Description
Core Product Summary
The GE RS-FS-9001 is a Reuter-Stokes Flame Tracker silicon carbide (SiC) ultraviolet flame sensor for continuous flame monitoring in combustion equipment. It detects UV radiation from the flame and transmits a proportional two-wire 4–20 mA signal to the associated control system.
The sensor uses a SiC photodiode behind a sapphire window, an AISI 316 stainless-steel body, and an argon-filled AISI 304 stainless-steel housing. It operates from a 12–30 VDC supply, responds in less than 25 milliseconds, and is intended for installation through a 3/4-inch NPT female process connection.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | GE Reuter-Stokes / Baker Hughes |
| Model | RS-FS-9001 |
| Product family | Flame Tracker |
| Sensor type | SiC two-wire UV flame sensor |
| Sensing element | Silicon carbide photodiode |
| Optical window | Sapphire |
| Output signal | 4–20 mA DC, two-wire current loop |
| Maximum output | Less than 21 mA |
| Response time | Less than 25 milliseconds |
| Supply voltage | 12–30 VDC |
| Supply current capability | Greater than 100 mA |
| Sensitivity | Greater than 5 mA at 1×1010 photons/in²/sec at 310 nm |
| Operating temperature | -40 °C to 150 °C |
| Body material | AISI 316 stainless steel |
| Housing | AISI 304 stainless steel, sealed and argon filled |
| Process connection | 3/4-inch NPT female |
| Electrical connector | MIL-C-38999 Series III, size 15, 5-pin |
| Documented connection cable | RS-E2-0285 or equivalent |
Engineering Selection Highlights
- The RS-FS-9001 is a two-wire, loop-powered 4–20 mA flame sensor, so its power and signal wiring share the same pair and must be planned as a current-loop circuit.
- Its SiC photodiode and sapphire window are intended for UV flame detection in high-temperature combustion environments.
- The documented operating limit is -40 °C to 150 °C; installations above this ambient temperature require a documented cooling arrangement.
- The sensor’s less-than-25-millisecond response time supports prompt flame-status reporting to the control system.
- Its AISI 316 stainless-steel body, sealed argon-filled AISI 304 housing, and sapphire window define the mechanical construction relevant to turbine and burner installations.
- The 3/4-inch NPT female process connection and MIL-C-38999 Series III electrical connector determine the mounting and cable-interface requirements.
- GE documentation specifies cable RS-E2-0285 or an equivalent connection to the turbine junction box.

RS-FS-9001

RS-FS-9001
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Control-system interface | Two-wire 4–20 mA current transmitter | The Flame Tracker connects to the controller as a conventional two-wire current transmitter. |
| Power supply | 12–30 VDC, capable of supplying more than 100 mA | The supply must support the sensor’s loop-current requirement. |
| Signal interpretation | Minimum flame intensity produces at least 5 mA | GE documentation identifies 5 mA as the output at the minimum specified flame intensity. |
| Flame-off threshold | 6.25% of 4–20 mA scale, equal to 5 mA | This is the documented flame-off set point in the quick-start guidance. |
| Flame-on threshold | 10% of 4–20 mA scale, equal to 5.6 mA | This is the documented flame-on set point in the quick-start guidance. |
| Connection cable | RS-E2-0285 or equivalent | The sensor connects to the turbine junction box through this documented cable or an equivalent. |
| Cooling requirement | Required above 150 °C ambient | Documented cooling methods include water cooling, ambient-air cooling, and pressurized-air cooling. |
Dimensions, Mounting & Connection Notes
| Item | Verified data |
|---|---|
| Process connection | 3/4-inch NPT female |
| Electrical connector | MIL-C-38999 Series III, size 15, 5-pin |
| Body material | AISI 316 stainless steel |
| Housing material | AISI 304 stainless steel, sealed and argon filled |
| Optical window | Sapphire |
| Operating temperature | -40 °C to 150 °C |
| Documented cable | RS-E2-0285 or equivalent |
| Water-cooling accessory | Water-cooling coil, Reuter-Stokes SP-566 / GE 353B3490G001 |
| Pressurized-air cooling accessory | Air-Cooling Can, Reuter-Stokes RS-E2-0259 / GE 07482SOCNL44821P01 |
The RS-FS-9001 mounts through its 3/4-inch NPT female process connection and uses a five-pin MIL-spec electrical connector. Where the ambient temperature exceeds the sensor’s 150 °C limit, the manufacturer documentation identifies water cooling, ambient-air cooling, or pressurized-air cooling as available methods.
Detailed Product Overview
The GE RS-FS-9001 is a Flame Tracker SiC two-wire flame sensor designed to monitor ultraviolet radiation from a combustion flame and report flame intensity as a 4–20 mA current signal. It combines a silicon carbide photodiode, an internal focusing lens, and a sapphire window in a sealed, argon-filled stainless-steel housing.
The sensor operates as a two-wire current transmitter: the same pair of conductors carries both the 12–30 VDC supply and the flame-intensity signal. The documented output range is 4–20 mA, with a maximum output below 21 mA. At the minimum flame intensity defined in GE specification 362A1052, the sensor provides at least 5 mA. The quick-start guidance therefore defines 5 mA as the flame-off set point and 5.6 mA as the flame-on set point.
The RS-FS-9001 responds in less than 25 milliseconds, allowing the control system to receive a prompt current-loop indication of flame status. Its sensitivity is specified as greater than 5 mA at 1×1010 photons/in²/sec at 310 nm. This sensitivity value defines the sensor’s response to the documented UV flame-radiation condition rather than a general-purpose fire-detection rating.
Mechanically, the sensor has an AISI 316 stainless-steel body, a sealed and argon-filled AISI 304 stainless-steel housing, and a sapphire window. It installs through a 3/4-inch NPT female process connection and uses a MIL-C-38999 Series III, size 15, five-pin electrical connector. GE documentation specifies connection to the turbine junction box using cable RS-E2-0285 or an equivalent.
The sensor’s documented operating temperature range is -40 °C to 150 °C. Where the installation location exceeds this limit, the operation and maintenance documentation identifies three cooling approaches: water cooling using the SP-566 / 353B3490G001 coil, ambient-air cooling, and pressurized-air cooling using the RS-E2-0259 Air-Cooling Can. The applicable cooling method and its installation requirements must match the actual turbine or burner installation.
Applications & System Role
The RS-FS-9001 is a flame-monitoring element in a combustion control or burner-management architecture. It views the flame, converts detected UV radiation into a 4–20 mA current signal, and provides the controller with a continuous indication of flame intensity.
In turbine and burner applications, this signal can be used for flame-presence verification and flame-loss logic. The documented quick-start guidance defines flame-off and flame-on thresholds at 5 mA and 5.6 mA respectively, giving the control system defined current levels for flame-status decisions.
The sensor is connected to the turbine junction box through RS-E2-0285 or an equivalent cable and is then integrated with the controller as a two-wire current transmitter. Its stainless-steel construction, sapphire window, and temperature limit define its suitability for high-temperature combustion installations where appropriate cooling is provided.
FAQ
What is the GE RS-FS-9001?
It is a GE Reuter-Stokes Flame Tracker silicon carbide ultraviolet flame sensor with a two-wire 4–20 mA output.
What does the RS-FS-9001 detect?
It detects ultraviolet radiation from a combustion flame using a silicon carbide photodiode behind a sapphire window.
What output does the sensor provide?
It provides a two-wire 4–20 mA DC current signal proportional to detected flame intensity.
What power supply does the RS-FS-9001 require?
It requires a filtered 12–30 VDC supply capable of providing more than 100 mA.
What is the sensor’s response time?
The documented response time is less than 25 milliseconds.
What are the flame-off and flame-on set points?
The documented flame-off set point is 6.25%, equal to 5 mA, and the flame-on set point is 10%, equal to 5.6 mA.
What is the maximum operating temperature?
The sensor operates from -40 °C to 150 °C. Above this range, a documented cooling method is required.
Which cable is specified for connection?
GE documentation specifies cable RS-E2-0285 or an equivalent connection to the turbine junction box.

WhatsApp: +86 16626708626