-62 connector, communicates over dual RJ45 Ethernet ports, and supports Simplex as well as Triple Modular Redundant (TMR) configurations when configured in ControlST software V04.04 or later.
Key Technical Specifications
| Parameter | Verified Specification |
| Manufacturer / Brand | GE (General Electric) |
| Model / Order Number | IS220PDIOH1B |
| Product Series | Mark VIe / Mark VIeS Control Systems |
| Product Type | Discrete Input/Output (PDIO) I/O Pack |
| Internal Processor Board | BPPC processor board paired with discrete I/O acquisition board |
| Input Channel Capacity | Up to 24 discrete contact inputs (voltage rating set by companion terminal board) |
| Output Channel Capacity | Up to 12 relay command channels (Form C / terminal-board dependent) |
| Input Hardware Filter | 4 ms |
| Input Isolation | 1500 V optical group isolation on inputs |
| Power Supply Voltage | 28.0 VDC nominal (27.4 VDC min to 28.6 VDC max) |
| Power Connector | 3-pin power input connector |
| Network Interfaces | 2 × RJ45 Ethernet ports (I/O Net) |
| Terminal Board Interface | DC-62 connector (mates directly with TDBS or TDBT terminal boards) |
| Redundancy Support | Simplex (1 pack on TDBS) or TMR (3 packs on TDBT) |
| Diagnostic Interfaces | Front-panel LEDs (Power, ATTN, Ethernet link/activity, relay status) and local infrared serial port |
| Engineering Software | GE ControlST software suite V04.04 or later |
Detailed Product Overview
In GE Mark VIe control architectures, discrete field sensing and relay actuation are often separated across dedicated input and output packs. The GE IS220PDIOH1B consolidates both roles into a single compact I/O pack—functionally equivalent to combining a PDIA discrete input pack and a PDOA discrete output pack—reducing panel footprint and network port consumption on mixed discrete I/O points.
The module houses two internal circuit boards: a common Mark VIe BPPC processor board that manages Ethernet communications and system diagnostics, and a specialized discrete acquisition board that conditions up to 24 contact inputs and drives 12 relay command outputs. Field wetting voltage and relay contact ratings are determined by the underlying terminal board rather than the pack itself, allowing the same IS220PDIOH1B unit to serve 24 VDC, 48 VDC, or 125 VDC contact-wetting circuits depending on the mated terminal board suffix.
For system-level availability, the IS220PDIOH1B supports two redundancy topologies. In Simplex control mode, a single IS220PDIOH1B mounts on a TDBS terminal board with one or two I/O Ethernet connections. In Triple Modular Redundant (TMR) mode, three IS220PDIOH1B packs mount onto a single TDBT terminal board, each connected to an independent I/O Ethernet network to provide fault-tolerant voting and continuous operation during single-channel faults.

IS220PDIOH1B
Engineering Selection Highlights
- Combined 24 DI / 12 DO channel density → Replaces separate PDIA and PDOA packs on mixed discrete circuits, conserving enclosure mounting space and I/O Ethernet switch ports.
- BPPC processor revision (
H1B) → Uses the BPPC processor board supported in ControlST V04.04 and later; verify ControlST version compatibility before deploying into older Mark VIe installations. - Terminal-board-defined field voltage → Pairs with TDBSH2A/TDBTH2A (24 VDC), TDBSH4A/TDBTH4A (48 VDC), TDBSH6A/TDBTH6A (125 VDC), or TDBSH8A/TDBTH8A (24 VDC hazardous-location variants) to match existing field wetting voltages.
- Simplex and TMR scalability → Operates as a single pack on TDBS boards or in a three-pack TMR configuration on TDBT boards without changing the I/O pack part number.
- 1500 V optical group isolation and 4 ms hardware filtering → Protects internal pack electronics from field transients and suppresses contact bounce on discrete inputs.
- 27.4–28.6 VDC supply window → Requires a regulated 28.0 VDC Mark VIe power distribution bus to stay within specified operating limits.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| Simplex Terminal Boards | TDBSH2A (24 VDC), TDBSH4A (48 VDC), TDBSH6A (125 VDC), TDBSH8A (24 VDC HazLoc) |
Accepts one IS220PDIOH1B pack; TDBSH2A/4A/6A support WROB, WROF, and WROG relay option boards. |
| TMR Terminal Boards | TDBTH2A (24 VDC), TDBTH4A (48 VDC), TDBTH6A (125 VDC), TDBTH8A (24 VDC HazLoc) |
Accepts three IS220PDIOH1B packs; TDBTH2A/4A/6A support the WROB relay power distribution option board. |
| Control Software | GE ControlST Suite V04.04 or later | Required to recognize and configure the BPPC processor board inside the H1B hardware revision. |
| Power Supply | 28.0 VDC nominal (27.4 VDC to 28.6 VDC) via 3-pin connector | Supplied from the Mark VIe 28 VDC I/O power bus; verify supply voltage under full relay coil load. |
| Network Connection | Mark VIe I/O Ethernet Network (1 or 2 RJ45 ports) | Simplex mode supports 1 or 2 network links; TMR mode uses 1 network link per pack across 3 packs. |
| Hazardous Location Constraint | TDBSH8A / TDBTH8A terminal boards |
Do not use TDBSH8 or TDBTH8 terminal boards with intrinsic safety barriers. |
Dimensions, Mounting & Connection Notes
- Mounting Method: Plugs directly onto the mated TDBS or TDBT terminal board via its integrated DC-62 multi-pin connector and secures with the terminal board’s mechanical retaining hardware.
- Power Connection: Connects to the 28 VDC power distribution bus through the pack’s 3-pin power input receptacle.
- Ethernet Connections: Dual front-panel RJ45 ports accept standard industrial shielded twisted-pair Ethernet cables for Mark VIe I/O Net communication.
- Relay Load Verification: When driving inductive loads such as solenoid valves from the terminal board relay outputs, verify that solenoid coil voltage and current ratings remain within the contact limits of the specific TDBS/TDBT terminal board and installed option card.
- Local Diagnostic Port: Includes an infrared serial interface on the housing for local diagnostic communication alongside visual front-panel status LEDs.
FAQ
What is the GE IS220PDIOH1B? The GE IS220PDIOH1B is a Mark VIe discrete input/output (PDIO) I/O pack that provides 24 discrete contact inputs and 12 relay output command channels over an Ethernet I/O network.
What is the difference between the IS220PDIOH1A and IS220PDIOH1B? The IS220PDIOH1A uses a BPPB processor board, whereas the IS220PDIOH1B uses a functionally compatible BPPC processor board supported in ControlST software V04.04 and later.
Which terminal boards work with the IS220PDIOH1B? It is compatible with TDBS simplex terminal boards (TDBSH2A, TDBSH4A, TDBSH6A, TDBSH8A) and TDBT TMR terminal boards (TDBTH2A, TDBTH4A, TDBTH6A, TDBTH8A).
What power supply voltage does the IS220PDIOH1B require? It requires a nominal 28.0 VDC power input, with an allowable operating range of 27.4 VDC to 28.6 VDC.
Can the IS220PDIOH1B be used in Triple Modular Redundant (TMR) systems? Yes. Three IS220PDIOH1B packs can be mounted on a single TDBT terminal board, with each pack connected to its own I/O Ethernet network for TMR operation.
What software version is needed to configure the IS220PDIOH1B? Because it contains the BPPC processor board, the IS220PDIOH1B requires GE ControlST software suite V04.04 or later.
Verification & Troubleshooting Notes
- Input Power Check: Measure voltage at the 3-pin power connector to confirm it stays between 27.4 VDC and 28.6 VDC; voltages below 27.4 VDC can prevent pack initialization or cause intermittent resets.
- Front-Panel LED Diagnostics: Inspect the Power LED,
ATTN(Attention) LED, Ethernet port link/activity LEDs, and individual relay status LEDs; an illuminated or flashingATTNLED indicates a configuration mismatch, firmware discrepancy, or terminal board communication fault visible in ControlST. - DC-62 Connector Seating: If discrete inputs fail to register or terminal-board feedback faults appear, power down the pack and confirm that the DC-62 connector is fully and evenly mated to the TDBS/TDBT terminal board without bent pins.
- ControlST Version & Firmware Check: When replacing an older
PDIOH1Apack with an, verify that the site ControlST suite is V04.04 or later and download the matching pack firmware if prompted by ToolboxST. - Electrical & Hazardous-Area Safety: Disconnect 28 VDC pack power and isolate external field wetting/relay contact voltages before removing the pack from its terminal board, and observe area classification rules when servicing
TDBSH8A/TDBTH8Aassemblies.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626