Description
Core Product Summary
The Honeywell TC-TAON11 is a redundant Analog Output Input/Output Termination Assembly (IOTA) for the Honeywell Experion Series C I/O architecture. It is the 12-inch (304 mm) field-termination assembly used with the CC-PAON01 Analog Output module, which provides 16 standard 4-20 mA outputs without HART communication.
The TC-TAON11 holds the I/O module and provides the field-wiring interface, signal terminations, and power distribution for the analog output channels. Its redundant configuration supports installation of a second CC-PAON01 module directly on the IOTA, without external redundancy cabling or a separate redundancy control device.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Honeywell |
| Model number | TC-TAON11 |
| Product type | Analog Output IOTA (Input/Output Termination Assembly) |
| I/O system | Honeywell Experion Series C I/O |
| Companion I/O module | CC-PAON01, Analog Output 16-point without HART |
| Configuration | Redundant |
| IOTA size | 12 inches (304 mm), nominal |
| Circuits supported | 16 analog output circuits |
| Output signal | 4-20 mA |
| HART support | No; CC-PAON01 is a non-HART analog output module |
| Redundancy method | Second IOM installed directly on the IOTA |
| Field wiring capacity | Up to 12 AWG / 2.5 mm² stranded wire |
Engineering Selection Highlights
- The TC-TAON11 is the redundant, 12-inch IOTA specifically listed for the CC-PAON01 analog output module; it is not the 6-inch non-redundant CC-TAON01 assembly.
- It supports 16 channels of 4-20 mA output, so it suits field devices that accept a standard current-loop command signal but do not require HART communication.
- Redundancy is implemented by adding a second CC-PAON01 IOM to the same IOTA, eliminating the need for external redundancy cabling or a separate redundancy controller.
- The IOTA receives power from the 24 VDC bus on the IOTA carrier and distributes field power through the assembly, reducing separate marshalling requirements.
- Series C field connectors accept up to 12 AWG / 2.5 mm² stranded wire, which should be checked against field-cable and terminal design.
- For applications requiring HART outputs, the CC-PAON01/TC-TAON11 combination is not the appropriate selection; Honeywell provides separate HART-capable analog output modules and IOTAs.

TC-TAON11

TC-TAON11
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| I/O module | Honeywell CC-PAON01 Analog Output, 16-point without HART | The TC-TAON11 is the redundant IOTA for this module. |
| I/O architecture | Honeywell Experion Series C I/O | The assembly is part of the Series C IOTA/IOM hardware arrangement. |
| Controller platform | Experion C300 controller and Series C I/O | The CC-PAON01 module is documented for the C300 controller and Series C I/O system. |
| Mounting | IOTA carrier with 24 VDC bussed power | The IOTA is screwed into the bussed power on the carrier. |
| Module installation | IOM plugs directly into the IOTA | The IOTA holds both the IOM and field-wiring connections. |
| Redundant configuration | Second CC-PAON01 IOM installed on the same IOTA | No external cabling or redundancy control device is required. |
| Field wiring | Up to 12 AWG / 2.5 mm² stranded wire | Applies to Series C field connectors. |
Dimensions, Mounting & Connection Notes
The TC-TAON11 is a 12-inch (304 mm nominal) redundant IOTA. It mounts on a Series C IOTA carrier and receives its power from the carrier’s 24 VDC bus. The CC-PAON01 I/O module plugs directly into the IOTA, which also provides the field-terminal interface.
The assembly uses Series C field connectors that accept up to 12 AWG / 2.5 mm² stranded wire. Series C hardware uses a vertical mounting arrangement and a two-level detachable terminal design for field wiring within the enclosure.
Detailed Product Overview
The Honeywell TC-TAON11 is the redundant field-termination assembly for Honeywell’s CC-PAON01 16-channel analog output module in the Experion Series C I/O family. In Honeywell’s Series C architecture, the IOTA holds the I/O Module and the field-wiring connections, while the IOM contains most of the electronics that perform the assigned I/O function. The TC-TAON11 therefore defines both the physical mounting arrangement and the field-interface point for the analog output channels.
The associated CC-PAON01 module provides 16 outputs of 4-20 mA. It is specified as an analog output module without HART, distinguishing it from Honeywell’s HART-capable analog output modules. The TC-TAON11 is the 12-inch redundant version of the required IOTA; the non-redundant equivalent is the 6-inch CC-TAON01.
A key integration feature of the Series C architecture is that redundancy is available directly on the IOTA. A second CC-PAON01 IOM can be added to the TC-TAON11 without external redundancy cabling or a separate redundancy control device. This makes the TC-TAON11 the correct termination assembly to specify when a CC-PAON01 output group is designed as redundant.
The IOTA receives power from the 24 VDC bus on the IOTA carrier and distributes field power through the assembly. This arrangement removes the need for separate field-power supplies and associated craft-wired marshalling for the analog output loops. The Series C design also combines the I/O module and field terminations in the same area, with the IOM plugging directly into the IOTA.
For output performance, the CC-PAON01 provides a directly settable current range of 0 mA or 2.9 mA to 21.1 mA, with a maximum resistive load of 800 ohms under the documented 22 VDC to 28 VDC supply condition. The output is specified with a calibrated accuracy of ±0.35% of full scale at 25°C, including linearity, and an output response that settles to within 1% of the final value within 80 ms. These characteristics should be considered when matching the output loop to actuator input requirements and loop-load calculations.
The TC-TAON11 uses the Series C field-terminal arrangement, which accepts up to 12 AWG / 2.5 mm² stranded wire. Its vertical, two-level detachable terminal design is intended to support cabinet wiring and maintenance access. When selecting or replacing this assembly, the essential checks are the CC-PAON01 module pairing, the redundant 12-inch IOTA configuration, and the 4-20 mA non-HART output requirement.
Applications & System Role
In an Experion PKS Series C installation, the TC-TAON11 provides the physical field-termination and mounting interface for a CC-PAON01 analog output module. The CC-PAON01 delivers high-level constant-current outputs to actuators and recording or indicating devices.
Typical fit scenarios include control-valve positioners, current-to-pressure converters, variable-speed drive references, and other final control elements that accept a 4-20 mA command signal. Because the CC-PAON01 is a non-HART analog output module, the TC-TAON11 is appropriate where standard current-loop outputs are required without HART communication.
The redundant IOTA arrangement is intended for output channels where continued operation through a second I/O module is part of the control-system design. Redundancy is established at the IOTA level by installing two IOMs, allowing the output function to be implemented without additional external redundancy wiring.
FAQ
What is the Honeywell TC-TAON11?
The Honeywell TC-TAON11 is a redundant, 12-inch Analog Output IOTA for the Honeywell Experion Series C I/O system.
Which I/O module does the TC-TAON11 support?
It supports the Honeywell CC-PAON01 Analog Output module, a 16-point 4-20 mA output module without HART.
Is the TC-TAON11 redundant or non-redundant?
It is the redundant IOTA. The non-redundant equivalent for the CC-PAON01 is the CC-TAON01, a 6-inch IOTA.
How many output channels does the TC-TAON11 support?
It supports 16 analog output circuits through the associated CC-PAON01 module.
What output signal does the supported module provide?
The CC-PAON01 provides standard 4-20 mA current outputs.
Does the TC-TAON11 support HART?
No. The CC-PAON01 module paired with the TC-TAON11 is a non-HART analog output configuration.
How is redundancy implemented?
A second CC-PAON01 I/O module is installed directly on the same IOTA; no external redundancy cabling or redundancy control device is required.
What wire size can be terminated on the IOTA?
Series C field connectors accept up to 12 AWG / 2.5 mm² stranded wire.