Description
Core Product Summary
The GE Multilin UR1HH is a high-range power supply module for the GE Multilin Universal Relay (UR) protection and control platform. It converts an AC or DC station supply into the internal operating power required by the UR relay chassis and its installed modules.
The UR1HH is the first-generation high-voltage power-supply option, designated UR-1H, with horizontal mounting indicated by the final H in the order code. It accepts a nominal 125–250 VDC input or 100–240 VAC input at 50/60 Hz. The module plugs into the UR chassis and supplies power to the relay’s processor, I/O, communications, and protection circuitry through the internal power-distribution arrangement.
Key Technical Specifications
| Parameter | Verified information |
|---|---|
| Manufacturer | GE Multilin |
| Exact model | UR1HH |
| Product type | Universal Relay power-supply module |
| System family | GE Multilin UR / Universal Relay |
| Power-supply generation | First-generation UR-1H |
| Voltage-range designation | H, high range |
| Mounting designation | H, horizontal mounting |
| Nominal DC input | 125–250 VDC |
| DC input limits | 88–300 VDC |
| Nominal AC input | 100–240 VAC, 50/60 Hz |
| AC input limits | 88–265 VAC, 25–100 Hz |
| Rated input current | 0.7 A |
| Mounting | Horizontal, 19-inch rack UR chassis |
| Module role | Supplies internal relay power from the station supply |
Engineering Selection Highlights
- UR-1H high-range supply: The UR1HH is a first-generation UR-1H high-range power supply, so it must be matched to a UR chassis configured for the high-voltage power-supply option.
- AC or DC station supply: The module accepts 125–250 VDC nominally or 100–240 VAC at 50/60 Hz, making it suitable for installations using either supply type within its documented range.
- Horizontal mounting requirement: The final H in UR1HH identifies horizontal mounting, which must match the physical orientation and chassis arrangement of the installed UR relay.
- Internal relay power role: The module powers the UR relay internally; it is not a standalone power supply and cannot function outside the UR chassis architecture.
- Chassis power distribution: The UR1HH receives the station supply and distributes internal operating power through the UR chassis to the relay’s functional modules.
- Input-range verification: The documented DC input window is 88–300 VDC, while the AC input window is 88–265 VAC at 25–100 Hz.
- Rated input current: The module’s rated input current is 0.7 A.

UR1HH
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Control platform | GE Multilin Universal Relay (UR) | The UR1HH is a power-supply module within the UR architecture. |
| Power-supply generation | First-generation UR-1H | The module is the high-range power-supply option for this generation. |
| Chassis orientation | Horizontal mounting | The final H in the order code identifies horizontal mounting. |
| Station supply | 125–250 VDC nominal or 100–240 VAC nominal | The module accepts either supply type within its documented ranges. |
| Internal power distribution | UR chassis power-distribution arrangement | The module supplies internal operating power to the relay’s functional modules. |
| Installation | Plug-in module in the UR chassis | The UR1HH must be installed in the UR relay chassis. |
Dimensions, Mounting & Connection Notes
The UR1HH is a plug-in power-supply module for the GE Multilin UR chassis. It mounts horizontally in a 19-inch rack UR arrangement, as identified by the final H in the order code.
The module receives the station AC or DC supply and distributes internal operating power through the UR chassis. Its input terminals and chassis wiring must be rated for the connected 125–250 VDC or 100–240 VAC supply. Installation and removal must follow the applicable UR relay hardware documentation and site electrical-safety procedures.
Detailed Product Overview
The GE Multilin UR1HH is a high-range power-supply module for the Universal Relay (UR) protection and control platform. It is the first-generation high-voltage power-supply option, designated UR-1H, with horizontal mounting indicated by the final H in the order code.
The module accepts a nominal 125–250 VDC input or 100–240 VAC input at 50/60 Hz. Its documented input limits are 88–300 VDC for DC operation and 88–265 VAC at 25–100 Hz for AC operation. The rated input current is 0.7 A. These input characteristics define the station-supply requirements for the module.
The UR1HH plugs into the UR chassis and supplies the internal operating power required by the relay’s processor, I/O, communications, and protection circuitry. Its role is to provide the power interface between the station supply and the internal power-distribution arrangement of the UR relay.
The UR architecture is modular. The power supply, CPU, CT/VT inputs, digital I/O, transducer I/O, communications, and process-bus modules operate together as one protection and control device. The UR1HH occupies the power-supply position in this architecture and must be matched to a UR chassis configured for the high-voltage power-supply option.
For installation, the module mounts horizontally in a 19-inch rack UR chassis. The final H in the order code identifies this mounting orientation. The module’s input terminals and chassis wiring must be rated for the connected supply, and installation and removal must follow the applicable UR relay hardware documentation and site electrical-safety procedures.
Applications & System Role
Within a GE Multilin Universal Relay, the UR1HH serves as the power-supply module that provides internal operating power from the station supply. Its role is to take the incoming AC or DC control supply and distribute the power required by the relay’s internal functional modules.
The UR architecture uses a modular chassis in which the power supply, CPU, CT/VT inputs, digital I/O, transducer I/O, communications, and process-bus modules operate together as one protection and control device. The UR1HH provides the power interface between the station supply and that internal modular architecture.
FAQ
What is the GE Multilin UR1HH?
It is a high-range power-supply module for the GE Multilin Universal Relay (UR) protection and control platform.
What input voltage does the UR1HH accept?
It accepts a nominal 125–250 VDC input or 100–240 VAC input at 50/60 Hz.
What are the documented input limits for the UR1HH?
The DC input window is 88–300 VDC, and the AC input window is 88–265 VAC at 25–100 Hz.
What does the final H in UR1HH mean?
The final H identifies horizontal mounting in the UR chassis.
Is the UR1HH a standalone power supply?
No. It is a plug-in module that supplies power internally to a GE Multilin UR relay chassis.
What is the rated input current of the UR1HH?
The module’s rated input current is 0.7 A.
Which UR power-supply generation does the UR1HH belong to?
It belongs to the first-generation UR-1H high-range power-supply generation.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626