Honeywell S81-U1002-1 Central Unit CPU Module

Parameter Value
Manufacturer Honeywell
Model S81-U1002-1
Product type CPU Card / System Central Unit
System H-S81-HS (S81) control panel
Microcontroller Renesas (Hitachi) H8-2318 at 25 MHz
RAM 4 MB (512K × 8) buffered static RAM with lithium battery
Flash memory 2 MB expandable
Ethernet 10/100BaseT via RJ45
Watchdog External to CPU
Categories: , , , , SKU: S81-U1002-1 Brand:

Description

Core Product Summary

The Honeywell S81-U1002-1 is the central processing unit (CPU) card for the H-S81-HS multifunction safety control panel system. It contains the microcontroller, memory, watchdog, and Ethernet interface that process all information from the other system cards. The module supports both single and dual-redundant operation up to SIL3 in accordance with IEC 61508 and can be hot-swapped.

Key Technical Specifications

Parameter Value
Manufacturer Honeywell
Model S81-U1002-1
Product type CPU Card / System Central Unit
System H-S81-HS (S81) control panel
Microcontroller Renesas (Hitachi) H8-2318 at 25 MHz
RAM 4 MB (512K × 8) buffered static RAM with lithium battery
Flash memory 2 MB expandable
Ethernet 10/100BaseT via RJ45
Watchdog External to CPU
Redundancy Single or parallel dual-CPU (up to SIL3)
Supply voltage 22–29 VDC
Quiescent current 70 mA
Operating temperature –5 °C to +50 °C
Storage temperature –30 °C to +80 °C
Humidity 95% RH non-condensing
Mounting Front plug-in with locking screws
Hot-swap capability Yes

Detailed Product Overview

The S81-U1002-1 serves as the central processing unit of the H-S81-HS system. It receives and processes data from all other cards in the panel, executes the application logic, manages communications, and maintains system time via a built-in clock.

Key internal components include a 25 MHz Renesas H8-2318 microcontroller, battery-backed static RAM, expandable flash memory for the operating system and configuration, an external watchdog for software cycle monitoring, hardware self-diagnostics, and a dedicated CPLD for communication management.

In redundant configuration, two CPU cards operate in parallel. Both process incoming information, but only the primary CPU issues commands. If the primary fails, the secondary CPU takes over automatically without interruption of the control cycle or loss of events. Insertion of a second CPU is recognized automatically.

An RJ45 Ethernet port allows interconnection of multiple S81 panels or connection to a supervisory PC for remote management and event transfer.

S81-U1002-1

S81-U1002-1

S81-U1002-1

S81-U1002-1

System Compatibility & Integration Requirements

  • Designed exclusively for the Honeywell H-S81-HS (S81) multifunction safety control panel system.
  • Installs in the central unit rack of the S81 system.
  • Requires system power supply in the range 22–29 VDC.
  • Supports single-CPU or dual-CPU redundant architectures for applications up to SIL3 (IEC 61508).
  • Compatible with other S81 system modules (I/O cards, display modules, power supply units, etc.).
  • Front-panel plug-in installation with locking screws; hot-swap capable under system guidelines.
  • Configuration programs can be transferred on-line.
  • Ethernet networking enables multi-panel systems and supervisory PC connectivity.

Always refer to the official Honeywell H-S81-HS Installation & Operation Manual for rack placement, cabling, redundancy setup, and safety-related application requirements.

Status Indications

Front-panel LEDs:

  • Link (Green)
  • Activity (Green)
  • Run (Green)
  • Wdo – Watchdog (Yellow)

FAQ

What is the Honeywell S81-U1002-1?
It is the central CPU card for the Honeywell H-S81-HS safety control panel system.

Does it support redundancy?
Yes. It can operate in single or dual-CPU parallel redundant configuration suitable for applications up to SIL3.

Can the card be replaced under power?
Yes, it is hot-swappable.

What communication interface does it provide?
A 10/100BaseT Ethernet port with RJ45 connector for panel interconnection or supervisory PC connection.

What is the supply voltage range?
22–29 VDC.