Core Product Summary (Brand / Model / Key Attributes)
The Honeywell SPS5710-2-LF (part number 51198685-100) is a dedicated power supply module designed for the Honeywell Experion Process Knowledge System (PKS) Series C hardware architecture. Operating within the Series C infrastructure, this module converts incoming power into regulated 24 VDC output to power control components, C300 controllers, and Series C Input/Output (I/O) modules mounted across system backplanes.
Engineered for continuous industrial process control environments, the SPS5710-2-LF provides up to 20 A of continuous output current at 24 VDC. The unit accepts a wide range AC input voltage (100–240 VAC at 47–63 Hz), allowing direct integration into global power infrastructure without requiring external steps or transformers. Featuring integrated protection circuitry against overvoltage, overcurrent, and output short circuits, the module supports redundant system configurations to safeguard critical automation loops against power-related downtime.
Key Technical Specifications
| Specification Category | Verified Technical Parameter / Value |
| Product Type / Series | System Power Supply Module / Experion PKS Series C |
| Honeywell Part Number | 51198685-100 |
| Model Identifier | SPS5710-2-LF |
| Nominal Input Voltage | 100–240 VAC |
| Input Frequency Range | 47–63 Hz |
| Maximum Input Current | 10 A |
| Output Voltage | 24 VDC (Adjustable range 24–26 VDC) |
| Maximum Output Current | 20 A |
| Energy Conversion Efficiency | > 85% |
| Protective Functions | Overvoltage, overcurrent, and short-circuit protection |
| Operating Temperature | -40 °C to +70 °C |
| System Backplane / Chassis | Honeywell Experion Series C carrier / rack assembly |
Detailed Product Overview
The Honeywell SPS5710-2-LF serves as a primary power delivery component within Honeywell Experion PKS Series C control hardware assemblies. It distributes steady DC voltage directly across the backplane to support C300 controllers, fieldbus interfaces, and Series C I/O modules, maintaining system stability during operational load fluctuations.
Designed for demanding process control installations—such as refining, chemical processing, power generation, and oil and gas facilities—the power supply handles wide input variations from standard plant mains (100–240 VAC). Internal conversion circuits maintain high energy efficiency (exceeding 85%), reducing localized heat dissipation inside switchgear cabinets and control enclosures.
For mission-critical applications where continuous control availability is mandatory, the SPS5710-2-LF supports redundant dual-module setups. In a redundant pair, load-sharing and diode isolation mechanisms allow continuous operation should one power feed or module encounter a fault. Built-in electronic safety limits protect downstream automation hardware by automatically interrupting or regulating output under fault conditions such as overvoltage spikes, overcurrent draw, or physical short circuits on the field wiring side.

SPS5710-2-LF

SPS5710-2-LF
Engineering Selection Highlights
- Series C Architecture Compatibility: Engineered specifically to interface with Honeywell Experion PKS Series C carriers, backplanes, and C300 controller hardware.
- High Output Capability: Delivers a continuous output rating of 24 VDC at up to 20 A to satisfy the energy demands of high-density I/O configurations.
- Universal AC Input Support: Accepts 100–240 VAC input at 47–63 Hz, eliminating the need for dedicated region-specific transformers or voltage selection switches.
- Redundancy Infrastructure: Enables parallel, dual-supply installations across Series C backplanes to prevent single-point power failures from interrupting process control loops.
- Integrated Safety Features: Contains automatic electronic protections for overvoltage, overcurrent, and continuous short-circuit conditions to shield backplane electronics.
Dimensions, Mounting & Connection Notes
- Mounting Configuration: Installs directly into the Honeywell Series C rack/carrier assembly via dedicated backplane connectors.
- Cooling & Clearances: Relies on standard enclosure convection and system airflow; maintain standard cabinet clearance around ventilation slots to allow heat dissipation across the operating temperature range (-40 °C to +70 °C).
- Terminal Wiring: Input power connections utilize industrial screw-terminal blocks. Ensure correct wire gauge selection corresponding to the maximum 10 A AC input current rating.
- Grounding Requirements: Chassis earth ground must be properly tied to the main cabinet ground bus to minimize noise coupling and maintain overvoltage protection performance.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note | |—|—| | System Architecture | Honeywell Experion PKS Series C | Mounts directly into designated power supply slots on Series C assembly carriers. | | Associated Hardware | Honeywell C300 Controller & Series C I/O Modules | Feeds power across the backplane bus to operational controllers and interface channels. | | Primary Input Power | 100–240 VAC, 47–63 Hz single-phase mains | Ensure power feed wiring is sized to handle up to 10 A input current draw. | | Configuration Setup | Standalone single supply or dual-redundant pair | In redundant pairs, both units share the load and provide automatic failover capability. |
FAQ
What is the Honeywell SPS5710-2-LF?
It is a 24 VDC, 20 A system power supply module manufactured for the Honeywell Experion PKS Series C automation platform.
What is the Honeywell part number for this module?
The associated Honeywell order/part number for the SPS5710-2-LF is 51198685-100.
Which control system uses the SPS5710-2-LF?
It is specifically designed for Honeywell Experion PKS systems utilizing Series C hardware, including C300 controllers and Series C I/O racks.
What is the input voltage range for this module?
The module accepts a wide AC input voltage range of 100–240 VAC at an input frequency of 47–63 Hz.
What output power does the module supply?
It provides a regulated output voltage of 24 VDC (adjustable between 24–26 VDC) with a maximum continuous output current of 20 A.
Does the SPS5710-2-LF support redundant power setups?
Yes, it can be installed in redundant dual-module configurations to ensure uninterrupted power delivery to the Series C backplane if one power module or supply line fails.
Verification & Troubleshooting Notes
- No Backplane Output Voltage: Verify incoming line voltage at the terminal connections (100–240 VAC). Confirm that the module is fully seated into the Series C carrier slot connector.
- Overcurrent / Trip Condition: If the unit cuts power or trips protection circuits, check downstream Series C I/O modules and backplane rails for short circuits or total load current exceeding 20 A.
- Thermal Shutdown Risk: Ensure panel ambient temperatures stay within the operational limits of -40 °C to +70 °C and verify that cooling vents are clear of dust accumulation or airflow obstructions.
- Redundancy Mismatch: When operating in a redundant pair, verify that both units share identical input supply characteristics and are properly latched into the redundancy-capable carrier slots.