Description
Core Product Summary
The Honeywell SAI-1620M is a safe high-density analog input module designed for the Safety Manager control architecture. It provides 16 analog input channels with a specified input range of 0–4.1 V and a 12-bit analog-to-digital converter. The module also includes an external voltage readback input for monitoring a voltage signal within the same range.
Integration requires attention to field-signal conditioning. The module’s analog inputs accept voltage signals, so standard 0–20 mA or 4–20 mA instrumentation signals require a compatible field termination or analog input conversion arrangement. Documented options include the TSAI-1620m, TSHART-1620m, TSGAS-1624, TSFIRE-1624, and BSAI-1620mE, subject to the applicable signal type and system configuration. The full module designation should be checked against the installed system’s hardware documentation before procurement.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Honeywell |
| Product model | SAI-1620M |
| Product type | Safe high-density analog input module |
| System family | Safety Manager |
| Analog input channels | 16 |
| Analog input range | 0–4.1 V |
| External voltage readback range | 0–4.1 V |
| Input resistance | Greater than 1 MΩ |
| Maximum load capacitance | 100 nF |
| A/D converter resolution | 12 bit |
| A/D converter inaccuracy | ±1 LSB |
| Module inaccuracy | Less than 0.25% |
| Absolute maximum input signal | ±36 V DC |
| Channel crosstalk | Greater than 60 dB |
| Power requirements | 5 V DC, 35 mA; 24 V DC, 35 mA |
| Module space requirement | 4 TE, 3 HE (4 HP, 3U) |
| Documented type numbers | FS-SAI-1620m, FC-SAI-1620m, FA-SAI-1620m |
Detailed Product Overview
Role in the Safety Manager architecture
The SAI-1620M acquires analog voltage signals for processing within a Honeywell Safety Manager system. Its 16-channel design allows multiple analog measurement points to be handled by one input module, while the shared isolated analog 0 V reference serves the module’s input channels.
The documented safety classification for the input channels is SIL 3 in accordance with IEC 61508. This classification describes the documented module function and does not, by itself, establish the safety integrity level of an entire installed system. The application, system architecture, configuration, and validation remain relevant to the final safety determination.
Field-signal conditioning is a key selection requirement
The input range is an important distinction when matching the module to field instrumentation. The SAI-1620M’s specified input is 0–4.1 V; it should not be treated as a direct 4–20 mA input card.
Honeywell’s documented architecture provides field termination assemblies and an analog input conversion module for signal conditioning. Depending on the application, these include the TSAI-1620m, TSHART-1620m, TSGAS-1624, TSFIRE-1624, and BSAI-1620mE.
Thermocouple and PT100 sensor signals also require appropriate conversion to a supported current-signal format before they can be used with this input arrangement. The required conversion hardware depends on the sensor and the installed configuration.
Measurement resolution and input limits
The 12-bit analog-to-digital converter determines the number of digital levels available to represent the input voltage. Its stated conversion inaccuracy is ±1 LSB, while the documented module inaccuracy is less than 0.25%. These are separate specifications and should not be treated as interchangeable accuracy figures.
The input resistance exceeds 1 MΩ, and the maximum load capacitance is 100 nF. The absolute maximum input signal is ±36 V DC. This absolute maximum is an electrical limit, not a normal operating range; the specified measurement range remains 0–4.1 V.
Procurement and engineering identification
The SAI-1620M family includes FS, FC, and FA type designations. Selecting a part by the shared model stem alone can leave important configuration details unresolved. Match the complete type number, including any suffix or revision marking, to the installed hardware and the project bill of materials.

SAI-1620M

SAI-1620M
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Control system | Honeywell Safety Manager | Confirm the installed system configuration and the exact module type. |
| Analog input signal | 0–4.1 V | Match the conditioned field signal to the module’s input range. |
| 0–20 mA field signals | Require signal conversion | Use an applicable field termination assembly or analog input conversion arrangement. |
| Field termination options | TSAI-1620m, TSHART-1620m, TSGAS-1624, TSFIRE-1624 | Select according to the field instrument and project configuration. |
| Backplane conversion option | BSAI-1620mE | The documented location is the programming connector (Px) on the rear of the I/O backplane in the 19-inch chassis. |
| Thermocouple and PT100 signals | Require dedicated conversion to 0(4)–20 mA | Select the appropriate converter and associated interface hardware. |
| Electrical supply | 5 V DC and 24 V DC, each specified at 35 mA | Account for both listed supply requirements in the applicable system design. |
| Physical space | 4 TE, 3 HE (4 HP, 3U) | Check available rack or chassis space before installation. |
Dimensions, Mounting & Connection Notes
The documented module space requirement is 4 TE by 3 HE, also expressed as 4 HP by 3U. This identifies the module’s space allocation; it should not be interpreted as a complete mechanical envelope measurement.
The module uses a voltage-input interface, and current-loop instrumentation requires the appropriate signal-conditioning arrangement. Before installation, confirm the connector coding, backplane position, field termination assembly, and wiring configuration against the installed Safety Manager hardware documentation.
The available exact-model information does not establish a single physical dimension set, terminal torque, wire-size limit, or clearance requirement applicable to every SAI-1620M variant. Those values should not be inferred from another module in the family.
FAQ
What is the Honeywell SAI-1620M?
The Honeywell SAI-1620M is a 16-channel safe high-density analog input module for the Safety Manager system. It acquires analog voltage signals within a specified range of 0–4.1 V.
How many analog input channels does the SAI-1620M provide?
The module provides 16 analog input channels. It also has an external voltage readback input with a range of 0–4.1 V.
Does the SAI-1620M accept 4–20 mA signals directly?
No. The documented input range is 0–4.1 V. A 4–20 mA field signal requires an appropriate signal-conversion arrangement before reaching the module’s voltage input.
Which signal-conversion modules are documented for the SAI-1620M?
Documented options include TSAI-1620m, TSHART-1620m, TSGAS-1624, TSFIRE-1624, and BSAI-1620mE. The appropriate choice depends on the field signal and the installed system configuration.
What is the A/D converter resolution?
The SAI-1620M uses a 12-bit analog-to-digital converter, with a specified converter inaccuracy of ±1 LSB.
What power requirements should be considered?
The documented requirements are 5 V DC at 35 mA and 24 V DC at 35 mA. Both listed supply requirements should be considered when checking system power provisions.
Which exact model designation should be ordered?
Honeywell documentation identifies FS-SAI-1620m, FC-SAI-1620m, and FA-SAI-1620m as type numbers in this module family. The complete designation should match the installed system’s required variant and the project documentation.