Core Product Summary (Brand / Model / Key Attributes)
The Honeywell TC-OAV081 is an 8-channel Analog Output Module designed for the Honeywell Experion PKS (Process Knowledge System) and C200/C300 Series A I/O chassis architecture. Operating within a standard Experion I/O rack, this output card converts digital control demand signals from the controller into 8 precision 0–10 VDC voltage or 4–20 mA current outputs to drive field control elements, such as control valve positioners, variable speed drives, I/P transducers, and dampeners.
Engineered for continuous industrial process control, the TC-OAV081 provides 8 galvanically isolated output channels featuring high-resolution D/A conversion, continuous loop-break diagnostic monitoring, configurable fail-safe hold/fallback states, and support for live online hot-swapping (Removal and Insertion Under Power – RIUP). The module holds Class I, Division 2 hazardous location certifications for demanding process environments.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer & Series | Honeywell / Experion PKS Series A I/O System |
| Model Number | TC-OAV081 |
| Module Type | 8-Channel Analog Output Module |
| Output Signal Modes | Configurable 0–10 VDC voltage / 4–20 mA DC current loop |
| Number of Channels | 8 isolated analog output channels |
| D/A Conversion | High-resolution 12-bit to 16-bit digital-to-analog conversion |
| Accuracy | ±0.1% of full scale at 25 °C |
| Load Resistance | Current mode: 0 Ω to 750 Ω; Voltage mode: >2000 Ω |
| Backplane Power | Powered via chassis backplane (350 mA @ 5 VDC) |
| External Loop Power | 24 VDC external supply required via Field Termination Assembly (FTA) |
| Isolation | Channel-to-backplane galvanic and optical isolation |
| Mounting Format | Direct insertion into Experion Series A I/O chassis card slots |
| Operating Temperature | 0 °C to 60 °C (32 °F to 140 °F) |
| Storage Temperature | -40 °C to 85 °C (-40 °F to 185 °F) |
| Relative Humidity | 5% to 95%, non-condensing |
| Hazardous Approvals | Class I, Division 2, Groups A, B, C, D compliant |
Detailed Product Overview
The Honeywell TC-OAV081 Analog Output Module serves as a core actuation node within the Honeywell Experion PKS process control platform. Applied across continuous manufacturing and utility process environments—including oil and gas refining, chemical manufacturing, power generation, and water treatment—the TC-OAV081 translates regulatory control loop outputs into precise physical positioning commands for final control elements.
At the hardware level, the TC-OAV081 features independent channel conditioning circuits and precision digital-to-analog (D/A) converters. Each channel can be configured independently for 0–10 V or 4–20 mA output modes depending on field actuator requirements. Integrated diagnostic routines continuously monitor field current loops for open-circuit wiring breaks, shorted outputs, or voltage supply drops, flagging immediate channel fault alarms in Experion Control Builder.
The TC-OAV081 plugs directly into assigned slots of an Experion Series A I/O chassis. Featuring full Removal and Insertion Under Power (RIUP) capability, maintenance personnel can extract and replace active modules live under power without interrupting adjacent I/O cards or causing backplane communications to drop.

TC-OAV081

TC-OAV081
Engineering Selection Highlights
- 8 Precision Output Channels: Delivers 8 isolated analog output channels in a single compact Experion Series A card profile.
- Configurable Signal Modes: Supports both 0–10 VDC voltage and 4–20 mA current loop output ranges per channel.
- RIUP Hot-Swap Capability: Supports Removal and Insertion Under Power for online module replacement without interrupting adjacent I/O modules.
- Integrated Field Line Monitoring: Continuously detects open-circuit loops, short circuits, and field supply voltage failures.
- Configurable Fail-Safe Modes: Allows individual channels to be programmed to hold last value or ramp to a predefined safety fallback value upon loss of controller communication.
- Hazardous Area Certified: Rated for Class I, Division 2 environments.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| System Chassis | Honeywell Experion Series A I/O Chassis | Plugs into standard Series A card slots on the chassis backplane. |
| Termination Assembly | Honeywell Field Termination Assembly (FTA) | Connects via multi-core cables to FTAs (e.g., TC-TBNH or screw terminal blocks). |
| Controller Platform | Experion C200 / C300 Controller | Receives output demand variables across the chassis backplane bus. |
| Field Loop Power | 24 VDC Regulated Field Power Supply | Connects at the FTA to drive 4–20 mA current loops across field loads. |
| Software Toolset | Experion Control Builder | Configures channel signal types (voltage/current), scaling, and fail-safe action parameters. |
Dimensions, Mounting & Connection Notes
- Mounting Method: Direct insertion into designated card slots of the Experion Series A I/O chassis; secured via top and bottom retention latches.
- Backplane Interface: High-density multi-pin connector engages with the chassis backplane to interface with system processors and power rails.
- Field Wiring Connection: Multi-core system cables route from the chassis backplane connector to external Field Termination Assemblies (FTAs) where field wiring terminates.
- Thermal Management: Requires standard forced-air cabinet ventilation to maintain ambient temperatures within the 0 °C to 60 °C (32 °F to 140 °F) operating range.
FAQ
What is the primary function of the Honeywell TC-OAV081?
The TC-OAV081 is an 8-channel analog output module for the Honeywell Experion PKS system, designed to drive field actuators using 0–10 V or 4–20 mA control signals.
How many output channels does the TC-OAV081 provide?
The module features 8 isolated analog output channels.
Does the TC-OAV081 support both voltage and current outputs?
Yes, individual channels can be software-configured for 0–10 VDC voltage or 4–20 mA current loop output signals.
Can the TC-OAV081 be hot-swapped under power?
Yes, the module supports Removal and Insertion Under Power (RIUP), allowing live online replacement.
What happens to outputs if controller communication is lost?
Each channel can be configured in Experion Control Builder to hold its last valid state or transition to a user-defined safety value (e.g., 0 mA or 4 mA) upon loss of communication.
Verification & Troubleshooting Notes
- Front Panel LED Diagnostics: Inspect status LEDs: OK (Green = Healthy, Red = Internal Hardware Failure) and individual channel fault indicators.
- Current Loop Troubleshooting: If an analog valve fails to respond, measure loop current at the Field Termination Assembly (FTA) using an in-series ammeter to verify output command execution.
- External Power Supply Check: Ensure the 24 VDC field supply connected to the FTA is active and delivering stable voltage within the required operating window.
- Card Retention: When replacing a card, seat the module firmly into the chassis guide frame until top and bottom latches click into place to ensure proper backplane contact.