Sale!

GE MM300-XELP3EABXXX Low Voltage Motor Management System

The GE MM300-XELP3EABXXX is a modular motor management system designed for low-voltage three-phase AC motor protection, control, automation, metering, and diagnostics. It belongs to the Multilin MM300 family and is intended for installation in NEMA or IEC Motor Control Centers or stand-alone panels.

Categories: , , , , SKU: MM300-XELP3EABXXX Brand:

Description

Core Product Summary

The GE MM300-XELP3EABXXX is a modular motor management system designed for low-voltage three-phase AC motor protection, control, automation, metering, and diagnostics. It belongs to the Multilin MM300 family and is intended for installation in NEMA or IEC Motor Control Centers or stand-alone panels.

This specific configuration provides no local control panel, English language support, a low-voltage power supply (24–48 V DC nominal), RS485 Modbus RTU plus Profibus DP slave and 10/100 Modbus TCP communications, Option 3 functionality (starter control, event recording, undervoltage autorestart, waveform capture, data logger, and FlexLogic programmable logic), Type E I/O (two 10 A form-A relays and six 20–60 V DC digital inputs), and base current/thermal protection elements. The modular architecture supports phase current inputs, optional voltage and RTD expansion, and simultaneous multi-protocol communication for integration into existing automation systems.

Key Technical Specifications

Parameter Value
Product type Modular low-voltage motor management system
Control panel None
Language English
Power supply Low: 24–48 V DC nominal
Communications RS485 Modbus RTU (standard) + Profibus DP Slave + 10/100 Modbus TCP
Options package Option 3: Starter control, event recorder, undervoltage autorestart, waveform capture, data logger, FlexLogic
I/O configuration Type E: 2 × 10 A form-A relays + 6 × 20–60 V DC digital inputs
Core protection Thermal overload, undercurrent, single-phase underpower, current unbalance, ground fault, locked/stalled rotor, starts-per-hour
Mounting DIN rail or panel (MCC bucket compatible)
Typical applications Low-voltage AC motors in MCC or panel environments

Detailed Product Overview

The MM300-XELP3EABXXX functions as a compact, modular digital motor protection and control device for low-voltage three-phase AC motors. It consolidates protection, starter control, process interlocks, metering, diagnostics, and multi-protocol communications into a single unit sized for Motor Control Center (MCC) buckets or panel mounting.

The advanced thermal model forms the core of motor protection. It accounts for overload curves, unbalance biasing, hot/cold safe-stall ratios, cooling time constants, and start supervision (starts-per-hour and time-between-starts). Additional elements include mechanical jam/stalled rotor detection, undercurrent and underpower, acceleration time monitoring, ground fault (core-balance or residual), and thermistor input support. Option 3 adds waveform capture, data logging, undervoltage autorestart, and FlexLogic programmable logic, enabling customized interlocking and control sequences without external PLCs in many applications.

The low-voltage power supply option (24–48 V DC) suits control circuits operating from DC sources common in certain industrial environments. Communications support simultaneous use of RS485 Modbus RTU, Ethernet Modbus TCP, and Profibus DP, allowing integration into existing SCADA, DCS, or fieldbus architectures. The absence of a local control panel means configuration, monitoring, and control are performed via the EnerVista MM300 Setup software, optional remote/handheld display, or the network protocols.

The modular hardware accepts phase current inputs (direct connection up to 5 A FLA or via CTs), optional voltage modules for expanded metering and voltage-based protection, and RTD modules for temperature biasing of the thermal model. Type E I/O provides DC-rated digital inputs and form-A trip-rated outputs suitable for interfacing with contactors, process interlocks, and status signaling. The design emphasizes reduced panel space, fewer discrete components, and simplified wiring compared with traditional discrete protection and control schemes.

Engineers select this exact order code when a low-voltage DC power supply, Profibus connectivity, FlexLogic capability, and DC digital inputs are required, while local operator interface is handled remotely or via software.

MM300-XELP3EABXXX

MM300-XELP3EABXXX

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
System family Multilin MM300 Motor Management System Modular base unit with expansion slots
Power supply 24–48 V DC nominal (low-voltage option) Confirm control power source matches rating before energizing
Communications RS485 Modbus RTU + Profibus DP + 10/100 Modbus TCP All ports can operate simultaneously; protocol-specific setpoints may require power cycle
I/O module Type E: 2 × form-A (10 A) relays + 6 × 20–60 V DC digital inputs DC input rating must match field device voltage
Software EnerVista MM300 Setup Required for full configuration, setpoint management, and firmware handling
Mounting DIN rail or panel / MCC bucket Designed for NEMA and IEC MCC environments
Companion items Optional graphical or basic control panel, handheld display, CT/VT modules, RTD modules Not included in this order code; order separately if local HMI or expanded sensing is needed

Dimensions, Mounting & Connection Notes

The MM300 uses a compact modular chassis designed for DIN-rail or panel mounting inside MCC buckets or control panels. Exact overall dimensions and weight are provided on the product label and in the mechanical installation drawings of the official technical documentation. Modules are inserted into designated slots; the power supply occupies the dedicated power slot, the CPU/communications module another, and I/O or protection modules the remaining expansion positions.

Terminal connections follow the module-specific layouts (phase current, digital inputs/outputs, communications, and control power). Proper grounding of the equipment ground terminal is required. Phase CT selection should keep full-load current near or slightly below CT primary rating for accuracy. Digital inputs on the Type E module are rated for 20–60 V DC. Always verify terminal assignments and torque values from the installation section of the technical manual for the installed modules.

FAQ

What is the GE -XELP3EABXXX?
It is a specific order configuration of the Multilin MM300 modular low-voltage motor management system providing protection, control, metering, diagnostics, and multi-protocol communications for three-phase AC motors.

Which power supply does this model use?
The low-voltage option rated 24–48 V DC nominal.

What communications protocols are included?
RS485 Modbus RTU (standard), Profibus DP Slave, and 10/100 Modbus TCP. These can operate simultaneously.

Does this unit include a local control panel?
No. The “X” designation indicates no control panel. Interface is via software, network protocols, or optional remote/handheld display.

What does Option 3 provide?
Starter control, event recorder, undervoltage autorestart, waveform capture, data logger, and FlexLogic programmable logic.

What I/O is included with the Type E module?
Two 10 A form-A relays and six digital inputs rated 20–60 V DC.

Is the MM300 suitable for MCC applications?
Yes. It is designed for both NEMA and IEC Motor Control Centers as well as stand-alone panel mounting.

What software is used for configuration?
EnerVista MM300 Setup software.