Description
Core Product Summary
The GE Multilin UR1HH is a high-range power supply module for the GE Multilin Universal Relay (UR) protection and control platform. It converts an AC or DC station supply into the internal power required by the UR relay chassis and its installed modules.
The UR1HH is the first-generation high-voltage power supply option, designated UR-1H, with horizontal mounting indicated by the final H in the order code. It accepts a nominal 125–250 V DC input or 100–240 V AC input at 50/60 Hz. The module plugs into the UR chassis and supplies the relay’s processor, I/O, communications, and protection circuitry through the internal power distribution arrangement.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Brand / model | GE Multilin UR1HH |
| Product type | Universal Relay power supply module |
| System family | GE Multilin UR / Universal Relay |
| Power-supply generation | First-generation UR-1H |
| Voltage range designation | H — high range |
| Nominal DC input | 125–250 V DC |
| DC input limits | 88–300 V DC |
| Nominal AC input | 100–240 V AC, 50/60 Hz |
| AC input limits | 88–265 V AC at 25–100 Hz |
| Rated input current | 0.7 A |
| Mounting | Horizontal, 19-inch rack UR chassis |
| Module role | Supplies internal relay power from the station supply |
Engineering Selection Highlights
- The UR1HH is a first-generation UR-1H high-range power supply, so it must be matched to a UR chassis configured for the high-voltage power-supply option.
- Its 125–250 V DC nominal input suits station battery or DC control systems commonly used in protection and substation applications.
- Its 100–240 V AC input allows use where the UR relay is powered from an AC control supply rather than a DC battery system.
- The final H in UR1HH identifies horizontal mounting, which must match the physical orientation and chassis arrangement of the installed UR relay.
- The module powers the UR relay internally; it is not a standalone power supply and cannot function outside the UR chassis architecture.
- For redundant power-supply configurations, GE guidance for UR power supplies requires both installed modules to be of the same module type, for example 1H and 1H.

UR1HH

UR1HH
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Relay platform | GE Multilin Universal Relay (UR) family | The module is a chassis power supply for UR-based protection and control relays. |
| Power-supply range | High range, UR-1H generation | Use where the relay is configured for the 125/250 V high-range supply option. |
| DC supply | 125–250 V DC nominal; 88–300 V DC limits | Confirm that the station DC system remains within the permitted input window. |
| AC supply | 100–240 V AC nominal, 50/60 Hz; 88–265 V AC limits | Confirm frequency and voltage conditions before connection. |
| Mounting | Horizontal UR chassis arrangement | The final order-code character denotes horizontal mounting. |
| Redundant supply | Same module type required | In a dual-supply arrangement, both modules should be the same type, such as 1H and 1H. |
| Internal integration | Plugs into the UR chassis and supplies internal relay power | The module is dependent on the UR chassis and its installed CPU and I/O modules. |
Dimensions, Mounting & Connection Notes
- The UR1HH is a plug-in power supply module for the GE Multilin UR chassis.
- The order code identifies horizontal mounting in a 19-inch rack UR arrangement.
- It receives the station AC or DC supply and distributes internal operating power through the UR chassis.
- Installation and removal must follow the applicable UR relay hardware documentation and site electrical-safety procedures.
- The module’s input terminals and chassis wiring must be rated for the connected 125–250 V DC or 100–240 V AC supply.
Detailed Product Overview
The GE Multilin UR1HH is a power supply module within the Universal Relay architecture. GE’s UR family uses a modular chassis in which the power supply, CPU, CT/VT inputs, digital I/O, transducer I/O, communications, and process-bus modules operate together as one protection and control device. The UR1HH provides the power interface between the station supply and that internal modular architecture.
The order code can be read in two parts. UR-1H identifies the first-generation high-voltage power supply module, while the trailing H identifies horizontal mounting. This distinction is important because UR power supplies were offered in high- and low-voltage ranges and in different mounting orientations. A UR1HH is therefore not interchangeable in identification terms with a low-range supply or a vertically mounted variant.
For DC-powered installations, the module is rated for a nominal 125–250 V DC input, with an permitted input window of 88–300 V DC. For AC-powered installations, it accepts a nominal 100–240 V AC supply at 50/60 Hz, with an permitted range of 88–265 V AC at 25–100 Hz. The rated input current is 0.7 A. These values should be checked against the actual station supply, battery-system voltage, and expected supply variation before installation.
The UR1HH is part of the original UR-1H power-supply generation. GE later introduced redesigned UR power-supply modules, and GE guidance states that, where redundant supplies are used, both modules must match by module type—for example, 1H with 1H. This makes exact module identification important when maintaining a dual-supply UR installation.
Because the UR1HH supplies the relay’s internal circuitry, its correct selection affects more than simply providing voltage. It determines whether the UR relay can operate from the available station supply, whether the physical mounting arrangement matches the chassis, and whether a redundant supply configuration remains consistent. Engineering review should therefore focus on the installed UR relay model, chassis orientation, supply type, input-voltage window, and the module type already present in redundant configurations.
Applications & System Role
The UR1HH occupies the power-supply position in a GE Multilin Universal Relay. Its role is to take the station control supply—either high-range DC or AC—and provide the internal operating power needed by the relay’s CPU, CT/VT input modules, digital I/O, communications modules, and protection functions.
In a UR-based protection and control system, the power supply is a foundational module: the relay’s protection elements, local display, communications, event recording, and control outputs depend on it. The UR1HH is therefore relevant when configuring or maintaining a UR relay that uses the first-generation high-range power-supply option and is installed in a horizontally mounted UR chassis.
FAQ
What is the GE Multilin UR1HH?
It is a first-generation high-range power supply module for the GE Multilin Universal Relay family.
Which system does the UR1HH belong to?
It belongs to the GE Multilin UR / Universal Relay protection and control platform.
What input voltages does the UR1HH accept?
It accepts 125–250 V DC nominally, or 100–240 V AC at 50/60 Hz.
What are the permitted input limits?
The DC input window is 88–300 V DC; the AC input window is 88–265 V AC at 25–100 Hz.
What does the final H in UR1HH mean?
It identifies horizontal mounting in the UR chassis arrangement.
Can the UR1HH be used as a standalone power supply?
No. It is a plug-in module that supplies power internally to a GE Multilin UR relay chassis.
Is the UR1HH suitable for redundant power supplies?
It can be used in a redundant arrangement, but GE guidance requires both installed power-supply modules to be the same module type, such as 1H and 1H.

WhatsApp: +86 16626708626