Description
Core Product Summary
The Honeywell S81-U1002-1 is the central processing unit (CPU) card for the H-S81-HS multifunction safety control panel system. It contains the microcontroller, memory, watchdog, and Ethernet interface that process all information from the other system cards. The module supports both single and dual-redundant operation up to SIL3 in accordance with IEC 61508 and can be hot-swapped.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Manufacturer | Honeywell |
| Model | S81-U1002-1 |
| Product type | CPU Card / System Central Unit |
| System | H-S81-HS (S81) control panel |
| Microcontroller | Renesas (Hitachi) H8-2318 at 25 MHz |
| RAM | 4 MB (512K × 8) buffered static RAM with lithium battery |
| Flash memory | 2 MB expandable |
| Ethernet | 10/100BaseT via RJ45 |
| Watchdog | External to CPU |
| Redundancy | Single or parallel dual-CPU (up to SIL3) |
| Supply voltage | 22–29 VDC |
| Quiescent current | 70 mA |
| Operating temperature | –5 °C to +50 °C |
| Storage temperature | –30 °C to +80 °C |
| Humidity | 95% RH non-condensing |
| Mounting | Front plug-in with locking screws |
| Hot-swap capability | Yes |
Detailed Product Overview
The S81-U1002-1 serves as the central processing unit of the H-S81-HS system. It receives and processes data from all other cards in the panel, executes the application logic, manages communications, and maintains system time via a built-in clock.
Key internal components include a 25 MHz Renesas H8-2318 microcontroller, battery-backed static RAM, expandable flash memory for the operating system and configuration, an external watchdog for software cycle monitoring, hardware self-diagnostics, and a dedicated CPLD for communication management.
In redundant configuration, two CPU cards operate in parallel. Both process incoming information, but only the primary CPU issues commands. If the primary fails, the secondary CPU takes over automatically without interruption of the control cycle or loss of events. Insertion of a second CPU is recognized automatically.
An RJ45 Ethernet port allows interconnection of multiple S81 panels or connection to a supervisory PC for remote management and event transfer.

S81-U1002-1

S81-U1002-1
System Compatibility & Integration Requirements
- Designed exclusively for the Honeywell H-S81-HS (S81) multifunction safety control panel system.
- Installs in the central unit rack of the S81 system.
- Requires system power supply in the range 22–29 VDC.
- Supports single-CPU or dual-CPU redundant architectures for applications up to SIL3 (IEC 61508).
- Compatible with other S81 system modules (I/O cards, display modules, power supply units, etc.).
- Front-panel plug-in installation with locking screws; hot-swap capable under system guidelines.
- Configuration programs can be transferred on-line.
- Ethernet networking enables multi-panel systems and supervisory PC connectivity.
Always refer to the official Honeywell H-S81-HS Installation & Operation Manual for rack placement, cabling, redundancy setup, and safety-related application requirements.
Status Indications
Front-panel LEDs:
- Link (Green)
- Activity (Green)
- Run (Green)
- Wdo – Watchdog (Yellow)
FAQ
What is the Honeywell S81-U1002-1?
It is the central CPU card for the Honeywell H-S81-HS safety control panel system.
Does it support redundancy?
Yes. It can operate in single or dual-CPU parallel redundant configuration suitable for applications up to SIL3.
Can the card be replaced under power?
Yes, it is hot-swappable.
What communication interface does it provide?
A 10/100BaseT Ethernet port with RJ45 connector for panel interconnection or supervisory PC connection.
What is the supply voltage range?
22–29 VDC.