Description
Core Product Summary
The Honeywell TC-FPCXX2 is a standard, non-redundant AC power supply module used in Honeywell Experion PKS C200/C200E control system configurations. It supplies the internal power rails required by the controller chassis and its installed modules.
The unit supports selectable AC input ranges of 85–132 VAC or 170–265 VAC, allowing it to operate with nominal 120 VAC or 240 VAC sources. It is installed at the left end of the controller chassis and does not occupy a standard I/O slot.
The associated order number 97284971-B01 is listed for this model. The TC-FPCXX2 should not be confused with the TC-FPDXX2, which is the corresponding DC-input power supply variant.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Honeywell |
| Model | TC-FPCXX2 |
| Product type | Standard AC power supply |
| System family | Experion PKS / C200 controller system |
| Configuration | Non-redundant |
| Associated order number | 97284971-B01 |
| Input voltage range | 85–132 VAC or 170–265 VAC, selectable |
| Input power | 150 VA, 92 W |
| Maximum inrush current | 15 A |
| Input frequency | 47–63 Hz |
| Maximum total output power | 70 W at 60 °C |
| Backplane output — 1.2 VDC | 1.5 A maximum |
| Backplane output — 3.3 VDC | 4 A maximum |
| Backplane output — 5.1 VDC | 10 A maximum |
| Backplane output — 24 VDC | 2.8 A maximum |
| Fuse protection | Non-replaceable, soldered fuse |
| Recommended input wiring | 14 AWG (approximately 1.4 mm²) |
| Dimensions (L × D × H) | 112 × 145 × 140 mm |
| Approximate weight | 1.1 kg |
| Mounting location | Left side of chassis; does not consume a slot |
The combined load across all four output rails must not exceed the 70 W total output rating.
Detailed Product Overview
AC Power Conversion for the Controller Chassis
The TC-FPCXX2 converts incoming AC power into the DC voltage rails required by the Honeywell controller backplane. These rails supply the electronic circuits of the processor and installed control-system modules.
Its selectable input range accommodates two nominal AC supply levels. The correct range must be selected to match the actual plant power source before the unit is placed into service.
Multiple Backplane Output Rails
The power supply provides four DC output rails:
- 1.2 VDC: Supports circuits requiring the lowest backplane voltage.
- 3.3 VDC: Supplies compatible low-voltage electronic circuitry.
- 5.1 VDC: Provides a principal backplane supply rail.
- 24 VDC: Supplies the corresponding backplane power requirements.
Each rail has a defined maximum current. The combined output load must remain within the module’s overall 70 W capacity at 60 °C. Power-budget calculations should account for the consumption of every module installed in the chassis.
Non-Redundant Power Configuration
The TC-FPCXX2 is a standard, non-redundant power supply. It provides the chassis power source in configurations designed around a single supply.
Applications requiring redundant power should use the appropriate Honeywell redundant power architecture rather than assuming that two standard TC-FPCXX2 units can be connected as a redundant pair.
Integrated Fuse Protection
The module incorporates a non-replaceable fuse soldered onto the assembly. This fuse is intended to reduce fire risk under short-circuit conditions; it should not be regarded as comprehensive protection against every overload condition.
If the power supply fails, inspect the connected load and chassis wiring as part of fault diagnosis. Do not attempt to bypass or replace the internal fuse without an approved repair procedure.

TC-FPCXX2

TC-FPCXX2
System Compatibility & Integration Requirements
The TC-FPCXX2 is associated with Honeywell’s Experion PKS C200/C200E controller and Series-A chassis power architecture.
| System component | Relationship |
|---|---|
| Honeywell Experion PKS | Control-system platform |
| C200/C200E controller | Associated controller family |
| Series-A chassis | Power-supply installation platform |
| TC-FXX042 | 4-slot chassis |
| TC-FXX072 | 7-slot chassis |
| TC-FXX102 | 10-slot chassis |
| TC-FXX132 | 13-slot chassis |
| TC-FXX172 | 17-slot chassis |
| TC-FPDXX2 | Corresponding DC-input, non-redundant power supply |
| TK- | Coated AC power supply variant |
Compatibility checks before replacement
- Confirm that the installed chassis uses the compatible Series-A power architecture.
- Verify that the required input source is AC rather than DC.
- Check the selected input voltage range against the plant supply.
- Calculate the combined DC load across all backplane rails.
- Confirm the module’s physical fit and chassis connection arrangement.
- Verify the exact part number and revision against the installed unit.
The TC-FPCXX2 and TC-FPDXX2 are not interchangeable without checking the power-source requirements: the former accepts AC input, while the latter is designed for DC input.
Dimensions, Mounting & Connection Notes
The TC-FPCXX2 measures approximately 112 × 145 × 140 mm and weighs about 1.1 kg.
It mounts on the left side of the compatible chassis and does not occupy a normal module slot.
Installation considerations:
- Isolate the AC supply before removing or installing the power supply.
- Confirm the input voltage selection before energizing the unit.
- Use the specified input wiring size and appropriate electrical protection.
- Check that the chassis grounding and power connections are secure.
- Verify the total load on the 1.2 V, 3.3 V, 5.1 V, and 24 V rails.
- Maintain adequate ventilation around the power supply.
- Follow the Honeywell installation procedure for the applicable chassis.
Frequently Asked Questions
Q1: What is the Honeywell TC-FPCXX2?
It is a standard, non-redundant AC power supply module for Honeywell Experion PKS controller chassis.
Q2: What is the input voltage range?
The input range is selectable between 85–132 VAC and 170–265 VAC.
Q3: What is the maximum output power?
The maximum combined output is 70 W at 60 °C. The individual output rails have separate current limits.
Q4: Which DC output voltages does it provide?
It provides 1.2 VDC, 3.3 VDC, 5.1 VDC, and 24 VDC backplane supplies.
Q5: Does the TC-FPCXX2 occupy a chassis slot?
No. It mounts on the left side of the compatible chassis and does not consume a standard module slot.
Q6: What is the difference between TC-FPCXX2 and TC-FPDXX2?
The TC-FPCXX2 accepts AC input, while the TC-FPDXX2 accepts DC input. Both belong to the standard, non-redundant power supply family.
Q7: Is the TC-FPCXX2 a redundant power supply?
No. It is a standard non-redundant model. Systems requiring redundancy need the corresponding redundant power supply configuration.
Q8: What should be checked when purchasing a replacement?
Verify the model, associated order number, hardware revision, AC input requirements, output ratings, and compatibility with the installed Honeywell chassis.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626