Sale!

HIMA X-AO1601 HIMax Analog Output Module

The HIMA X-AO1601 (also designated X-AO 16 01) is a 16-channel analog output module for the HIMax programmable electronic system. It provides 4…20 mA current outputs with pairwise galvanic isolation and is certified for SIL 3 applications.

Categories: , , , , SKU: X-AO1601 Brand:

Description

Core Product Summary

The HIMA X-AO1601 (also designated X-AO 16 01) is a 16-channel analog output module for the HIMax programmable electronic system. It provides 4…20 mA current outputs with pairwise galvanic isolation and is certified for SIL 3 applications.

The module is designed for insertion into HIMax base plate slots (excluding system bus reserved positions). Outputs support ohmic, inductive, and capacitive loads within specified limits. Configuration and diagnostics are performed within the SILworX engineering environment.

 

Key Technical Specifications

Parameter Value
Product type Analog output module for HIMax
Number of channels 16 (single-channel connection); 8 with redundant connection
Nominal output range 4…20 mA
Operating range 0…22.5 mA
Digital resolution 16-bit (10 000 digits in SILworX)
LSB value ≤ 2 µA
Ohmic load Max. 600 Ω
Inductive load Max. 1 mH
Capacitive load Max. 100 µF (parallel to ohmic load)
Settling time 5 ms
Shutdown time to safe state 16 ms
Supply voltage 24 VDC, −15 %…+20 %, ripple ≤ 5 %, SELV/PELV
Current input (all outputs active) Max. 1.3 A
Current input (all outputs off) Min. 0.6 A
Current input per channel pair 80 mA
Isolation Pairwise galvanically isolated from supply and remaining channel pairs
Safety integrity SIL 3
Operating temperature 0…+60 °C
Storage temperature −40…+85 °C
Degree of protection IP20

 

Detailed Product Overview

The X-AO1601 is an analog output module intended for use in the HIMA HIMax safety system. It delivers 16 current outputs in the 4…20 mA nominal range (operating range 0…22.5 mA). Channels are pairwise galvanically isolated from the supply voltage and from the remaining channel pairs, supporting both single-channel and redundant wiring configurations.

Each output is generated by a D/A converter and continuously monitored by independent internal measuring devices for functional testing. The module supports ohmic loads up to 600 Ω, inductive loads up to 1 mH, and capacitive loads up to 100 µF in parallel with the ohmic load. Settling time is 5 ms; transition to the safe state in the event of a fault occurs within 16 ms.

Power is supplied at 24 VDC with a tolerance of −15 % to +20 % and a maximum ripple of 5 % (SELV/PELV). Maximum current consumption with all outputs active is 1.3 A; minimum consumption with all outputs off is 0.6 A. Each channel pair draws up to 80 mA.

The module is configured and diagnosed in SILworX. It occupies a standard I/O slot on a HIMax base plate (system bus slots are reserved). Status and diagnostic information is available via module LEDs and the engineering system. The module is listed by HIMA as suitable for SIL 3 applications.

 X-AO1601

X-AO1601

 X-AO1601

X-AO1601

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
System family HIMA HIMax Inserted in base plate I/O slots
Slot restriction Any base plate slot except system bus reserved positions Refer to HIMax System Manual
Engineering tool SILworX Required for configuration and diagnostics
Safety integrity SIL 3 Pairwise galvanic isolation supports safety applications
Field connection Via connector board / termination board Module and connector board form the field interface
Related termination Compatible with HIMA-specific termination boards (e.g., for single or redundant mode) Separate accessory

 

Dimensions, Mounting & Connection Notes

  • Mounting: HIMax base plate slot (I/O positions)
  • Degree of protection: IP20
  • Operating temperature: 0…+60 °C
  • Storage temperature: −40…+85 °C
  • Connection: Module interfaces to the field via a dedicated connector board; power and signals follow HIMax system conventions
  • Isolation: Channel pairs are galvanically isolated from each other and from the supply

 

FAQ

What is the HIMA X-AO1601?
It is a 16-channel analog output module for the HIMax system providing 4…20 mA current outputs with pairwise galvanic isolation and SIL 3 capability.

How many channels does the module have?
It offers 16 analog outputs in single-channel connection mode or 8 outputs in redundant connection mode.

What is the output signal range?
Nominal range is 4…20 mA; operating range is 0…22.5 mA.

What load types are supported?
Ohmic loads up to 600 Ω, inductive loads up to 1 mH, and capacitive loads up to 100 µF in parallel with the ohmic load.

What supply voltage is required?
24 VDC with a tolerance of −15 % to +20 % and ripple ≤ 5 % (SELV/PELV).

Is the module SIL certified?
Yes. It is listed for SIL 3 applications within the HIMax system.

Where can the module be installed?
In any HIMax base plate I/O slot except those reserved for system bus modules.